FV4C Fan Coil for Puron® Refrigerant

Installation Instructions

Model Numbers: 002, 003, 005, 006

ℹ️ NOTE: Read the entire instruction manual before starting the installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.

Recognize safety information. When you see this symbol ⚠️ on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

⚠️ WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.

❗ CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.

INTRODUCTION

Model FV4C Fan Coil units are designed for flexibility and can be used for upflow, horizontal, or downflow (kits required on manufactured and mobile home) applications. These units are designed specifically for Puron® refrigerant (R-410A) and must be used only with Puron air conditioners and heat pumps as shipped.

These units are designed to meet the low air leak requirements currently in effect. Because of this, the units need special attention in the condensate pan and drain connection area and when brazing tubing.

These units are available for application in systems of 18,000 through 60,000 Btuh nominal cooling capacities. Factory-authorized, field-installed electric heater packages are available in 5 through 30 kW. See Product Data for available accessory kits.

INSTALLATION

Procedure 1 — CHECK EQUIPMENT

Unpack unit and move to final location. Remove carton taking care not to damage unit.

Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.

Procedure 2 - MOUNT FAN COIL

Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.

IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require a field-supplied secondary condensate pan to be installed under the entire unit. Some localities may allow the alternative of running a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.

When installing any fan coil over a finished ceiling and/or living area, installation of a secondary drain pan under entire unit to avoid damage to ceiling is recommended.

FV4C Fan Coils can be installed for upflow and horizontal-left applications as factory shipped. Units can be installed for horizontal-right applications with field modifications. Units may be converted for downflow applications using factory-authorized accessory kits.

ℹ️ NOTE: To ensure proper drainage for horizontal installations, unit must be installed so it is within 1/8 in. (3.2mm) level of the length and width of unit.

A. Upflow Installation

If return air is to be ducted, install duct flush with floor. Set unit on floor over opening. Only use return-air opening provided. All return air must pass through the coil. (See Fig. 2.)

Fig. 2 - Slope Coil Unit in Upflow Application

Procedure 3 – AIR DUCTS

Connect supply-air duct over outside of 3/4-in. (19mm) flange provided on supply-air opening. Secure duct to flange with proper fasteners for type of duct used, and seal duct-to-unit joint.

Duct connection flanges are provided on unit air discharge connection. When using FV4C units with 20-, 24-, and 30-kW electric heaters, maintain a 1-in. (25mm) clearance from combustible materials to discharge plenum and ductwork for a distance of 36 in. (914mm) from unit. Use accessory downflow base to maintain proper clearance on downflow installations.

Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.

Ductwork Acoustical Treatment

Metal duct systems that do not have a 90° elbow and 10 ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining.

As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association Standards 90A or B as tested by UL Standard 181 for Class 1 air ducts.

Procedure 4 - ELECTRICAL CONNECTIONS

On units with a factory installed disconnect with pull-out removed, service and maintenance can be safely performed on only the load side of the control package.

⚠️ WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Field wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull-out is removed. Service and maintenance to incoming wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off.

A. Line-Voltage Connections

If unit contains an electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation Instructions.)

For units without electric heat:

  1. Connect 208/230v power leads from field disconnect to yellow and black stripped leads.
  2. Connect ground wire to unit ground lug.

Check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation.

⚠️ WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.

B. 24-V Control System Connections to Unit Printed-Circuit Board (PCB)

Refer to unit wiring instructions for recommended wiring procedures. Use No. 18 AWG color-coded, insulated (35°C minimum) wires to make low-voltage connections between thermostat and unit. If thermostat is located more than 100 ft (30m) from unit (as measured along the low-voltage wires), use No. 16 AWG color-coded, insulated (35°C minimum) wires. PCB is circuited for single-stage heater operation. When additional heater staging is desired using outdoor thermostats or Intelligent Heat Staging, remove Jumper J2 on PCB to enable staging.

Connect low-voltage leads to thermostat and outdoor unit. (See Fig. 9, 10, 11, or 12.)

Fig. 9 - FV4C Fan Coil Wiring with 1-Speed Air Conditioner
Fig. 10 - FV4C Fan Coil Wiring with 2-Speed Air Conditioner
Fig. 11 - FV4C Fan Coil Wiring with 1-Speed Heat Pump
Fig. 12 - FV4C Fan Coil Wiring with 2-Speed Puron (R-410A) Refrigerant Heat Pump

Procedure 5 — REFRIGERANT TUBING CONNECTION AND EVACUATION

Use accessory tubing package or field-supplied tubing of refrigerant grade. Insulate entire suction tube if field-supplied tubing is used. Tubing package has an insulated suction tube. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow control device.

When tubing package is used and sweat connections are made within 60 sec, coil and tubing system does not require evacuation. Always evacuate coil and field-supplied tubing to 500 microns before opening outdoor unit service valves.

❗ CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.

A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent damage to the unit surface and condensate pan fitting caps.

Units have sweat suction and liquid tube connections. Make suction tube connection first.

  1. Cut tubing to correct length.
  2. Insert tube into sweat connection on unit until it bottoms.
  3. Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder (materials which melt below 800°F).

Consult local code requirements.

Procedure 6 - CONDENSATE DRAIN

To connect drains the cap openings must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the disk. Clean the edge of the opening if necessary and install the condensate line. Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit.

❗ CAUTION

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.

The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.

Units are equipped with primary and secondary 3/4-in. (19mm) FPT drain connections. For proper condensate line installation see Fig. 2, 4, 5, 6, and 8.

To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly-sized condensate traps. (See Fig. 14 and 16.) Factory-approved condensate traps are available. Be sure to install plastic push-in plugs in unused condensate drain fittings. It is recommended that PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten plus 1-1/2 turns. Use pipe dope.

❗ CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.

Shallow running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 15.)

DO NOT USE SHALLOW RUNNING TRAPS!

Fig. 15 - Insufficient Condensate Trap

ℹ️ NOTE: When connecting condensate drain lines avoid blocking filter access panel. Prime both primary and secondary condensate traps after connecting to drain pan.

ℹ️ NOTE: If unit is located in or above a living space where damage may result from condensate overflow, a field-supplied external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan.

Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4-in. (19mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing, or water damage will occur.

Install traps in the condensate lines as close to the coil as possible. (See Fig. 16.) Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area.

Fig. 14 - Recommended Condensate Trap
Fig. 16 - Insufficient Condensate Trap

Condensate drain lines should be pitched downward at a minimum of 1 in. (25mm) for every 10 ft. (3m) of length. Consult local codes for additional restrictions or precautions.

Procedure 7 - UNIT START-UP

Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

Procedure 8 - EASY SELECT CONFIGURATION TAPS

Easy Select™ taps are used by the installer to configure a system. The ECM motor uses the selected taps to modify its operation to a pre-programmed table of airflows. (See Table 3 and 4.) Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need for de-humidification. (See Fig. 17 and 18.)

Fig. 17 - Detail of FV4C Printed-Circuit Board
Fig. 18 - Detail of FV4C Printed-Circuit Board

The FV4C Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used.

A. AUX HEAT KW/CFM - Select heater range for size of electric heater installed

Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked with a range of heaters for which airflow, also marked, is approved. For increased comfort select the narrowest kW range matching the heater size, for example, 0-10 for 10-kW heater. This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation. (See Table 5 and 6 for airflow delivery and minimum CFM.) Note that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ECM motor will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved. (See Fig. 17, A as indicated.)

B. AC/HP SIZE - Select system size installed

The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased. Installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes. (See Fig. 17, B as indicated.)

C. SYSTEM TYPE - Select system type installed AC or HP

The type of system must be selected:

  1. AC - Air conditioner
  2. HP-COMFORT - Heat Pump Comfort provides approximately 315 CFM per ton for higher normal heating air delivery temperature. Provides approximately 350 CFM per ton cooling airflow for good humidity removal.
  3. HP-EFF - Heat Pump Efficiency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton. The factory setting is AC. (See Fig. 17, C as indicated.)

D. AC/HP CFM ADJUST - Select Medium, Low, or High Airflow

To provide airflow at rates described above, the AC/HP ADJUST select is factory set to the nominal (nom) tap. The adjust selections HI/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15% airflow over nominal unit size selected and LO provides 10% airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal. (See Fig. 17, D as indicated.)

E. ON/OFF DELAY - Select desired time delay profile

ℹ️ NOTE: Delay selections are active in cooling and heat pump heating modes only. Auxiliary heating modes have a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden.

Four motor operation delay profiles are provided to customize and enhance system operation. (See Fig. 17, E as indicated)

Selection options are:

  1. The standard 90 sec off delay (Factory setting) at 100% airflow.
  2. No delay option used for servicing unit or when a thermostat is utilized to perform delay functions.
  3. A 30 sec on delay with no airflow/90 sec off delay at 100% airflow profile is used when it is desirable to allow system coils time to heat-up/cool-down in conjunction with the airflow.
  4. ENH, enhanced selection, provides a 30 sec on delay with no airflow/ plus 150 sec at 70% airflow/ no off delay for added comfort. This profile will minimize cold blow in heat pump operation and could enhance system efficiency.

F. CONTINUOUS FAN - Select desired fan speed when thermostat is set on continuous fan

ℹ️ NOTE: If installed with a 2-speed outdoor unit, do not select HI speed continuous fan. If HI is selected, low speed compression will also run HI speed possibly resulting in insufficient dehumidification.

  1. LO speed - factory setting, 50% cooling mode airflow.
  2. MED speed - move connector to MED, 80% cooling mode airflow.
  3. HI speed - move connector of HI, 100% cooling mode airflow. (See Fig. 17, F as indicated.)

G. Low-Voltage Circuit Fusing and Reference

The low-voltage circuit is fused by a board-mounted 5-amp automotive fuse placed in series with the transformer SEC2 and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at SEC1 connected to metal standoff marked with ground symbol.

H. Basic Fan Coil Configuration

The following basic configuration of the fan coil will provide ARI rated performance of the heat pump:

  1. AUX HEAT KW/CFM - Select the heater range for the size electric heater installed.
  2. AC/HP SIZE - Select system size installed.
  3. SYSTEM TYPE - Select system type HP-EFF.
  4. AC/HP CFM ADJUST - Select NOM.
  5. ON/OFF DELAY - Select 0/90 profile.
  6. CONTINUOUS FAN - Select desired fan speed when thermostat is set to continuous fan.

I. COMFORT OPTIONS - WARMER HEATING AND SUPER DEHUMIDIFY (See Fig. 21 for Quick Reference Guide)

The FV4C Fan Coil provides better than average humidity control and heated air temperature. This configuration will improve the comfort provided by the heat pump system if more humidity removal or if warmer heating air is desired. While providing this improved comfort, the heat pump system will operate efficiently, but not at the published HSPF or ARI SEER efficiency.

The following fan coil configuration is recommended for maximum heating and cooling/dehumidifying comfort: (See Fig. 17.)

  1. AUX HEAT KW/CFM - Select narrowest heater range to match size of electric heater installed (skip this step if no heater is installed).
  2. AC/HP SIZE - Select system size installed.
  3. SYSTEM TYPE - Select system type HP-COMFORT (for heat pump system) or AC (for air conditioner system).
  4. AC/HP CFM ADJUST - Select LO.
  5. ON/OFF DELAY - Select ENH profile.
  6. CONTINUOUS FAN - Select desired fan speed when thermostat is set to continuous fan.
  7. If the fan coil is installed with Intelligent Heat Staging capable electric heaters, remove jumper J2. (See Fig. 17.)
  8. ℹ️ NOTE: If configuring to run warmer heating, do not remove jumper J2 when using 5-, 8-, or 10-kW heaters.
  9. Remove jumper J1 to activate dehumidify modes.
  10. Wire low voltage connections as shown in Fig. 9, 10, 11, or 12.
  11. Configure Thermidistat (or capable zoning system) following its installation instructions for enhanced dehumidification and SuperComfort/Perfect Heat operation.

This configuration provides the following comfort enhancements:

  1. A 30 second blower on delay with 150 seconds at 70% airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100% airflow reducing the cold blow sensation at start up in heating and allowing the indoor coil to more quickly reach wet coil operating conditions in cooling.
  2. No blower off delay eliminates cold blow which may be associated with running the blower after shut down of the compressor and avoids re-evaporation of condensed moisture after cooling/dehumidifying operation.
  3. Lower airflow while the compressor is running to reduce draft effects and increase heating air temperature and improved humidity control during cooling operation.
  4. Intelligent Staging of the electric heater elements to more closely match heating load requirements and provide more consistent heating air temperatures.

Procedure 9 — ACCESSORY INSTALLATION

A. Accessory Electric Heaters

Electric heaters may be installed with the FV4C Fan Coil per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits.

ℹ️ NOTE: Units installed without electric heat should have a sheet metal block-off plate covering the heater opening. This reduces air leakage and formation of exterior condensation.

B. Auxiliary Terminals

The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24-vac signal whenever the G terminal is energized. (See Fig. 17 and 18.) During Super Dehumidify and SuperComfort / Perfect Heat modes, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of these operating modes, do not use these terminals to control accessories. See Electronic Air Cleaner and Humidifier sections for further information.

C. Electronic Air Cleaner Connections

The AUX1 and AUX2 terminals are not always energized during blower operation, as described above. When using an electronic air cleaner with the FV4C Fan Coil, use Airflow Sensor Part No. KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the fan coil blower is operating.

D. Humidifier/Humidistat Connections

Easy Select Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat. (See Fig. 19.) These terminals are energized with 24vac when G thermostat signal is present. (See Fig. 20.) Alternately, the 24-vac signal may be sourced from the W and C terminal block connections when electric heaters are used as primary heating source. When using a Thermidistat™ Control, Zone Perfect Plus or Comfort Zone II, the 24-vac signal may be sourced directly from the Thermidistat HUM terminal. (See Fig. 9, 10, 11, and 12.)

Fig. 19 - Humidifier Wiring
Fig. 20 - Humidistat Wiring for De-Humidify Mode

E. Dehumidify Capability with Standard Humidistat Connection

Latent capacities for systems using the FV4C Fan Coil are better than average systems. If increased latent capacity is an application requirement, the field wiring terminal block provides connection terminals for use of a standard humidistat. The FV4C Fan Coil will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80% of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100% of the selected cooling airflow. To activate this mode, remove Jumper J1 and wire in a standard humidistat. (See Fig. 20.)

F. Dehumidify and Super Dehumidify Capabilities

This model fan coil is capable of responding to a signal from indoor system control (Thermidistat, zoning control) to operate in comfort control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are available, and to see control set up instructions. No special setup or wiring of fan coil is required.

Procedure 10 – FV4C FAN COIL SEQUENCE OF OPERATION

The FV4C will supply airflow in a range which is more than twice the range of a standard fan coil. It is designed to provide nominal cooling capacities at a 50°F (10°C) evaporator temperature and the required airflow which enables it to match with 4 air conditioner or heat pump system sizes. Table 2 outlines the CFM range for the different FV4C Fan Coil sizes.

A. Continuous Fan

B. Cooling Mode - Single speed

C. Cooling Mode - Dehumidification

D. Cooling Mode - Super Dehumidify Operation (See Fig. 22 for Quick Reference Guide)

ℹ️ NOTE: The indoor control used, such as Thermidistat, must be capable of providing Super Dehumidify operation mode and control must be configured as outlined in its installation instructions. Consult indoor control literature to determine if control is capable of providing Super Dehumidify inputs and for configuration instructions.

If the indoor temperature is below the temperature set point and the humidity is above the humidity set point, the Thermidistat closes circuit R to O, opens circuits R to DH and R to G, and cycles circuit R to Y/Y2 (for single speed system R to Y1, or R to Y1 and Y/Y2 for 2-speed system).

The ECM motor reads the G signal to the fan coil while the heat pump is operating, (circuit R to Y/Y2 for single speed system, R to Y1 or R to Y1 and Y/Y2 for 2-speed system), closed (24 vac). If circuit R to G is closed (24 vac), the motor will deliver airflow at the full cooling or cooling plus dehumidify mode requested value. If circuit R to G is open (0 vac) for super dehumidify mode, the motor delivers reduced airflow to maximize the humidity removal of the system while minimizing over-cooling.

E. Electric Heat Heating Mode

F. Heat Pump Heating Mode - Single speed

G. Heat Pump Heating with Auxiliary Electric Heat

Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with R to W/W1 or W2 (and R to O in the case of defrost).

In the event that electric heating is called for by the thermostat while the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.

Procedure 11 - TROUBLESHOOTING ECM MOTOR AND CONTROLS

❗ CAUTION

ELECTRICAL SHOCK HAZARD

Failure to follow this caution may result in personal injury.

High voltage is always present at motor. Disconnect power to unit before removing or replacing connectors or servicing motor. Wait at least 5 min after disconnecting power before opening motor.

The ECM motor used with this product contains two parts: the control module and motor winding section. Do not assume the motor or module is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor. The control module is available as a replacement part.

A. If motor turns slowly:

  1. Replace panel. Motor may appear to run slowly if access panel is removed.
  2. It is normal operation to run noticeably slower if G terminal is not energized in cooling or heat-pump modes.

B. If motor does not run:

Turn off power and check the following:

  1. Check 5 amp fuse on Easy Select Board.
  2. Check for 24vac on SEC1 and SEC2. If no voltage is present, check transformer.
  3. Check all plugs and receptacles for any deformation which could cause loose connections. Be sure plugs are fully seated.
  4. Verify that approximately 230vac is present at motor.
  5. Verify low-voltage control signals to motor. The motor receives its control signals through the 12-pin plug (PL-1) on Easy Select Board and 16-pin plug on wiring harness. (See Troubleshooting Example.) The combinations of pins energized will determine motor speed. (See Fig. 20.) See Table 7 for circuit board, low-voltage screw terminals energized and for voltage present at each pin on 12-pin plug (PL-1). See Table 7 for pin number on 16-pin plug which should have voltage when Easy Select Board screw terminals have 24vac.

C. Use following procedure to check control signals:

THERMOSTAT
  1. Remove all thermostat wires from Easy Select Board.
  2. Jumper screw terminals (1 at a time): R-G, R-Y/Y2, R-Y1, R-W1. If motor runs in all cases, thermostat is mis-wired, configured incorrectly or defective. If motor runs in some cases, but not others, continue to check wiring harness and circuit board.
WIRING HARNESS
  1. Shut off power to unit; wait 5 min.
  2. Remove 5-pin plug from motor.
  3. Remove 16-pin from motor.
  4. Replace 5-pin plug and turn power on.
  5. Check for appropriate voltages on 16-pin connector with screw terminals jumpered. (See Table 7 for values and see examples below.)

If signals check correctly and motor does not run, inspect wiring harness for loose pins or damaged plastic that could cause poor connections. If connections are good, either control module or motor is defective. If proper signals are not present, check circuit board using procedure below:

12-PIN PLUG (PL-1) ON EASY SELECT BOARD
  1. Unplug harness from board.
  2. Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered. (See Table 7 for values and see example below.)

If proper signals are not present, replace Easy Select Board. If present at board and not at 16-pin connector, wiring harness is defective.

TROUBLESHOOTING EXAMPLE:

Motor is not running on a call for heat-pump heating. System is a single-speed heat pump.

  1. After performing checks in Thermostat section, follow steps 1 thru 5 in Wiring Harness section. Then proceed with example.
  2. With all thermostat wires removed from Easy Select Board, place a jumper wire between R and Y/Y2 low-voltage screw terminals on the Easy Select board.
  3. Check Table 7 for pin number on 16-pin connector associated with the Y/Y2 signal. The correct pin is #14. The far right column shows that (-) 12vdc should be present between pin #14 and pin #1 (common) on the 16-pin connector.
  4. Set meter to read DC voltage. Place meter between pins #1 and #14 and check for (-) 12vdc (common side of meter on pin #1). If signal is present, the problem is in the module or motor. If signal is not, problem is either in wiring harness or Easy Select Board.

These steps can be repeated for other modes of operation.

To check Easy Select Board:
  1. Leave jumper wire in place between R and Y/Y2.
  2. Check Table 7 under "Wiring Harness Connection to Easy Select Board" column and row for pin #14 to see pin# on Easy Select Board that should have voltage. The correct pin is #2. The column on far right will show voltage that should be present between pin #2 and #9 (or #10 common).
  3. Place meter between pins #2 and #9 on Easy Select Board and check for (-) 12vdc.
  4. If voltage is present, the wiring harness is bad; if not, the Easy Select Board is bad.

D. Verify Motor Winding Section:

Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed and unplugged from winding section:

  1. The resistance between any 2 motor leads should be similar.
  2. The resistance between any motor lead and the unpainted motor end plate should be greater than 100K ohms.

If motor winding section fails one of these tests, it is defective and must be replaced.

CARE AND MAINTENANCE

For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. The only required maintenance that may be performed by the consumer is filter maintenance.

⚠️ WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect all power to unit before servicing field wires or removing control package. The disconnect (when used) on access panel does not disconnect power to the line side of disconnect, but does allow safe service to all other parts of unit. If unit does not have a disconnect, disregard the foregoing. Instead, make sure that a disconnecting means is within sight from, and is readily accessible from, the unit. Disconnect all electrical power to unit before performing any maintenance or service on it.

The minimum maintenance requirements for this equipment are as follows:

  1. Inspect and clean or replace air filter each month or as required.
  2. Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary. An inspection port is provided on all A-coil delta plates. Remove plastic plug to inspect.
  3. Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
  4. Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service as necessary.

Consult Fan Coil Service Manual available from equipment distributor for maintenance procedures.

❗ CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.

Using the Owner's/User Manual furnished in outdoor unit, the installing technician should explain system operation to the consumer with particular emphasis on indoor fan coil operation sounds and filter maintenance.

Tables

Table 1 - Filter Kits

FILTER KIT (12 PACK) PART NUMBER SIZE USED WITH
KFAFK0212MED 002
KFAFK0312LRG 003, 005
KFAFK0412XXL 006

Table 2 – CFM Range for FV4C Units

FAN COIL SIZE SYSTEM SIZES CFM RANGE
FV4CNF002 024, 030, 036 350-1275
FV4CN(B,F)003 024, 030, 036, 042 415-1475
FV4CN(B,F)005 036, 042, 048 425-1700
FV4CNB006 042, 048, 060 540-2150

Table 3 - FV4C Fan Coil Airflow Delivery (CFM) in Cooling Mode

UNIT SIZE OUTDOOR UNIT CAPACITY OPERATING MODE FAN ONLY
SINGLE-SPEED APPLICATION TWO-SPEED APPLICATION Lo Med High
Nominal A/C Cooling A/C Cooling Dehumidity High Speed Nominal A/C Cooling A/C Cooling Dehumidity Low Speed Nominal A/C Cooling A/C Cooling Dehumidity
002 018 525 420 -- -- -- -- 350 420 525
024 700 560 700 560 560 450 350 560 700
030 875 700 -- -- -- -- 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
003 024 700 560 700 560 560 450 415 560 700
030 875 700 -- -- -- -- 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
042 1225 980 -- -- -- -- 610 980 1225
005 030 875 700 -- -- -- -- 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
042 1225 980 -- -- -- -- 610 980 1225
048 1400 1120 1400 1120 1120 895 700 1120 1400
006 036 1050 840 1050 840 840 670 540 840 1050
042 1225 980 -- -- -- -- 610 980 1225
048 1400 1120 1400 1120 1120 895 700 1120 1400
060 1750 1400 1750 1400 1400 1120 875 1400 1750

NOTES: 1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM. 2. Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only. 3. Dry coil at 230 volts and with 10KW heater and filter installed. 4. Airflows shown are at standard air conditions.

Table 4 - FV4C Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode

UNIT SIZE OUTDOOR UNIT CAPACITY OPERATING MODE FAN ONLY
SINGLE-SPEED APPLICATION TWO-SPEED APPLICATION Lo Med High
Heat Pump Comfort Heat Pump Efficiency High Speed Heat Pump Comfort Heat Pump Efficiency Low Speed Heat Pump Comfort Heat Pump Efficiency
002 018 470 525 -- -- -- -- 350 380 470
024 630 700 630 700 505 560 350 505 630
030 785 875 -- -- -- -- 390 630 785
036 945 1050 945 1050 755 840 470 755 945
003 024 630 700 630 700 415 560 415 505 630
030 785 875 -- -- -- -- 415 630 785
036 945 1050 945 1050 755 840 470 755 945
042 1100 1225 -- -- -- -- 550 880 1100
005 030 785 875 -- -- -- -- 425 630 785
036 945 1050 945 1050 755 840 470 755 945
042 1100 1225 -- -- -- -- 550 880 1100
048 1260 1400 1260 1400 1010 1120 630 1010 1260
006 036 945 1050 945 1050 755 840 540 755 945
042 1100 1225 -- -- -- -- 550 880 1100
048 1260 1400 1260 1400 1010 1120 630 1010 1260
060 1575 1750 1575 1750 1260 1400 785 1260 1575

NOTES: 1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM. 2. Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only. 3. Dry coil at 230 volts and with 10KW heater and filter installed. 4. Airflows shown are at standard air conditions.

Table 5 – FV4C Airflow Delivery (CFM)

FAN UNIT SIZE OUTDOOR UNIT CAPACITY BTUH ELECTRIC HEATER kW RANGE 0 - 5 0 - 10 0 - 15 0 - 20
Lo Nom High Lo Nom High Lo Nom High Lo Nom High
002 18,000 625 625 625 675 675 -- -- -- -- -- --
24,000 650 725 835 -- 725 835 875 875 -- -- --
30,000 815 905 1040 -- 905 1040 900 900 -- -- --
36,000 980 1085 1250 980 1085 1250 980 1085 -- 1100 1100
003 24,000 675 725 835 875 875 -- -- -- -- -- --
30,000 815 905 1040 875 905 1040 1100 1100 -- 1100 1100
36,000 980 1085 1250 980 1085 1250 1100 1100 1250 1225 1225
42,000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270
005 30,000 975 975 1040 1100 1100 1100 -- -- -- -- --
36,000 980 1085 1250 1100 1100 1250 1250 1250 1250 1250 1250
42,000 1140 1270 1460 1140 1270 1460 1250 1270 1460 1460 1460
48,000 1305 1450 1665 1305 1450 1665 1305 1450 1665 1500 1500
006 36,000 1100 1100 1250 1350 1350 1350 -- -- -- -- --
42,000 1140 1270 1460 1350 1350 1460 1525 1525 1525 1525 1525
48,000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1665 1665
60,000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1750

NOTE: Lo, NOM, and HI refer to AC, HP CFM ADJUST selection. --- Airflow not recommended for heater/system size.

Table 6 – FV4C Minimum CFM for Electric Heater Application

FAN COIL UNIT HEAT PUMP UNIT SIZE CFM HEATER SIZE kW
5 8, 9, 10 15 18, 20 24, 30
002 Heater Only 625 625 725 875 --
018 625 625 -- -- --
024 650 725 875 -- --
030 800 875 875 1040 --
036 970 970 970 1040 --
003 Heater Only 675 700 1050 1050 --
024 675 875 -- -- --
030 800 875 1100 -- --
036 975 975 1100 1225 --
042 1125 1125 1125 1225 --
005 Heater Only 675 700 1050 1050 1400
018 800 875 1100 -- --
036 975 975 1100 1225 --
042 1125 1125 1125 1225 --
048 1305 1305 1305 1305 1400
006 Heater Only 1050 1050 1050 1050 1750
018 1100 1100 1350 1350 --
042 1125 1125 1350 1350 --
048 1300 1300 1350 1465 1750
060 1625 1625 1625 1750 1750

NOTES: 1. Heater Only—Air conditioner with electric heater application. 2. These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow deliver chart for Electric Heating Modes.

Table 7 - Wiring connection of FV Fan Coil Wiring Harness

16-PIN PLUG ON WIRING HARNESS TO MOTOR WIRING HARNESS CONNECTION TO EASY SELECT BOARD
Pin on 16-Pin Plug Description Pin on 12-Pin Plug or Set-up Selection Wire Color Signal on Pin with Screw Terminal Jumpered to R*
1 Common Pin 9 on PL-1 Brown 24VAC**
2 W1 Pin 7 on PL-1 Violet
3 Common Auxiliary Heat Stage 1 Pin 10 on PL-1 Orange
4 On/Off Delay Selection On/Off Delay Selection White
5 AC/HP Size Selection AC/HP Size Selection Blue
6 Y1 Low Speed AC or HP Pin 3 on PL-1 Black (--) 12VDC**
7 AC/HP CFM Adjust Selection AC/HP CFM Adjust Selection Black
8 Not Used N/A Not Used
9 System Type Selection System Type Selection Orange
10 Dehumidify Pin 12 on PL-1 Gray 0V (24VAC on no call)
11 Aux Heat Size Selection Aux Heat Size Selection Violet
12 24v AC Pin 8 on PL-1 Red 24VAC continuous
13 W2 Auxiliary Heat Stage 2 Pin 4 on PL-1 White 24VAC**
14 Y/Y2 Single Speed AC or HP, High Speed 2-Speed AC or HP Pin 2 on PL-1 Yellow (--) 12VDC*
15 G Fan Pin 1 on PL-1 Green 24VAC**
16 Not Used N/A Not Used

* Check voltages with 16-Pin Plug disconnected from motor. ** These signals will start motor.

PURON® (R-410A) QUICK REFERENCE GUIDE

PDF preview unavailable. Download the PDF instead.

FV4C Installation Manual Acrobat Distiller 8.1.0 (Windows)

Related Documents

Preview Carrier WeatherMaster 50GCQ Series Installation Instructions
Comprehensive installation guide for Carrier's WeatherMaster 50GCQ*07-09 single package rooftop heat pumps, detailing safety, unit setup, electrical connections, and economizer options.
Preview Carrier FT5, FG5 Fan Coil Installation Instructions for R-454B Refrigerant
Comprehensive installation guide for Carrier FT5 and FG5 Fan Coil units designed for Puron Advance™ R-454B refrigerant. Covers safety, unit mounting, electrical connections, airflow adjustments, and troubleshooting for various configurations including upflow, horizontal, and downflow installations.
Preview Carrier FT5 Fan Coil: Performance, Efficiency, and InteliSense™ Technology
Explore the Carrier FT5 Fan Coil, featuring InteliSense™ technology, Puron Advance® refrigerant, and a variable speed ECM motor for superior comfort, efficiency, and environmental responsibility. View detailed specifications, performance data, and model information for residential and light commercial HVAC applications.
Preview Carrier CVPVA CSPVA Cased Cooling Only Evaporator Coil Installation Instructions
Comprehensive installation guide for Carrier CVPVA and CSPVA Cased Cooling Only Evaporator Coils, covering safety, airflow, TXV, refrigerant lines, and condensate management for R-410A systems in upflow and downflow configurations.
Preview Carrier NAVA4 Accessory Coil Installation Instructions
This document provides detailed installation instructions for the Carrier NAVA4 Accessory Coil, designed for FEV fan units. It covers safety precautions, procedures for downflow and upflow applications, refrigerant tubing, condensate drain setup, unit start-up, and maintenance. Includes wiring diagrams and airflow performance data for R-410A systems.
Preview Carrier CAAMP Evaporator A-Coil Installation Instructions for Puron Advance Refrigerant
Detailed installation instructions for the Carrier CAAMP Cased Evaporator A-Coil, designed for Puron Advance (R-454B) refrigerant. Covers safety, inspection, coil installation, refrigerant line connections, condensate drain, electrical connections, and leak dissipation system setup.
Preview Carrier FT5/FG5 Fan Coil Installation Instructions
Comprehensive installation manual for Carrier FT5 and FG5 Fan Coil units, detailing setup, safety, wiring, and troubleshooting for Puron Advance™ refrigerant systems. Covers various installation types and system configurations.
Preview Carrier CA13NA-16NW Series Air Conditioner Installation Guide
Comprehensive installation instructions for Carrier CA13NA, CA14NA, CA15NA, CA16NA, and CA16NW series air conditioners. Covers safety, site preparation, electrical connections, refrigerant handling, and startup procedures.