Input DC (PV side) |
---|
Recommended max. PV array size | 16 kW | 20 kW | 24 kW | 30 kW |
Max. usable PV input power | 12.8 kW | 16 kW | 19.2 kW | 24 kW |
Max. input voltage | 1000 V |
Rated voltage | 550 V |
Start-up voltage | 160 V |
MPPT voltage range | 200-850 V |
Max. input current | 20 A / 40 A | 40 A / 40 A | 50 A / 50 A | 50 A / 50 A |
Max. short circuit current | 30 A / 50 A | 40 A / 40 A | 50 A / 50 A | 50 A / 50 A |
MPPT number / Max. input strings number | 2 / 3 | 2 / 4 |
Battery |
---|
Battery type | Li-ion / Lead-acid |
Battery voltage range | 40 - 60 V |
Max. charge / discharge current | 180 A | 220 A | 250 A | 290 A |
Communication | CAN / RS485 |
Output AC (Grid side) |
---|
Rated output power | 8 kW | 10 kW | 12 kW | 15 kW |
Max. apparent output power | 8 kVA | 10 kVA | 12 kVA | 15 kVA |
Rated grid voltage | 3/N/PE, 220 V / 380 V; 3/N/PE, 230 V / 400 V |
Rated grid frequency | 50 Hz / 60 Hz |
Rated grid output current | 12.2 A / 11.5 A | 15.2 A / 14.4 A | 18.2 A / 17.3 A | 22.8 A / 21.7 A |
Max. output current | 12.2 A / 11.5 A | 15.2 A / 14.4 A | 18.2 A / 17.3 A | 22.8 A / 21.7 A |
Power factor | > 0.99 (0.8 leading - 0.8 lagging) |
THDi | < 3% |
Input AC (Grid side) |
---|
Input voltage range | 323 - 460 V |
Max. input current | 18.3 A / 17.3 A | 22.8 A / 21.7 A | 27.3 A / 26.0 A | 34.2 A / 32.5 A |
Frequency range | 45 - 55 Hz / 55 - 65 Hz |
Input Generator |
---|
Max. input power | 8 kW | 10 kW | 12 kW | 15 kW |
Max. input current | 12.2 A | 15.2 A | 18.2 A | 22.8 A |
Rated input voltage | 3/N/PE, 220 V / 380 V; 3/N/PE, 230 V / 400 V |
Rated input frequency | 50 Hz / 60 Hz |
Output AC (Back-up) |
---|
Rated output power | 8 kW | 10 kW | 12 kW | 15 kW |
Max. apparent output power | 12.2 A | 15.2 A | 18.2 A | 22.8 A |
Back-up switch time | 2 times of rated power, 10 s < 10 ms |
Rated output voltage | 3/N/PE, 220 V / 380 V; 3/N/PE, 230 V / 400 V |
Rated frequency | 50 Hz / 60 Hz |
Rated output current | 12.2 A / 11.5 A | 15.2 A / 14.4 A | 18.2 A / 17.3 A | 22.8 A / 21.7 A |
Max. continuous output current | 12.2 A / 11.5 A | 15.2 A / 14.4 A | 18.2 A / 17.3 A | 22.8 A / 21.7 A |
Max. continuous AC passthrough current | 50 A |
THDv (@linear load) | < 3% |
Efficiency |
---|
Max. efficiency | 97.5% |
EU efficiency | 97.0% |
BAT charged by PV / AC max. efficiency | 95.0% / 94.4% |
BAT discharged to AC max. efficiency | 94.5% |
Protection |
---|
Anti-islanding protection | Yes |
Output over current protection | Yes |
Short circuit protection | Yes |
DC reverse-polarity protection | Yes |
Surge protection | DC Type II / AC Type II (Optional) |
Integrated AFCI 2.0 | Optional |
Integrated DC switch | Yes |
General Data |
---|
Dimensions (W x H x D) | 430 x 660 x 305 mm |
Weight | 42 kg |
Topology | Non-isolated |
Self-consumption (night) | < 30 W |
Operating ambient temperature range | -40 ~ +60°C |
Relative humidity | 0 - 100% |
Ingress protection | IP66 |
Noise emission (typical) | < 65 dB(A) |
Cooling concept | Intelligent fan-cooling |
Max. operation altitude | 4000 m |
Grid connection standard | NRS 097-2-1, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, SriLanka, EN 50438L, Vietnam, PEA, MEA |
Safety / EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-3 |
Features |
---|
DC connection | MC4 Quick connection plug (PV) & Screw terminal (Battery) |
AC connection | Screw terminal |
Display | 7.0" LCD display & Bluetooth + APP |
Communication | CAN, RS485, Ethernet, Optional: Wi-Fi, Cellular, LAN |