Danfoss KDC/GVD Pressure Control Valve Installation Guide

This guide provides instructions for the installation of Danfoss KDC/GVD pressure control valves, sizes 65 - 200 (2½ - 8 in.).

Refrigerants

These valves are applicable to HCFC, HFC, R717 (Ammonia), and R744 (CO2). Flammable hydrocarbons are not recommended. The valve is recommended for use only in closed circuits. For further information, please contact Danfoss.

Temperature and Pressure Ranges

Installation

General Installation Requirements (Fig. 1)

The valve must be installed with the spindle vertically upwards. The valve is designed to withstand high internal pressure. However, the piping system should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. Ensure the valve is protected from pressure transients such as "liquid hammer" in the system.

Fig. 1: Correct and incorrect valve orientations.

Flow Direction (Fig. 3)

Important: The flow direction must be from the cone side towards the branch.

Fig. 3: Correct flow direction indicated by an arrow.

Welding (Fig. 4)

Before welding, remove the actuator to prevent damage to the gasket between the valve body and bonnet, and the Teflon gasket in the valve seat. Only use materials and welding methods compatible with the valve housing material. After welding, clean the valve internally to remove welding debris before reassembly. Avoid welding debris and dirt in the threads of the housing and bonnet. The valve housing must be free from stresses (external loads) after installation.

KDC/GVD valves must not be mounted in systems where the outlet side of the valve is open to the atmosphere. The outlet side must always be connected to the system or properly capped off, for example, with a welded-on end plate.

Fig. 4: Illustration showing actuator removal for welding.

Assembly (Fig. 5)

Remove welding debris and any dirt from pipes and the valve body before assembly. After mounting the bonnet and tightening the bonnet bolts, remove the disassembly bolt (pos. 32). This bolt secures the insert from falling out during disassembly and prevents damage to the Teflon seat when the bonnet is mounted.

Note! Always pull the valve seat back into the open position before assembling the valve.

For a pilot line, use DN10 steel pipe. Connection can be made directly to the valve using the NPT ¼" thread or via an adapter for a cutting ring.

Fig. 5: Assembly steps including bolt removal and pilot line connection.

Tightening (Fig. 5)

Tighten the bonnet with a torque wrench to the values indicated in the table.

DN Nm LB-feet
DN 65 75 53
DN 80 44 32
DN 100 75 53
DN 125-150 183 135
DN 200 370 272

Colours and Identification

KDC/GVD valves are factory-painted with a red oxide primer. Valve identification is confirmed by the ID ring on top of the bonnet and stamping on the valve body. Prevent the external surface of the valve housing against corrosion with a suitable protective coating after installation and assembly. It is recommended to protect the ID ring when repainting the valve.

Maintenance

Dismantling the Valve (Fig. 4 and Fig. 5)

Do not remove the bonnet while the valve is still under pressure.

Evacuate the pipe system where the valve is installed. Ensure refrigerant is evacuated from both the inlet and outlet sides of the valve. Use the service port (pos. 15) on the valve to evacuate refrigerant from above the cone.

Mount the dismantling bolt (pos. 32), hexagon flange nut (pos. 31), and nylon ring (pos. 30) as shown in Fig. 5. Tighten the nut (pos. 31) a few rounds to draw the valve cone from the seat. Remove the bolts and then the valve top (actuator).

Assembly (Fig. 5)

Remove welding debris and any dirt from pipes and the valve body before assembly. Mount the hexagon screw (pos. 32), hexagon flange nut (pos. 31), and nylon ring (pos. 30) as shown in Fig. 5. Tighten the nut (pos. 31) a few rounds to draw the valve cone from the seat. Remove the disassembly bolt after mounting the bonnet and tightening the bonnet bolts. The purpose of the bolt is to secure the insert from falling out during disassembly and to prevent damage to the Teflon seat when the bonnet is mounted.

Note! Always pull the valve seat back into the open position before assembling the valve.

Models: KDC-GVD 65, KDC-GVD 200, KDC-GVD 65 Pressure Control Valve, KDC-GVD 65, Pressure Control Valve, Control Valve

PDF preview unavailable. Download the PDF instead.

AN149486416503en-000401 Danfoss A/S GPL Ghostscript 10.05.0

Related Documents

Preview Danfoss Industrial Refrigeration Field Service Guide: Installation and Operation
Comprehensive installation and operation guide for Danfoss industrial refrigeration components, including valves, regulators, controls, and sensors. Features product details, service procedures, and technical specifications.
Preview Danfoss Pilot Operated Internal Safety Valve POV Installation Guide
Installation guide for the Danfoss Pilot Operated Internal Safety Valve (POV), covering refrigerants, temperature and pressure ranges, mounting, flow direction, welding, assembly, and tightening specifications.
Preview Danfoss EV220B 65-100 Solenoid Valve Installation Guide
Comprehensive installation guide for Danfoss EV220B 65, 80, and 100 solenoid valves, covering product contents, specifications, installation steps, and maintenance recommendations.
Preview Danfoss NRD Differential Pressure Valve Installation Guide
Installation guide for the Danfoss NRD differential pressure valve, detailing refrigerant compatibility, working pressure, media temperature, and installation notes. Includes technical specifications and system schematics.
Preview Danfoss ICLX 100-150 2-Step Solenoid Valve Installation Guide
Comprehensive installation, maintenance, and technical specifications for the Danfoss ICLX 100-150 2-step solenoid valve, covering operation, assembly, and troubleshooting.
Preview Danfoss ICM/ICAD Motorized Valves: Installation, Programming, and Troubleshooting Quick Start Guide
A comprehensive guide for the installation, programming, and troubleshooting of Danfoss ICM/ICAD Motorized Valves, covering valve identification, wiring, parameter settings, and common issues.
Preview Danfoss AB-QM DN 40-100 Operating Guide
This guide provides operating instructions for the Danfoss AB-QM DN 40-100 automatic balancing and control valve, covering installation, setting, resetting, locking, and measuring procedures.
Preview Danfoss HFI Float Valve (High Pressure) Installation Guide
Comprehensive installation and maintenance guide for the Danfoss HFI Float Valve (High Pressure), covering refrigerants, temperature and pressure ranges, welding, assembly, and parts replacement.