Installation guide

Solenoid valve

Type EV220B 65 - 100

Illustration of a Danfoss EV220B solenoid valve, a flanged industrial valve with a coil assembly, shown in a line drawing. Document reference: 016R9522.

Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB

Product Overview

The product contains

  • EV220B 65
  • EV220B 80 & 100
  • EV220B 65-100 Small box

Included parts:

  • 8 pieces
  • 2 pieces
  • 1 piece
  • 1 piece*

*Only in case of water hammer risk, change the equalizing orifice. See page 6 for installation guide.

Accessories

  • Cable plug
  • Coil BB/BE/BG/BY
  • Flange set
  • Manual override kit

Identification

Example marking: Week: 06 / year: 2020

Recommendations

  • Filter requirement: ≥ 50 mesh (≤ 297 microns) [filter]
  • Operation: [ON/OFF indicator]
  • Water quality: Hardness 6 - 18 °dH, Conductivity 50 - 800 µS/cm t, Media temp. < 25°C
  • Maintenance: every 6 to 12 months ?

Parts and Specifications

Parts List

NO. Part
1 Water supply
2 Filter
3 Ball valve, water supply
4 Solenoid valve
5 Ball, test reservoir
6 Test reservoir
7 Ball valve, application
8 Application

Technical Specifications

Type L [mm] L₁ [mm] Required min. L₂* [mm] B₁ [mm] Coil type ØD [mm] H₁ [mm] H₂ [mm] Weight without coil [kg] Required min. inside tube diameter d** [mm]
EV220B 65 320 224 300 46 BB/BE, BG 185 85 185 24 65
EV220B 80 370 265 350 46 BB/BE, BG 200 93 215 34 80
EV220B 100 430 315 400 46 BB/BE, BG 220 103 240 44 100

* Avoid closing problems caused by turbulent flow; it is required to have a straight tube on both sides of the valve.

** Required to keep same tube size for entire application, same or bigger inside diameter as valve orifice 65 / 80 / 100 mm.

Dimensional diagram of the solenoid valve showing key measurements L, L₁, L₂, D, H₁, H₂.

Installation Guide

Installation Steps

  1. Disconnect power [power plug].
  2. Turn valve to OFF position [OFF indicator].
  3. Connect valve to pipework.
  4. Tighten flange bolts to 10 ± 0.5 Nm [torque].
  5. Ensure valve is installed within ± 5° of horizontal.
  6. Connect coil.
  7. Insert pipe into valve end.
  8. Align valve with pipework, ensuring straight pipe sections.
  9. Tighten pipe connections to Max. 190 Nm [torque].
  10. Mount valve assembly.
  11. Connect pipework to valve.
  12. Ensure coil clicks into place.
  13. Tighten coil retaining screws to 50-60 Ncm (0.39-0.44 lb-ft) [torque].
  14. Do not allow water to drip onto the coil [water drip symbol crossed out].
  15. Connect power [power socket].

Pressure Specifications

DN Max. working pressure (MWP) [bar] Max. test pressure (MTP) [bar]
65 - 100 10 15

Maintenance and Adjustments

Change Equalizing Orifice (for water hammer)

Instructions for changing the equalizing orifice from 2 mm to 1.2 mm.

  1. Disconnect power [power plug].
  2. Turn valve to OFF [OFF indicator].
  3. Disconnect coil.
  4. Remove valve assembly.
  5. Remove retaining nut.
  6. Remove old orifice (2 mm).
  7. Insert new orifice (1.2 mm).
  8. Replace retaining nut.
  9. Reassemble valve.
  10. Turn valve to ON [ON indicator].
  11. Check for leaks [water leak symbol crossed out].
  12. Connect power [power socket].

Visit www.product.danfoss.com for further technical data.

Para más información, visite www.product.danfoss.es.

Rendez-vous sur le site www.products.danfoss.fr pour plus de données techniques.

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material.

Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.

All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Models: EV220B 65, EV220B 80, EV220B 100, EV220B 65-100, Solenoid Valve, EV220B 65-100 Solenoid Valve

File Info : application/pdf, 6 Pages, 3.03MB

PDF preview unavailable. Download the PDF instead.

Solenoid valve - Type EV220B 6

References

Danfoss A/S Adobe PDF library 17.00

Related Documents

Preview Danfoss ICLX 100-150 2-Step Solenoid Valve Installation Guide
Comprehensive installation, maintenance, and technical specifications for the Danfoss ICLX 100-150 2-step solenoid valve, covering operation, assembly, and troubleshooting.
Preview Danfoss ICF Valve Station: Technical Data and Applications
Comprehensive data sheet for Danfoss ICF valve stations (models ICF 15, 20, 25, 50, 65), detailing features, technical specifications, function modules, material data, connection types, and application examples for industrial refrigeration.
Preview Danfoss ICLX 32-65 2-Step Solenoid Valve Installation Guide
Comprehensive installation guide for the Danfoss ICLX 32-65 2-step solenoid valve, covering technical specifications, application, wiring, maintenance, and troubleshooting for industrial refrigeration systems.
Preview Danfoss EV251B NC Mounting Guide
Official mounting guide for the Danfoss EV251B NC solenoid valve. Learn about valve identification, proper installation, coil mounting and replacement, and common troubleshooting steps. Includes technical specifications and support information.
Preview Danfoss ICM 100-150 Motor Operated Valve Installation and Maintenance Guide
Comprehensive guide for installing and maintaining the Danfoss ICM 100-150 motor operated valve, including technical specifications, assembly, disassembly, and lubrication procedures.
Preview Danfoss ICMTS Motor Operated Valve with ICAD 600A-TS Actuator: Installation Guide
This installation guide provides detailed instructions for the Danfoss Motor Operated Valve Type ICMTS with Actuator Type ICAD 600A-TS. It covers refrigerant compatibility, temperature and pressure ratings, technical data, installation procedures, welding and soldering guidelines, manual operation, insulation, surface treatment, assembly, and maintenance. Designed for high-pressure R744 applications, this valve is suitable for various industrial refrigeration systems.
Preview Danfoss ICLX 32-65 2-Step Solenoid Valve Installation Guide
Comprehensive installation guide for the Danfoss ICLX 32-65 2-step solenoid valve, covering features, operation, maintenance, and safety instructions.
Preview Danfoss EcoTM Smart Thermostat Installation and User Manual
Comprehensive guide to installing, operating, and troubleshooting the Danfoss EcoTM smart thermostat. Learn about features, app connectivity, and adapter compatibility for efficient home heating control.