User Guide for KMC CONTROLS models including: TRF-5901C-AFMS TrueFit Airflow Measurement System, TRF-5901C-AFMS, TrueFit Airflow Measurement System, Airflow Measurement System, Measurement System, System
Controller: TrueFit Airflow Measurement System, BACnet AAC, Clock, MSTP | KMC Controls
Browse all of our KMC products today and find the right fit for you!
File Info : application/pdf, 9 Pages, 2.63MB
DocumentDocumentAirflow Measurement System Selection Guide For estimation, try the AFMS Selection Assistant interactive form, a companion to this selection guide. Contents Introduction ...............................................................................1 Example Diagrams.......................................................................2 Selecting an AFMS Controller (with inclinometer).............................4 Selecting Flow Pickup Tubes.........................................................5 Selecting Pressure Transducers ....................................................6 Selecting the Mixed Air Temperature Sensor ...................................7 Selecting the Outside Air Temperature Sensor .................................7 Selecting the Return Air Temperature Sensor ..................................7 Selecting a Proportional Actuator ..................................................8 Selecting an HLO-1050 Linkage Kit ................................................8 Selecting Tools for Configuration and Operation...............................9 Support .....................................................................................9 Introduction The TrueFit Airflow Measurement System (AFMS) reliably provides accurate outside, return, and supply airflow data for monitoring and control. The system delivers accurate, repeatable results on any type of equipment, without the traditionally expected mechanical limitations, performance issues, or ongoing maintenance issues. The system consists of the following components, installed on an AHU, RTU, or unit ventilator: · One controller with airflow measurement programming · One inclinometer (included with the controller) mounted on a horizontal out- side or return air damper blade · If only vertical damper blades, one HLO-1050 Linkage Kit · At least two airflow pickup tubes installed in a pitot array duct on the supply fan inlet, in the supply air duct · If a TRF-5901C(E)-AFMS is used, one pressure transducer · If pressure assist measurements are needed (see Considerations on page 4), one additional pressure transducer, connected to two additional flow pickup tubes that are mounted on both sides of either the outside air damper or return air damper. · Three temperature sensors for outside, mixed, and return air · One proportional actuator mounted on the damper shaft KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com Example Diagrams Standard Application OAD (Outside Air Damper) PA (Pressure Assist) Application 2 RAD (Return Air Damper) PA (Pressure Assist) Application 3 Selecting an AFMS Controller (with inclinometer) Considerations Does the unit have any of these non-standard features?: · A relief fan that is variable speed, or is operating independent of mixed air damper position · A return fan that is not controlled by a supply fan / return fan offset · A bypass damper utilized to bypass a heat recovery system · Return VAV boxes · Supply to return bypass (typically found in zone damper applications, or where a bypass damper is used in place of a VFD) · Outside and return air dampers that modulate independently · More than one outside air damper If yes, the pressure of the unit's mixed and/or return air sections may change. In that case, select a TRF-5901C(E)-AFMS for (OAD or RAD) pressure assist measurements. TRF-5901C-AFMS (inclinometer included) TRF-5901CE-AFMS (inclinometer included) Is customizable programming needed? If the capability to program the controller for other functions in addition to airflow measurement is needed, select a TRF-5901C(E)-AFMS. The inputs and outputs of a TRF9311C(E)-AFMS will be used by the components of the airflow measurement system. Therefore, it must be solely dedicated to airflow measurement. TRF-9311C-AFMS (inclinometer included) Where will the controller be mounted? If the controller will be mounted more than 20 feet from the location of the airflow pickup tubes (see Selecting Flow Pickup Tubes on page 5), select a TRF-5901C(E)-AFMS. A pressure transducer can be mounted closer to the pickup tubes, then wired over a greater distance to the controller. (See Selecting Pressure Transducers on page 6.) TRF-9311CE-AFMS (inclinometer included) MODEL APPLICATIONS INPUTS OUTPUTS FEATURES Customizable Pressure Sensing Real Time Clock (RTC) Network Airflow Measurement Programming TRF5901CAFMS 10 total: · 2 analog (room sensor port) · 8 universal 8 universal: · Software configurable as analog or inputs (software binary configurable as · Override TRF- analog, binary, or boards give 5901CE- accumulator on additional AFMS RTU terminals) options TRF9311CAFMS TRF9311CE- AFMS AHU unit ventilator 1 air pressure sensor and 8 (total) standard: · 2 analog (room sensor port) · 6 universal inputs (software configurable as analog, binary, or accumulator on 10 total: · 6 triacs (binary) · 4 universal (software configurable as analog or binary) terminals) 4 External Integrated MS/TP Ethernet standard airflow measurement, OAD pressure assist, and RAD pressure assist application programming MS/TP Ethernet standard airflow measurement application Selecting Flow Pickup Tubes Options for Installation Location The array of supply airflow pickup tubes can be installed in one of two places: · At the supply air fan inlet · At least six straight duct widths down the supply air duct If pressure assist measurements are needed (see Considerations on page 4) two additional flow pickup tubes must be installed, one on either side of the outside air damper (for OAD pressure assist) or return air damper (for RAD pressure assist). Arrangement in Parallel Array The pickup points must be arranged in a parallel array that evenly covers the area of the supply air duct or fan inlet, similar to what is show below: Determining the Number of Pickup Points 1. Measure the duct or fan inlet: · For a rectangular or square duct, measure the length of the longest side. · For a circular duct or the supply fan inlet, measure the diameter. 2. Consult one of the tables below to determine the total minimum number of pickup points needed: FOR A RECTANGULAR OR SQUARE DUCT If the longest side is less than Total minimum number of or equal to: pickup points needed is: 4 inches 2 15 inches 3 24 inches 4 35 inches 5 48 inches 6 63 inches 7 80 inches 8 99 inches 9 100 inches or greater 10 traverse on round and square duct areas FOR A CIRCULAR DUCT OR THE FAN INLET Duct diameter Total minimum number of pickup points needed: <10 inches 6 10 inches 10 rectangular duct array rounodundducdtuacrtray 5 Selecting the Tubes Select multiple airflow pickup tubes (at least two) from below that are the maximum length that will fit in the space and total to at least the minimum number of pickup points needed: SSS-101x models have 3/16" connections for 1/4" OD polyethylene tubing and flat mounting flanges for installation in ducts (or on fan inlets that have struts): SSS-111x models have 3/16" connections for 1/4" OD polyethylene tubing and right-angled mounting feet for installation on the supply air fan bell. SSS-1012 SSS-1013 SSS-1014 SSS-1015 One pickup point, 80 mm (about 3") length tubes Two pickup points, 137 mm (about 5.5") length tubes Three pickup points, 195 mm (about 8") length tubes Four pickup points, 252 mm (about 10") length tubes Single mounting foot: SSS-1112 SSS-1113 SSS-1114 One pickup point, 80 mm (about 3") length tubes Two pickup points, 137 mm (about 5.5") length tubes Three pickup points, 195 mm (about 8") length tubes Dual mounting feet: SSS-1115 SSS-1116 SSS-1117 Four pickup points, five sections*, 315 mm (about 13") length tubes Five pickup points, six sections*, 395 mm (about 15.5") length tubes Six pickup points, seven sections*, 457 mm (about 18") length tubes *NOTE: The extra section connects the tubes to the second mounting foot, which mounts to the other end of the fan bell (or a midway strut). Selecting Pressure Transducers NOTE: Select pressure transducers for a TRF-5901C(E)-AFMS only. TRF-9311C(E)-AFMS have differential air pressure ports, so a pressure transducer is not necessary to connect the flow pickup tubes. For the standard airflow measurement application, select one pressure transducer. For airflow measurement applications with pressure assist, select two pressure transducers. MODEL NUMBER TPE-1475-21 TPE-1475-22 INPUT PRESSURE RANGES (SELECTABLE) 2 to +2" or 0 to 2" wc (0.5 to +0.5 kPa or 0 to 0.5 kPa) 10 to +10 or 0 to 10 wc (2.5 to +2.5 kPa or 0 to 2.5 kPa) 6 Selecting the Mixed Air Temperature Sensor Averaging sensors are necessary to minimize errors due to stratification or poor airflow mixing in the mixed air chamber. It is recommended to install the largest averaging sensor that the equipment will accommodate. Copper sensors are recommended when the mixed air section is easily accessible. If not easily accessible, a cable sensor can be used. MODEL SENSOR TYPE PROBE TYPE PROBE LENGTH ENCLOSURE CONNECTIONS* STE-1411 STE-1412 STE-1414 STE-1413 STE-1415 Duct, Averaging STE-1416 STE-1417 6 feet (1.8 m) Copper, bendable 12 feet (3.6 m) 20 feet (6.1 m) 24 feet (7.3 m) Flexible, FT-6 plenum-rated cable 6 feet (1.8 m) 12 feet (3.6 m) 24 feet (7.3 m) Plastic, UL94-V0, IP65 (NEMA 4X) ABS FT-6 plenum-rated, 22 AWG wire leads Selecting the Outside Air Temperature Sensor For units with accessible outside air hoods, select an STE-1412 12-foot bendable copper averaging sensor. For units with inaccessible outside air hoods, or for outside air ducts, select an STE-1404 duct-mounted 12-inch probe with enclosure. (For sheltered tight fits, an STE-1405 duct-mounted 4-inch probe without enclosure can be used.) MODEL SENSOR TYPE STE-1405 STE-1404 Duct, Rigid probe OA Hoods, STE-1412 Averaging PROBE TYPE PROBE LENGTH ENCLOSURE 1/4-inch OD 4 inches (100 mm) stainless-steel 12 inches (300 mm) Copper, bendable 12 feet (3.6 m) None (mounting bracket only) Plastic, UL94-V0, IP65 (NEMA 4X) ABS CONNECTIONS 10-ft. FT-6 plenum-rated, 22 AWG cable PVC insulated, 22 AWG, wire leads FT-6 plenum-rated, 22 AWG, wire leads Selecting the Return Air Temperature Sensor When possible, select an STE-1404 duct-mounted 12-inch probe with enclosure. For sheltered tight fits, an STE-1405 ductmounted 4-inch probe without enclosure can be used. MODEL SENSOR TYPE PROBE TYPE PROBE LENGTH ENCLOSURE CONNECTIONS STE-1405 STE-1404 Duct, Rigid probe 1/4-inch OD stainless-steel 4 inches (100 mm) 12 inches (300 mm) None (mounting bracket only) Plastic, UL94-V0, IP65 (NEMA 4X) ABS 10-ft. FT-6 plenum-rated, 22 AWG cable PVC insulated, 22 AWG, wire leads 7 Selecting a Proportional Actuator The unit must have a proportional damper actuator for the AFMS to modulate the damper as needed. If the unit does not have a proportional damper actuator already, select one. MODEL MEP-4552 MEP-4952 TORQUE* in-lb. (N·m) 45 (5) 90 (10) PROPORTIONAL CONTROL FEEDBACK 0-10 or 2-10 VDC 0/1-5 or 0/2-10 VDC MEP-7552 180 0-10 VDC, 2-10 VDC, (20) or 4-20 mA *Use the online Actuator Calculator to assist with torque requirements. FAILSAFE Selecting an HLO-1050 Linkage Kit The AFMS controller's inclinometer must be mounted on a horizontal-axis damper blade. For units with vertical-axis damper blades, select an HLO-1050 Linkage Kit. The linkages transfer the damper motion to a surface with a horizontal axis (the kit's inclinometer crankarm), on which inclinometer can then be mounted. The kit's damper blade crankarm can be mounted to a damper blade or on a jackshaft using its included jackshaft coupler and V-bolt. If the kit's axle mount shaft cannot be mounted on a unit's damper frame (such as when mounting in a duct), select a VTD-0903 right-angle bracket in addition to the kit. damper blade mounting jackshaft mounting damper blade mounting in a duct with VTD-0903 8 Selecting Tools for Configuration and Operation The rows in the table below list the processes to set up and operate an AFMS. The columns present the KMC Controls tools that can be used to complete the processes. Consult the table to determine which tools can complete each process and for which AFMS applications. The user interface and setup requirements of each tool varies. For more information, see each tool's product pages and documents. PROCESSES Selecting the application Configuring communication Setting AFMS parameters Calibrating sensors BAC5051(A)E router Ethernet controller1 served web pages CONFIGURATION TOOLS ConquestTM NetSensor KMC ConnectTM or TotalControlTM KMC ConvergeTM for Niagara Workbench KMC Commander®2 KMC Connect LiteTM (NFC) app3 Starting Learning Mode Controlling airflow Monitoring operation & faults 1 Ethernet "E" models with the latest firmware can be configured with a web browser from pages served within the controller. 2 KMC Commander's AFMS module currently supports the standard AFMS application only. 3 Near Field Communication via enabled smart phone or tablet running the KMC Connect Lite app. Support Additional resources for product specifications, installation, configuration, application, operation, programming, upgrading and much more are available on the KMC Controls web site (www.kmccontrols.com). Log in to see all available files. © 2024 KMC Controls, Inc. Specifications and design su9bject to change without notice AG230816B