Installation Guide for MAYTAG models including: 13.4 SEER2, Series, A-GPHM3 Packaged Heat Pump Unit, A-GPHM3, Packaged Heat Pump Unit, Heat Pump Unit, Pump Unit
Mar 26, 2025 — Refer to the Roof Curb Installation Instructions for proper curb installation. ... SEE USER MANUAL. FOR MORE DETAILS. RED LED'S STATUS. MODE. CHECK. 1 FLASH.
File Info : application/pdf, 36 Pages, 3.58MB
DocumentDocumentPackaged Heat Pump Unit A/GPHM3 13.4 SEER2 "M" Series with R-32 Installation Instructions WARNING Only personnel that have been trained to install, adjust, service, maintenance or repair (hereinafter, "service") the equipment specified in this manual should service the equipment. This equipment is not intended for use by persons (including children) with reduced physical, sensory or mental capacities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper supervision, service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper supervision, installation, adjustment, servicing, maintenance or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper supervision or training may result in product damage, property damage, personal injury or death. NOTE: This equipment is only approved for use with R-32 refrigerant. WARNING Do not bypass safety devices. RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. NOTE: *PHM3 models apply to both Amana® Brand and Goodman products only. IOG-3035B 03/2025 Our continuing commitment to quality products may mean a change in specifications without notice. © 2024-2025 Daikin Comfort Technologies Manufacturing, L.P. 19001 Kermier Rd. Waller, TX 77484 www.goodmanmfg.com · www.amana-hac.com is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved. Table of Contents To The Installer............................................................. 2 Shipping Inspection ....................................................... 3 Transportation Damage ......................................... 3 Message to the Homeowner ................................... 3 Replacement Parts ....................................................... 3 Ordering Parts ......................................................... 3 Important Safety instructions................................... 3 Recognize Safety Symbols, Words and Labels . 3 Cabling ....................................................................... 3 General Information .................................................... 5 Qualification of Workers ...................................... 5 EPA Regulations ....................................................... 5 National Codes ......................................................... 5 Major Components................................................... 5 Pre-Installation Checkpoints................................ 5 Unit Location.................................................................. 6 Clearance and Accessibility.................................. 6 Roof Top Installation.............................................. 7 Roof Curb Installations ......................................... 7 Rigging Details .............................................................. 8 Circulating Air and Filters......................................... 9 Air Flow Conversion................................................. 9 Horizontal Air Flow .................................................. 9 Down Discharge Applications ................................. 9 Ducting......................................................................... 9 Connecting the Return and Supply Flexible Duct in Manufactured or Modular Housing Application ................................................................ 10 Plenum Application.................................................. 10 Filters ........................................................................ 10 Condensate Drain Piping............................................ 10 Electrical Wiring ....................................................... 11 High Voltage Wiring............................................... 12 Low Voltage Wiring ............................................... 12 Internal Wiring....................................................... 12 Start-up Procedures and Checklists ..................... 12 Heat Pump Start up Procedure ........................... 12 Final System Check................................................ 13 Components .................................................................. 13 Heat Pump Operation .................................................. 14 Cooling Cycle ......................................................... 14 Heating Cycle.......................................................... 14 Defrost Control .................................................... 14 Suggested Field Testing / Troubleshooting ......... 15 Testing Defrost Control ..................................... 15 Testing Defrost Thermostat................................ 15 Airflow Measurement and Adjustment .................. 15 Adjusting Speed Tap for Indoor Blower Motor... 16 EEM Motor ............................................................... 16 EEM Motor Speed Adjustment ............................. 16 [*PH] CFM Delivery and Adjustments ................. 16 [*PH] Thermostat "Fan Only" Mode ..................... 16 Superheat and Subcooling........................................ 16 Checking Subcooling ............................................ 16 Checking Superheat............................................... 16 Refrigerant Charge Check .................................. 17 Units with TXV ......................................................... 17 RDS Function........................................................... 17 RDS Operation......................................................... 17 Electric Heat Installation & Adjustment............... 18 Heater Kit................................................................. 18 Maintenance ................................................................. 19 Recovery .................................................................. 19 Charging Procedures ........................................... 19 Service........................................................................... 21 Inadequate Air Volume Through ID Coil............ 21 Outside Air Into Return Duct .............................. 21 Malfunctioning Reversing Valve ....................... 21 Clean Outdoor Coil (Servicer Only).................. 21 Clean Indoor Coil (Servicer Only) ..................... 21 Servicing Measures for the Refrigerant Detection System ................................................... 21 Reversing Valve Troubleshooting .......................... 22 Checking Reversing Valve and Solenoid........... 22 Troubleshooting the Reversing Valve for Electrical Failure .......................................... 22 Troubleshooting Mechanical Failures on a Reversing Valve by Pressure............................... 22 Troubleshooting Mechanical Failures on a Reversing Valve by Temperature ........................ 22 Poor "Terminating" Sensor Contact ................. 22 Undercharge ........................................................... 22 Troubleshooting Code............................................... 23 Troubleshooting Chart............................................. 24 Blower Performance Data........................................ 25 Unit Dimensions ........................................................... 27 Wiring Diagram............................................................ 28 Homeowner's Routine Maintenance ........................ 31 Start-Up Checklist...................................................... 32 TO THE INSTALLER Carefully read all instructions for the installation prior to installing unit. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. After deciding where to install unit, closely look the location over both the inside and outside of the home. Note any potential obstacles or problems that might be encountered as noted in this manual. Choose a more suitable location if necessary. IMPORTANT NOTE: If a crankcase heater is used, the unit should be energized 24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor. Compressor damage may occur if this step is not followed. Before using this manual, check the serial plate for proper model identification. The installation and servicing of this equipment must be performed by qualified, experienced technicians only. 2 SHIPPING INSPECTION Transportation Damage Upon receiving the unit, inspect it for damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, specifications, electrical characteristics, and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer assumes no responsibility for installation of incorrectly shipped units. Message to the Homeowner These instructions are addressed primarily to the installer; however, useful maintenance information is included and should be kept, after installation, for future reference. REPLACEMENT PARTS Ordering Parts When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit's nameplate. Replacement parts for this appliance are available through your contractor or local distributor. For the location of you nearest distributor, see website www.daikincomfort.com or contact: HOMEOWNER'S SUPPORT DAIKIN COMFORT TECHNOLOGIES MANUFACTURING, L.P. 19001 KERMIER ROAD WALLER, TEXAS 77484 (855) 770-5678 IMPORTANT SAFETY INSTRUCTIONS Recognize Safety Symbols, Words, and Labels The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner's responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of serious personal injury or death, property damage and/or product damage. Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. WARNING Do not connect to or use any device that is not certified by the manufacturer for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such nonapproved devices. WARNING HIGH VOLTAGE! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. WARNING Connecting unit ductwork to unauthorized heat producing devices such as a fireplace insert, stove, etc. May result in property damage, fire, carbon monoxide poisoning, explosion, personal injury or death. WARNING To avoid property damage, personal injury or death, do not use this unit if any part has been under water. Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control having been under water. WARNING This unit must not be used as a "construction heater" during the finishing phases of construction on a new structure. This type of use may result in premature failure of the unit due to extremely low return air temperatures and exposure to corrosive or very dirty atmospheres. WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. CAUTION Auxiliary devices which may be a POTENTIAL IGNITION SOURCE shall not be installed in the duct work. Examples of such POTENTIAL IGNITION SOURCES are hot surfaces with a temperature exceeding 700 °C and electric switching devices. WARNING LEAK DETECTION SYSTEM installed. Unit must be powered except for service. 3 WARNING This unit is equipped with electrically powered safety measures. To be effective, the unit must be electrically powered at all times after installation, other than when servicing. WARNING Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. The Appliance shall be stored in a room without continuously operating ignition sources (For example: Open flames, an operating gas appliance, or an operating electric heater). Do not pierce or burn. Be aware that refrigerants may not contain an odor. WARNING Only auxiliary devices approved by the appliance manufacturer or declared suitable with the refrigerant shall be installed in connecting ductwork. WARNING Prior to servicing the unit or removing the compressor terminal plug or terminal cover, disconnect all electrical power from the unit. Multiple power sources may be present. WARNING Do not operate the compressor(s) without the terminal plug fully engaged or the terminal cover properly installed. WARNING 1. Connect the vacuum pump, micron gauge, and vacuum-rated hoses to both service valves. Evacuation must use both service valves to eliminate system mechanical seals. 2. Evacuate the system to less than 500 microns. 3. Isolate the pump from the system and hold the vacuum for 10 minutes (minimum). Typically, pressure will rise slowly during this period. If the pressure rises to less than 1000 microns and remains steady, the system is considered leak-free; proceed to system charging and startup. 4. If pressure rises above 1000 microns but holds steady below 2000 microns, non-condensable air or moisture may remain, or a small leak may be present. Return to step 2: If the same result is achieved, check for leaks and repair. Repeat the evacuation procedure. 5. If pressure rises above 2000 microns, a leak is present. Check for leaks and repair them. Then, repeat the evacuation procedure. Accessory Installation WARNING All accessories that may become a potential ignition source if installed, such as electronic air cleaners, must only be powered through our accessory control board kit. If an electronic air cleaner is already installed in the duct work and not connected to the accessory control board, it will have to be disabled or removed. Ensure that any additional wiring from the indoor unit to the accessory control board is routed and protected from damage wear, avoiding the flue pipe and any joints that may need brazed or disconnected for service. Refer to the product specification sheet for the accessory control board kit part number. A tripped circuit breaker or blown fuse may indicate that an electrical problem exists. Do not reset a circuit breaker or replace fuses without first performing thorough electrical troubleshooting and testing procedures. The Following Instructions are Mandatory for A2L Systems and Supersede Other Instructions WARNING Only brazing techniques or approved mechanical joints should be used to connect refrigerant tubing connections. Non-approved mechanical connectors and other methods are not permitted in this system containing A2L refrigerant. Approved mechanical joints will be detailed in the product's specification sheets. Altitude Adjustment Factor to Calculate Minimum Room Area The Indoor equipment mitigation requirements are calculated at sea level. For higher altitudes adjust the minimum room area specified on or near the Serial Plate by the corresponding altitude adjustment factor shown below. This table is provided as a reference. Adjusted room area (Amin adj) is the product of the minimum room area specified on the serial plate and the adjustment factor AF, as shown in below formula. Amin adj = Amin (serial plate) * AF Deep Vacuum Method The Deep Vacuum Method requires a vacuum pump rated for 500 microns or less. This method effectively and efficiently ensures the system is free of non-condensable air and moisture. The Triple Evacuation Method is detailed in the Service Manual for this product model as an alternative. To expedite the evacuation procedure, it is recommended that the Schrader Cores be removed from the service valves using a core-removal tool. 4 Height in meters At sea level 1~200 200~400 400~600 600~800 800~1000 1000~1200 1200~1400 1400~1600 1600~1800 1800~2000 2000~2200 2200~2400 2400~2600 2600~2800 2800~3000 3000~3200 Height in feet At sea level 1~660 660~1320 1320~1970 1970~2630 2630~3290 3290~3940 3940~4600 4600~5250 5250~5910 5910~6570 6570~7220 7220~7880 7880~8540 8540~9190 9190~9850 9850~10500 Altitude Adjustment Factor (AF) 1.00 1.02 1.03 1.05 1.07 1.09 1.11 1.13 1.15 1.17 1.19 1.21 1.24 1.26 1.29 1.31 1.34 · Information about the explosion potential of FLAMMABLE REFRIGERANTS to show that flammables may be dangerous when handled without care. · Information about POTENTIAL IGNITION SOURCES, especially those that are not obvious, such as lighters, light switches, vacuum cleaners, electric heaters. · Information about the different safety concepts, including ventilated and unventilated areas. · Information about refrigerant detectors, including function, operation, and service measures. · Information about the concept of sealed components and sealed enclosures according to IEC 6007915:2010. · Information about the correct working procedures, including commissioning, maintenance, repair, decommissioning, and disposal procedures. GENERAL INFORMATION EPA Regulations IMPORTANT: The United States Environmental Protection Agency (EPA) has issued various The [PH]M3 SEER2 M-Series heat pumps are designed regulations regarding the introduction and for OUTDOOR USE ONLY. [*PH]M3 SEER2 M-Series disposal of refrigerants in this unit. Failure is available in cooling capacities of 2, 2.5, 3, 3.5, 4 and 5 to follow these regulations may harm the nominal tons of cooling. Optional field-installed heat kits environment and can lead to the imposition of are available in 5, 8, 10, 15 and 20kW. The units can be substantial fines. Because regulations may vary easily installed in manufactured or modular homes with due to passage of new laws, we suggest a certified existing high-static duct work. The units can also be easily technician perform any work done on this unit. converted to accommodate a plenum for normal or low- Should you have any questions please contact the static applications. The [*PH]M3 SEER2 M-Series are local office of the EPA. self-contained packaged units so the only connections needed for installation are the supply and return ducts, the National Codes line and low voltage wiring and drain connection. Rated This product is designed and manufactured to permit performance is achieved after 20 hours of operation. Rated installation in accordance with National Codes. It is the performance is delivered at the specified airflow. See installer's responsibility to install the product in accordance product specification for packaged models. with National Codes and/or prevailing local codes and regulations. Specification sheets can be found at: www.goodmanmfg.com for Goodman® brand products Major Components or www.amana-hac.com for Amana® brand products. The unit includes a hermetically sealed refrigerating system Within either website, please select the Products and (consisting of a compressor, condenser coil, evaporator Services menu and then select the submenu for the type coil with flowrator), an indoor blower, a condenser fan, and of product to be installed, such as heat pumps, to access all necessary internal electrical wiring. The heat pump also a list of product pages that each contain links to the includes a reversing valve, solenoid, defrost thermostat model's specification sheet. The units are UL listed, and and control and loss of charge protection. The system AHRI certified. The information on the rating plate is in is factory-evacuated, charged and performance tested. compliance with the FTC & DOE rating for single phase Refrigerant amount and type are indicated on rating plate. units. Pre-Installation Checkpoints The units are ETL listed, and AHRI certified. The Carefully read all instructions for the installation prior information on the rating plate is in compliance with FTC to installing unit. Ensure each step or procedure is and DOE rating for single phase units. understood and any special considerations are taken into account before starting installation. Assemble all tools, Qualification of Workers hardware and supplies needed to complete the installation. Personnel must be certified to service, work, and/or repair Some items may need to be purchased locally. units with FLAMMABLE REFRIGERANTS. A certificate should document the competence and qualification achieved through training that included the substance of the following: 5 Check that cabling /wiring will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. The following leak detection methods are deemed acceptable for all refrigerant systems. Electronic leak detectors may be used to detect refrigerant leaks but, in the case of FLAMMABLE REFRIGERANTS, the sensitivity may not be adequate, or may need recalibration (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. Heat Pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum of 2" clearance under the outdoor coil is required in milder climates. Heat Pump Elevation Chart Design Temperature Suggested Minimum Elevation +15° and above 2 ½" -5° to +14° 8" Below -5° 12" UNIT LOCATION NOTE: Units are designed for outdoor installation only at a max altitude of 8,000 feet above sea level. WARNING The appliance shall be installed, operated and stored in a room with a floor area not less than the minimum room area. If a leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system. Before attempting any installation, the following points should be considered: · Structural strength of supporting members · Clearances and provision for servicing · Power supply and wiring · Air duct connections · Drain facilities and connections · Location may be on any four sides of a home, manufactured or modular, to minimize noise Consider the effect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away. The unit should be set on a solid, level foundation preferably a concrete slab at least 4 inches thick. The slab should be above ground level and surrounded by a graveled area for good drainage. Any slab used as a unit's foundation should not adjoin the building as it is possible that sound and vibration may be transmitted to the structure. For rooftop installation, steel or treated wood beams should be used as unit support for load distribution. Minimum Room Area Figure IMPORTANT NOTE: Refer to the Altitude Adjusted room area calculation referenced in this manual. Clearances and Accessibility The unit is designed to be located outside the building with unobstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for service and installation. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant gauge connections are made on the right side of the unit as you face the compressor compartment. Electrical connections can be made either on the right or left sides of the unit. The best and most common application is for the unit to be located 12" from the wall (4" minimum) with the connection side facing the wall. This "close to the wall" application minimizes exposed wiring. Close to the wall application assures free, unobstructed air to the other two sides. In more confined application spaces, such as corners provide a minimum 12" clearance on all air inlet sides. Allow 36" minimum for service access to the compressor compartment and controls. The top of 6 the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 48" clearance and provisions made to deflect the warm discharge air out from the overhang. See FIGURE 1: GROUND LEVEL INSTALLATION. Roof Curb Installations NOTE: Sufficient structural support must be determined prior to locating and mounting the curb and package unit. Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Construct duct work using current industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. See FIGURE 3: ROOFCURB INSTALLATION. Figure 1: Ground Level Installation Roof Top Installation (Figure 2) 1. Before locating the unit on the roof, make sure that the strength of the roof and beams is adequate to support the weight involved (See specification sheet for weight of units). This is very important and the installer's responsibility. 2. Make a proper consideration for weather-tight integrity of the roof and proper drainage of condensate. 3. To ensure proper condensate drainage, unit must be installed in a level position. 4. Consideration should also be given to shade, appearance, and noise. Figure 2: Rooftop Installation Figure 3: Roofcurb Installation 7 RIGGING DETAILS WARNING To prevent property damage, the unit should remain in an upright position during all rigging and moving operations. To facilitate lifting and moving when crane is used, place the unit in an adequate cable sling. CAUTION If units are lifted two at a time, the fork holes on the condenser end of the unit must not be used. Minimum for length is 42" to prevent damage to the unit; however, 48" is recommended. NOTE: Provisions for forks have been included in the unit base frame. No other fork locations are approved. WARNING To avoid possible property damage, personal injury or death, ensure the roof has sufficient structural strength to carry the weight of the unit(s), roofcurb, snowloads, and water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof. CAUTION To avoid possible personal injury, a safe, flat surface for service personnel should be provided. WARNING To prevent possible equipment damage, property damage, personal injury or death, the following bullet points must be observed when installing the unit. Figure 4: Rigging Unit must be lifted by the four lifting holes located at the base frame corners. See Figure 4: Rigging. · Lifting cables should be attached to the unit with shackles. · The distance between the crane hook and the top of the unit must not be less than 60". · Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come into contact with the unit during transport. · Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from forklift damage. Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit. Refer to rigging label on the unit. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual. Corner and Center of Gravity Locations NOTE: Units should be lifted at a point above center of gravity. Model Shipping Operating Weight (lb) Weight (lb) *PHM32431 389 379 *PHM33031 377 367 *PHM33631 414 383 *PHM34231 478 445 *PHM34831 463 453 *PHM36031 501 470 Corner Weights (lb) LF LR RF RR 13 150 197 19 100 57 113 97 40 123 160 60 72 114 181 78 145 41 127 140 12 180 253 25 X (in) 26.79 26.89 27 27.36 27.7 27.8 Y (in) 22.74 21.4 24.37 22 20.38 22.24 Corner Weights Table 8 CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily be converted from horizontal to down discharge air flow delivery. See FIGURE 5A: HORIZONTAL FLOW DUCT COVER INSTALLATION and FIGURE 5B: DOWNFLOW DUCT COVER INSTALLATION. In down discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow. Horizontal Air Flow Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman's Service Parts department. Figure 5A: Horizontal Flow Duct Cover Installation Down Discharge Applications Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place. Figure 5C: Downshot Conversion Kit NOTE: A horizontal duct cover kit and either an approved downflow conversion kit or an approved downflow economizer are required for downflow installation. refer to the spec sheet for details. Ducting Ducting work should be fabricated by the installing contractor in accordance with local codes. Industry manuals may be used as a guide when sizing and designing the duct system-such as NESCA (National Environmental Systems Contractors Association, 1501 Wilson., Arlington, Virginia 22209). The unit should be placed as close as possible to the space to be air-conditioned allowing clearance dimensions as indicated. Ducts should run as directly as possible to supply and return outlets. Use of non-flammable weatherproof flexible connectors on both supply and return connections at the unit to reduce noise transmission is recommended. It is preferable to install the unit on the roof of the structure if the registers or diffusers are in the wall or ceiling. A slab installation is recommended when the registers are low on the wall or in the floor. Connecting the Return and Supply Flexible Duct in Manufactured or Modular Housing Application The return and supply fittings are to be attached at the unit to a suitable square to round duct converter. Your distributor has a factory designed square to round converter transition. The model #'s of these kits are as follows in the table below (See Specification Sheets for Dimension details). Figure 5B: Downflow Duct Cover Installation 9 Accessory Description Downflow Square to Round Horizontal Square to Round Item Number Medium Chassis Large Chassis SQRPG101/102 SQRPG103 SQRPGH102 SQRPGH103 The SQRPG101, SQRPG102, and SQRPG103 fit up to the Return and Supply Downflow vents having dimensions: Return (22 ¾" x 12 ¼") and Supply (22 ¼" x 14 ¾"). The SQRPGH101, SQRPGH102, and SQRPGH103 fit up to the Horizontal Return and Supply downflow vents having dimensions: Medium Chassis (16 ½" x 16 ½") and Large Chassis (18 ½" x 18 ½"). The Medium Chassis kits transition to a 16" Diameter and the Large Chassis kits transition to an 18" Diameter (equivalent diameter, opening is oval) on the return. The collars are to be slipped into the openings, and the flanges bent around the converter. The square to round converter is attached to the flanges of the square duct openings. The flexible duct is then clamped on to the collars. Once the duct is affixed to the unit, seal the collars and flanges with a proper waterproof sealant. SEE FIGURE 6: MANUFACTURED HOME MODIFICATION KIT. NOTE: A downshot conversion kit and horizontal duct cover kit are both required when changing the unit to downshot orientation. Please refer to spec sheets for kit numbers. properly supported from the unit. False ceilings or drop ceilings may be used as a return air plenum. NOTE: Adequate return grills have to be supplied for each room for proper return for that space. NOTE: Proper sealing of all ductwork and air handling compartments is extremely important to overall unit efficiency. Filters Filters are not provided with unit and must be supplied and externally installed in the return duct system by the installer. A field-installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning. When installing filters, ensure the air flow arrows on the filter are pointing toward the circulator blower. For unit filter size information, see table below for recommended filter size. UNIT 2 TON 2 1/2 TON 3 TON 3 1/2 TON 4 TON 5 TON Min. Filter Size (1)25X25X1 (1)25X25X1 (1)25X25X1 (1)25X25X1 (2)20X20X1 (2)20X20X1 CONDENSATE DRAIN PIPING The condensate drain connection of the evaporator is a ¾" NPT half coupling. A trap must be provided to have proper condensate draining. Install condensate drain trap as shown in FIGURE 7: CONDENSATE DRAIN TRAP PLUMBING. Ensure drain connection is 3/4" or larger. Do not operate unit without trap and ensure unit is level or slightly inclined toward drain. Unit 2" Minimum Figure 6: Manufactured Home Modification Kit It is strongly encouraged to use appropriately sized ducts based upon the CFM for your application (unit's CFM). If duct sizing through industry manuals or air duct calculators requires larger ducts than converter openings, run larger duct size up to unit converter openings and reduce with a reducer duct fitting or transition right at the unit. Plenum Application A suitable plenum or square duct must be constructed. The duct cross-sectional area should be determined by industry duct sizing manuals or air duct calculators. Drain Connection 3" Minimum Flexible Tubing-Hose Or Pipe A Positive Liquid Seal Is Required Figure 7: Condensate Drain Trap Plumbing ELECTRICAL WIRING WARNING High voltage - prior to servicing the unit or removing the compressor terminal plug or terminal cover, disconnect all electrical power from the unit. Multiple power sources may be present. On ductwork exposed to outside air conditions of temperature and humidity, use an insulation with a good K factor, and a vapor barrier. Industry practices should be followed. Balancing dampers are recommended for each branch duct in the supply system. Ductwork should be 10 WARNING CAUTION Do not operate the compressor(s) without the terminal plug fully engaged or the terminal cover properly installed. Get away if unusual sounds are heard from within the compressor. Disconnect electrical power from the unit. WARNING A tripped circuit breaker or blown fuse may indicate that an electrical problem exists. Do not reset a circuit breaker or replace fuses without first performing thorough electrical troubleshooting and testing procedures. To avoid property damage or personal injury due to fire, use only copper conductors. All wiring should be made in accordance with the National Electrical Code. The local power company should be consulted to determine the availability of sufficient power to operate the unit. The voltage, frequency, and phase at the power supply should be checked to make sure it corresponds to the unit's RATED VOLTAGE REQUIREMENT. WARNING Hermetic compressor electrical terminal venting can be dangerous. In certain circumstances, the terminal may be expelled, venting the refrigerant vapor and compressor oil contained within the compressor housing and system. Be alert for sounds of arcing (Sizzling, sputtering, or popping) inside the compressor. Immediately get away if you hear these sounds and disconnect electrical power from the unit. Never operate the compressor without the terminal cover secured and properly in place or without the electrical plug fully seated and engaged to the terminal posts. If a terminal is damaged, electrically overloaded, or short circuits to ground, there is a remote possibility that the terminal can be suddenly expelled from the terminal housing thereby venting the refrigerant and compressor oil mixture to atmosphere. This discharge can be ignited from electrical arcing, or other open sources of ignition, and can cause potentially severe or fatal injury. This event is known as "Terminal Venting". To reduce the possibility of external ignition, all open flames or other heat sources must be extinguished, and all electrical power must be turned off prior to opening the terminal cover or removing the electrical plug and servicing the system. Install a branch circuit fused disconnect near the unit, in accordance with the N.E.C. or local codes. Wire sizes and overcurrent protection should be determined from the unit nameplate ampacity and in accordance with N.E.C. and local building codes. Under no circumstances should wiring be sized smaller than is recommended by either of these two sources. Fuses smaller than that recommended on the unit nameplate could result in unnecessary fuse failure or service calls. The use of protective devices of larger size than indicated could result in extensive damage to the equipment. The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices. All units have undergone a run test prior to packaging for shipment. This equipment has been started at minimum rated voltage and checked for satisfactory operation. Do not attempt to operate this unit if the voltage is not within the minimum and maximum voltages shown on the nameplate. The units are designed for operation at the voltage, frequency and phase as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. The low voltage wiring must be connected between the unit control panel and the room thermostat. Proper sealed system evacuation is required during servicing to maintain adequate internal system cleanliness while eliminating contaminates. Be alert for sounds of arcing (sizzling, sputtering, or popping) inside the compressor. IMMEDIATELY GET AWAY from the unit if you hear these sounds and disconnect electrical power. All exterior wiring must be within approved weatherproof conduit. The unit must be permanently grounded in accordance with local codes, or in absence of local codes with N.E.C. ANSI/NFPA NO. 70 or latest edition by using ground lug in the control box. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE. NOTE: Never operate the compressor in a vacuum or in reverse operation. Fuses or HACR type circuit breakers may be used where codes permit. IMPORTANT NOTE: Units may be equipped with a single pole contactor. Caution must be exercised when servicing as only one phase of the power 11 supply is broken with the contactor. Rated Voltage 208/240V Minimum Supply Voltage 197 Minimum Supply Voltage 253 WARNING HIGH VOLTAGE! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. CAUTION To avoid the risk of electrical shock, wiring to the unit must be polarized and grounded. High Voltage Wiring Single phase Connect two leads to terminals L1 & L2 in the electrical control section, using wire sizes specified in wiring table. Thermostats must be set to energize "G" during cooling. This is default on most thermostats. Internal Wiring A diagram detailing the internal wiring of this unit is located on the electrical box cover. If any of the original wire supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring. 1. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of the run can be determined from N.E.C., local building codes, and using the circuit ampacity found on the unit rating plate. From the unit disconnect to unit, the smallest wire size allowable may be used for the ampacity, as the Disconnect MUST be in accordance with federal, state, and local jurisdiction requirements. 2. Wire size based on 60°C rated wire insulation and 30°C Ambient Temperature (86°F). 3. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor. Branch Circuit Ampacity SUPPLY WIRE LENGTH - FEET 15 20 25 30 35 40 45 50 START-UP PROCEDURE AND CHECKLIST Begin with power turned off at ALL disconnects. 200 64443322 150 86644433 WARNING 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table NOTE: The unit transformer is factory connected for 240V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram. Low Voltage Wiring Heat Pumps - Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18 AWG as follows: *PHM3 Terminal Thermostat Red R (24V) Green G (fan) Orange O (Rev. Valve) White W1 (Heat, Aux Heat Stage 1)* Brown W2 (Heat, Aux Heat Stage 2)* Yellow Y (Cool) Blue C (Common) *Optional field installed heat connections HIGH VOLTAGE! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Heat Pump Start-Up Procedure 1. Check the cooling mode for the heat pump by placing the thermostat in COOL mode and the fan to AUTO. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contactor is energized. The compressor, blower and fan should then be running. After the colling mode is checked out, turn the thermostat system switch to "OFF". 2. Turn the thermostat system switch to "HEAT" and fan switch to "AUTO". 3. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting. The compressor, blower and fan should now be running with the reversing valve in the de-energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air. 4. If the outdoor ambient is above 80°F, the unit may trip on its high-pressure cutout when in heating mode. The compressor should stop. The heating cycle 12 must be thoroughly checked, so postpone the test to another day when conditions are more suitable but, DO NOT FAIL TO TEST. 5. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly. NOTE: 5-Ton 13.4 SEER2 models have two stages of compressor heat. During resistance heat test, increase temperature setting until third stage heat is energized. NOTE: If outdoor thermostats are installed the outdoor ambient must be below the set point of these thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild. 6. THERMOSTATS WITH EMERGENCY HEAT. For thermostats with an emergency heat switch, raise the temperature setting until the heating second stage makes contact. The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on. 7. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely. Final System Check 1. Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling. 2. Check for air leaks in the ductwork. 3. Check air flow and refrigerant charge. See Sections on Air Flow Measurement and Adjustment and Refrigerant Charge Check. 4. Ensure the unit is free of "rattles", and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges. If discovered, ensure issue is corrected. 5. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use. 6. Ensure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc. COMPONENTS 1. Contactor This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has a 24V coil and supplies power to the compressor and outdoor fan motor. 2. Crankcase Heater This item is "ON" whenever power is supplied to the unit and crankcase heater thermostat is closed. Crankcase heater thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage. The insert type heater is self-regulating. It is connected electrically to the contactor L1 & L2 terminals. 3. Condenser Motor This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation. On 460V heat pumps, the condenser motor is activated by the CMR. 4. Compressor This item is activated by the contactor for heating and cooling, except during emergency heat. It is protected by an internal overload. 5. Contactor Relay This control is activated by the thermostat (24V coil) and supplies power to the contactor. 6. Defrost Control The Defrost control provides time/temperature initiation and termination of the defrost cycle. When a Defrost cycle is initiated, the defrost control shifts the reversing valve to "cooling" mode, stops the outdoor fan and brings on supplemental heat. Normally, a Defrost cycle will take only 2-3 minutes unless system is low on charge or outdoor conditions are severe. (Windy and cold). The defrost control also provides for a 3 minute off cycle compressor delay. 7. Outdoor Thermostat These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0°F to 45°F). They are normally open above their set points and closed below to permit staging of indoor supplement heater operation. If the outdoor ambient temperature is below 0°F (-18°C) with 50% or higher RH, an outdoor thermostat (OT) must be installed and set at (0°F) on the dial. Failure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer's warranty. 8. Reversing Valve Coil This coil is activated by the thermostat, in the colling mode and during defrost. It positions the reversing valve pilot valve for cooling operation. 9. Indoor Blower Motor Units with EEM Motors Only. The EEM model indoor blower motor is activated by the room thermostat by COOLING/HEATING or fan ON position. EEM motors are constant torque motors with low power consumption. (See Air Flow Measurement and Adjustment for speed adjustment instructions). 10. Blower Interlock Relay This relay is used to energize the blower during the electric heat operation. Some room thermostats do not energize the motor during electric heat. This relay ensures blower operation when the room thermostat energizes heat. This relay is energized by the electric heat kit sequencer. 13 HEAT PUMP OPERATION Cooling Cycle When the heat pump is in the cooling cycle, it operates exactly as an Air Conditioner Unit. See Figure 8: HEAT PUMP COOLING SCHEMATIC. TXVs also act as check valves to allow for the reverse of refrigerant flow. Figure 8: Heat Pump Cooling Schematic Heating Cycle The heat pump operates in the heating cycle by redirecting refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished with the reversing valve. Hot discharge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the compressor. When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve. The following figure, FIGURE 9: HEAT PUMP HEATING SCHEMATIC, shows a schematic of the heat pump in the heating cycle. Figure 10 When the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil temperature, the greater the heating capacity of the heat pump. This phenomenon is a characteristic of a heat pump. It is a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45°F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump, such as a compressor, or refrigerant leak, etc. Since the temperature of the liquid refrigerant in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run, and the supplementary heaters are energized. Defrost Control During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30, 60 and 90 minutes may be selected by setting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 30 ± 5°F), and when the wall thermostat calls for heat. At the end of the timing period, the unit's defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 60°± 5°F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor temperature, a twelve-minute override interrupts the unit's defrost period. Figure 9: Heat Pump Heating Schematic For 5-Ton Heat Pump unit, the expansion devices are Thermal Expansion Devices (TXV) and perform the same function on the heating cycle as on the cooling cycle. The 14 SUGGESTED FIELD TESTING/ TROUBLESHOOTING Testing Defrost Control NOTE: PCBDM133 Defrost controls have a three (3) minute compressor off cycle delay. NOTE: The PCBDM133 defrost controls are shipped from the factory with the compressor delay option selected. This will de-energize the compressor contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to normal, the compressor will continue to run during defrost initiation and defrost termination. The control will also ignore the lowpressure switch connected to R-PS1 and PS2 for 5 minutes upon defrost initiation and 5 minutes after defrost termination. To check the defrost control for proper sequencing, proceed as follows: With power ON; unit not running. 1. Jumper defrost thermostat by placing a jumper wire across the terminals "DFT" and "R"/" R-DFT" at defrost control board. 2. Remove jumper from timer pins and jump across test pins on defrost control board. NOTE: Do not use screwdriver or field supplied jumper to test the control. 3. Set thermostat to call for heating. System should go into defrost within 21 seconds. 4. Immediately remove jumper from test pins. 5. Using VOM check for voltage across terminals "C & O". Meter should read 24 volts. 6. Using VOM check for voltage across fan terminals DF1 and DF2 on the board. Should read line voltage (208-230 VAC) indicating the relay is open in the defrost mode. 7. Using VOM check for voltage across "W"/"W2" & "C" terminals on the board. Should read 24 volts. 8. If not as above, replace control board. 9. Set thermostat to off position and disconnect power. Remove jumper from defrost thermostat and replace timer jumper to the desired defrost time. NOTE: Remove jumper across defrost thermostat before returning system to service. See Figure 11: Defrost control Wiring Diagram. Figure 11: Defrost Control Wiring Schematic Testing Defrost Thermostat 1. Install a thermocouple type temperature test lead on the tube adjacent to the defrost control. Insulate the lead point of contact. 2. Check the temperature at which the control closes its contacts by lowering the temperature of the control. It should close at approximately 30°F. 3. Check the temperature at which the control opens its contacts by raising the temperature of the control. It should open at approximately 60°F. If not as above, replace control. AIR FLOW MEASUREMENT AND ADJUSTMENT After reviewing section on DUCTING, proceed with airflow measurements and adjustments. Unit's blower curves (in Specification Sheets) are based on external static pressure (ESP, in. of W.C.). The duct openings on the unit are considered internal static pressure, so long as ESP is maintained, the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application (i.e., home, building, etc.). In general, 400 CFM per ton of cooling capacity is a rule of thumb. Some applications depending on the sensible and latent capacity requirements may need only 350 CFM or up to 425 CFM per ton. Check condition space load requirements (from load calculations) and equipment expanded ratings data to match CFM and capacity. After unit is set and ducted, verify ESP with a 1" inclined manometer with pitot tubes or a Magnahelic gauge and confirm CFM to blower curves in the specification sheets. All units have multiple speed blower motors. If factory selected speed is not utilized, the speed tap can be changed. NOTE: Never run CFM below 300 CFM per ton, evaporator freezing, or poor unit performance is possible. 15 Total external static pressure 1. Using a digital manometer measure the static pressure of the return duct at the inlet of the unit (Negative Pressure). SEE FIGURE 13: TOTAL EXTERNAL STATIC. 2. Measure the static pressure of the supply duct (Positive Pressure). 3. Add the two readings together. EXAMPLE: Static reading from return duct = -.1" w.c. Static reading from supply duct = .3" w.c. Total external static pressure on this system = .4" w.c. NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. 4. Consult proper table for quantity of air. If the external static pressure exceeds the maximum allowable static, check for closed dampers, dirty filter, undersized or poorly laid out ductwork. Figure 12: Total External Static ADJUSTING SPEED TAP FOR INDOOR BLOWER MOTOR EEM Motor The blower motor speed for the EEM motor is controlled by three 24V low voltage leads: green, yellow, and white. The green lead sets the speed for fan-only mode. The yellow lead sets the speed for cooling and heat pump heating mode (if applicable). EEM Motor Speed Adjustment The white lead sets the speed for electric heat mode (emergency heat and second stage heat, if applicable). The leads are factory connected as follows: Green to T1, Yellow to T2, and White to T3. T1 is the low speed setting and is dedicated to fan-only mode. T2 is medium speed cooling and T3 is medium speed heating. T4 is high speed cooling and T5 is high speed heating. To adjust the blower speed, move the yellow and/or white wires to T4 and T5. NOTE: If more than one lead is energized at the same time, the motor will use the higher speed setting. See appendix for Blower Performance Data tables. [*PH]M3 CFM Delivery and Adjustments See Appendix for CFM Output, Adjustments, and DIP switch settings. [*PH]M3 Thermostat "Fan Only" Mode During Fan Only Operations, the CFM output is 50% of the high stage cooling setting. SUPERHEAT AND SUBCOOLING Checking Subcooling NOTE: Units with a TXV should be charged to Subcooling only. EXAMPLE: a. Liquid Line Pressure = 417 PSI b. Corresponding Temp. = 120°F c. Thermometer on Liquid line = 109°F. To obtain the amount of subcooling, subtract 109°F from 120°F. The difference is 11° subcooling. See the specification sheet or technical information manual for the design subcooling range for your unit. SUBCOOLING FORMULA = SATURATED LIQUID LINE TEMPERATURE - LIQUID LINE TEMPERATURE Checking Superheat EXAMPLE: a. Suction Pressure = 143 PSI b. Corresponding Temp. = 50°F c. Thermometer on Suction Line = 59°F 16 To obtain the degrees temperature of superheat, subtract 50.0 from 59.0°F. The difference is 9° Superheat. The 9° Superheat would fall in the ± range of allowable superheat. SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP. TXV Superheat Adjustment TXV is designed for specific units installed. Therefore, NO adjustments should be needed. NOTE: Superheat adjustments should not be made until indoor ambient conditions have stabilized and correct air flow (CFM) has been verified. This could take up to 24 hours depending on indoor temperature and humidity. Before checking superheat, run the unit in cooling for 15-20 minutes or until refrigerant pressure stabilizes. NOTE: TXV adjustments should not exceed one turn clockwise (CW) or counterclockwise (CCW) from the factory setting. Unscrew the cover from the expansion valve, locate the adjustment screw, and turn in clockwise (in) to increase superheat or counterclockwise (out) to decrease superheat. It is recommended to make small adjustments at a time, 1/8 - 1/4 turn increments. Replace adjustment cap. Wait a minimum of 15 minutes between adjustments to allow time for the TXV and pressure to stabilize. Refrigerant Charge Check NOTE: For optimal performance, follow charging instructions below. Units with TXV Single Stage Cooling Application: Refer to the Design Superheat & Subcooling table. superheat. c. If subcooling and superheat are high, adjust TXV valve superheat, then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve superheat and remove charge to lower the subcooling. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. If an under charge is suspected, recover the charge, reevacuate the system, and recharge per data plate. No adjustments should be made if suspecting a charge issue. 4. Disconnect manifold set, installation is complete. Design Superheat & Subcool Model Superheat Subcool Expansion Cooling Outdoor ±2°F ±1°F Valve Stage Ambient °F *PHM32431 7.5 - Piston High 95 *PHM33031 8.0 - Piston High 95 *PHM33631 10.0 - Piston High 95 *PHM34231 22.0 - Piston High 95 *PHM34831 8.0 - Piston High 95 *PHM36031 16.0 8.0 TXV Low 82 Design Superheat and Subcooling Table RDS Function The mitigation system is a stationary device that detects the presence of R-32 refrigerant above 25% LFL using refrigerant sensors and then initiates mitigation actions. The mitigation system's primary function is to reduce the concentration of leaked R-32 refrigerant to prevent serious safety hazards. The mitigation actions are accomplished by halting HVAC operation and continuing indoor blower operation to provide airflow. Once refrigerant concentration reaches below a safe threshold, the unit will remain in mitigation mode for five minutes to evacuate any remaining R-32 refrigerant within the unit. Upon completion, the unit will resume its normal operation. Two-Stage Cooling Application: Run unit on Low Stage cooling and refer to Design Superheat & Subcooling table. RDS Operation The mitigation system is controlled by a refrigerant 1. Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insulate for best possible reading. 3. Check subcooling and superheat. System should have a subcooling and superheat within the range listed on the Design Superheat and Subcooling table. a. If subcooling and superheat are low, adjust TXV superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clockwise to increase and counterclockwise to decrease. Refer to TXV Superheat Adjustment referenced in this manual. b. If subcooling is low and superheat is high, sensor(s), which is secured to a designated location(s) for active monitoring. If a leak is detected, HVAC operation is disabled and the indoor blower fan is activated, providing airflow at or above minimum required airflow to evacuate excess concentration. If a Zone Control system is installed in the ductwork attached to this system, the Zone controller must be powered through a Daikin Zoning/ Accessory PCB to ensure that the Zoning Dampers open during mitigation mode to provide ventilation throughout all ducting. If the unit is installed with a communicating thermostat, the thermostat will display relevant alerts/ information concerning mitigation mode. Once sensors read concentration levels below a safe threshold, a fiveminute timer will initiate. Once the time is over, the unit will resume back to its normal operation. If the sensors detect another concentration excess, the unit will go back into mitigation mode and will repeat the same process. add charge to raise subcooling then check 17 ELECTRICAL HEAT INSTALLATION & ADJUSTMENT Heater Kit NOTE: A separate power supply is required for HKTPD Heater Kits. Refer to the specification manual for heater kit match up and Heater Kit Electrical Data. This series of electric cooling and heat pump package equipment is designed to accept a field installed electric heat kit. The unit is equipped to easily install the HKTPD Series Electric Heat Kit. Full Installation Instructions are included in this kit. Please use this document for guidance in field equipping the package unit with electric heat. Choose the heat kit that fits the application for the specific installation. Permanently mark the unit's nameplate with the model being installed. High and low voltage connections are detailed in the heat kit instructions. Indoor Blower motor speed tap selection may need to be modified to accommodate normal continuous operation to prevent a nuisance trip. 18 MAINTENANCE WARNING HIGH VOLTAGE! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. The Self-Contained Package Heat Pump should operate for many years without excessive service calls if the unit is installed properly. However, it is recommended that the homeowner inspect the unit before a seasonal start up. The coils should be free of debris so adequate airflow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced. These few steps will help to keep the product up time to a maximum. The Troubleshooting Chart should help in identifying problems if the unit does not operate properly. Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely. Charging Procedures In addition to conventional charging procedures, the following requirements shall be followed. · Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. · Cylinders shall be kept in an appropriate position according to the instructions. · Ensure that the REFRIGERATING SYSTEM is grounded prior to charging the system with refrigerant. · Label the system when charging is complete (if not already). · Extreme care shall be taken not to overfill the REFRIGERATING SYSTEM. NOTE: "Earthing" is defined as achieving an earth ground by connecting the equipment's supplied grounding lug to the earth. This should verified by a certified technician. Prior to recharging the system, it shall be pressuretested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of the flammable refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. The recovered refrigerant shall be processed according to local legislation in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. 19 Part Number HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201 Max E.S.P. IN. W.C kPa 0.8 0.19 0.8 0.19 0.8 0.19 0.8 0.19 0.5 0.12 0.8 0.19 Circuit 1 MCA MOP 28.74 25 36.46 40 49.48 50 49.48 50 49.48 50 49.48 50 Circuit 2 MCA MOP - - - - - - 24.74 25 36.46 25 36.46 25 Output @ 240V kW BTU/hr 4.75 16200 7.00 23800 9.50 32400 14.25 48600 19.00 64800 19.00 64800 *PHM3 Heater Kit Part # M ode l HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201 *PHM32431 X X X *PHM33031 X X X X *PHM33631 X X X X *PHM34231 X X X X *PHM34831 X X X X X *PHM36031 X X X X X Speed Tap Selection for 0.0-0.5 E.S.P. Heater Kit Part # M ode l HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201 *PHM32431 T3 T3 T3 *PHM33031 T3 T3 T3 T5 *PHM33631 T3 T3 T3 T5 *PHM34231 T3 T3 T3 T5 *PHM34831 T3 T3 T3 T3 T5 *PHM36031 T3 T3 T3 T3 T5 Speed Tap Selection for 0.5-0.8 E.S.P. Heater Kit Part # M ode l HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201 *PHM32431 T5 T5 T5 *PHM33031 T5 T5 T5 T5 *PHM33631 T5 T5 T5 T5 *PHM34231 T5 T5 T5 T5 *PHM34831 T5 T5 T5 T5 T5 *PHM36031 T5 T5 T5 T5 T5 20 SERVICE NOTE: The following information is for use by qualified service agency only: Others should not attempt to service this equipment. Common Causes of Unsatisfactory Operation of Heat Pump on the Heating Cycle: Inadequate Air Volume Through Indoor Coil When a heat pump is in the heating cycle, the indoor coil is functioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cut out. Outside Air Into Return Duct Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop below 65°F. Air below this temperature will cause low discharge pressure, thus low suction pressure, and excessive defrost cycling resulting in low heating output. It may also cause false defrosting. Malfunctioning Reversing Valve This may be due to: 1. Solenoid not energized In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized, and the unit is in the cooling cycle. 2. No voltage at unit's solenoid Check unit voltage. If no voltage, check wiring circuit. 3. Valve will not shift: a. Undercharged Check for leaks. b. Valve Body Damaged Replace valve. c. Unit Properly Charged If it is on the heating cycle, raise the discharge pressure by restricting airflow through the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. Do Not Tap the Valve Body. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off, and wait until the discharge and suction pressure equalize, and repeat above steps. If the valve does not shift, replace it. Clean Outdoor Coil (Qualified Servicer Only) The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. Clean Indoor Coil (Qualified Servicer Only) Before cleaning the indoor coil, A2L sensor must be removed from the unit to avoid damage and contamination. Air filters should also be removed before performing maintenance. The coil with the filtered air flowing over it should be inspected and cleaned as frequently as necessary to keep the finned areas free of debris. Coil cleaning should be performed, utilizing an approved cleaning method and cleaning agent, from inside-out (opposite operating airflow direction) to prevent damage to the tube, fin coil, and any other components. Prior to resuming unit operation, ensure to reinstall the A2L sensor. Servicing Measures for the Refrigerant Detection System Before servicing, identify the mode of operation of the system by reading the LED flashing pattern on the PCB within the control box and matching the LED flashing pattern with mode of operation in the REFRIGERANT DETECTION SYSTEM TROUBLESHOOTING GUIDE on the wiring diagram which is attached on the back side of the control box panel (RDS PCB Fault Code table). After identifying the mode of operation, take recommended actions as specified in the Recommended Actions for PCB LED Flashing Codes table. REFRIGERANT SENSORS for REFRIGERANT DETECTION SYSTEMS shall only be replaced with sensors specified by the manufacturer. If REFRIGERANT SENSOR requires replacement, please replace with Sensata R32 Sensor PN#RGD-00ML12 (Daikin PN#SER2A08012). MODE LED STATUS LED FLASHING PATTERN SLOW LED FLASHING PATTERN NORMAL OPERATION (2 SECONDS ON 2 SECONDS OFF) R-32 LEAK ALARM DELAY MODE SYSTEM VERIFICATION MODE CONTROL BOARD INTERNAL FAULT FAST LED FLASHING PATTERN LED WILL BE ON CONTINUOUSLY FAST LED FLASHING PATTERN LED WILL FLASH 2 TIMES AND THEN BE OFF FOR 5 SECONDS R32 SENSOR LED WILL FLASH 3 TIMES AND COMMUNICATION FAULT THEN BE OFF FOR 5 SECONDS LED WILL FLASH 4 TIMES AND R32 SENSOR FAULT THEN BE OFF FOR 5 SECONDS RDS PCB Fault Code Table 21 REVERSING VALVE TROUBLESHOOTING Checking Reversing Valve and Solenoid Reversing valve used in heat pumps could potentially leak internally. Discharge gases can leak into the suction inside the valve. Compound gages will give the same symptoms as bad compressor valves or broken scroll flanks. The temperature between true suction and the suction line after the valve should not be greater than 4 degrees. NOTE: The center tube is always the suction line and should be cold. If voltage is registered at the coil, tap the valve body lightly while switching the system from HEATING to COOLING, etc. If this fails to cause the valve to switch positions, remove the coil connector cap and test the continuity of the reversing valve solenoid coil. If the coil does not test continuous - replace it. If the coil test continuous and 24 volts is present at the coil terminals, the valve is inoperative - replace it. Troubleshooting the Reversing Valve for Electrical Failure 1. Place unit into the cooling mode. Test for 24 volts at the solenoid. If there is no voltage present at coil, check the control voltage. 2. If voltage is present, loosen the nut on the top of the coil. Remove the coil, there should be slight resistance. 3. If the slight resistance is felt, remove the coil. As you remove the coil listen carefully, an audible click should be detected. The clicking is due to the movement of the pilot valve plunger. The absence of a clicking sound indicates the plunger is stuck. Troubleshooting Mechanical Failures on a Reversing Valve by Pressure 1. Troubleshooting the reversing valve can be done by pressure and touch. 2. Raise the head pressure. In the cooling mode block the fan exhaust. Once head pressure has been raised, cycle between cooling and heating and see if the piston can be freed. Troubleshooting Mechanical Failures on a Reversing Valve by Temperature 1. When operating properly the valve contains refrigerant gases at certain temperatures. 2. The discharge line should be the same temperature after the valves discharge line. 3. The true suction should be the same as the suction line after the valve. If there is a 4-degree difference, valve is leaking. Figure 13: Reversing Valve Poor "Terminating" Sensor Contact The unit's defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor contact may not terminate the unit's defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure. Undercharge An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil. When stuck in the mid-position, part of the discharge gas from the compressor is directed back to the suction side, resulting in excessively high suction pressure. An increase in the suction line temperature through the reversing valve can also be measured. Check operation of the valve by starting the system and switching the operation from COOLING to HEATING cycle. If the valve fails to change its position, test the voltage (24V) at the valve coil terminals, while the system is on the COOLING cycle. 22 TROUBLESHOOTING CODE MODE 1 Normal Operation 2 R32 Leak Alarm DEFINITION No faults to report. R32 leak is currently being detected. LED TROUBLESHOOT STATUS LED FLASHING PATTERN RECOMMENDED ACTIONS Slow LED flashing pattern (2 seconds on and 2 seconds off) No actions needed. Fast LED Flashing Pattern A technician will need to find the refrigerant leak and address it. Unit shall be thawed before servicing. NOTES In terms of the controls, no action is needed. The controls and sensor are working fine. No action needed - If the system was previously experiencing an After R32 leak or alarm has been actual R32 Leak, the refrigerant can no longer be detected by 3 Delay Mode cleared, the unit will remain in alarm mode for 5 minutes before returning to LED will be on continuously the sensor meaning it's either gone and the system won't work After any alarm or fault, it is required to remain in anymore or there was a false alarm. If the system was R32 mitigation mode for 5 minutes. normal operation. experiencing a Fault, the fault is gone and the system will return to normal operation in 5 min. Manual test run by contractor to 4 System Verification Mode simulate R32 Leak Alarm (test will last for 5 minutes max). Fast LED Flashing Pattern No actions needed. To enter system verification test mode, press the button on the control 2 times within 5 seconds. The control will enter a simulated R32 Leak Alarm state and remain in that mode for 5 minutes. After 5 minutes, the control will return to Normal Operation automatically. If the contractor wants to end the test early they need to press the button one time. 5 Control Board Internal Fault Control board has detected an issue with the R32 detection system. 1) Unplug and plug the R32 sensor back in. Cycle power to the system. 2) If the control is in "Normal Operation" or "Delay Mode", This error could indicate an on board relay failure or LED will flash 2 times and then be off for 5 seconds, before repeating pattern there is no more issue. If not, continue with diagnostics 3) Unplug R32 sensor and leave unplugged. Cycle power to the system 4) If the control still displays "Control Board Internal Fault" (2 a short with the sensor communications. A sensor communication short could occur on the board itself or external to the board. These steps will determine if the error is on the board or external to flash pattern), replace the control. If the control now displays the board. "R32 Sensor Communication Fault" (3 flash pattern), replace the sensor. 6 R32 Sensor Communication Fault Control board does not have communications with R32 sensor. LED will flash 3 times and then be off for 5 seconds, before repeating pattern 1) Unplug and plug the R32 sensor back in. Cycle power to the system. 2) If control is in "Normal Operation" or "Delay Mode", there is no more issue. If not, continue with diagnostics. 3) If the control still displays "R32 Sensor Communication Fault" (3 flash pattern), replace both the sensor and the PCB. If the control cannot talk to the sensor there could be a problem with the sensor, a problem with the sensor harness or a problem internal to the control. The field will not be able to measure anything to reliably fix this error assuming the connector is properly secured to the control. Replacing both is the only option. 7 R32 Sensor Fault R32 Sensor has reported an internal issue. LED will flash 4 times and then be off for 5 seconds, before repeating pattern Replace R32 sensor. Recommended Actions for PCB LED Flashing Codes Table Communications to the sensor are perfectly fine. The sensor itself is reporting an internal fault. warning; flammable materials service indicator; read technical manual operator's manual; operating instructions warning; low burning velocity material UN GHS flame symbol Marking Symbol Table 23 TROUBLESHOOTING CHART SYMPTOM High head - low suction High head - high or normal suction Low head - high suction Unit will not run Condenser fan runs, compressor doesn't Low suction - cool compressor Iced evaporator coil Compressor short cycles Registers sweat High suction pressure Insufficient cooling Evaporator coil freezing or frosting POSSIBLE CAUSE a. Restriction in liquid line or flowrator a. Dirty condenser coil b. Overcharged c. Condenser fan not running a. Incorrect flowrator b. Defective compressor valves c. Flowrator not seating properly a. Power off or loose electrical connection REMEDY a. Remove or replace with proper size flowrator. a. Clean coil b. Correct System charge c. Repair or Replace a. Replace with correct flowrator b. Replace compressor c. Check for debris under flowrator or deformed flowrator. Remove debris or replace flowrator. a. Check for unit voltage at contactor in unit b. Thermostat out of calibration set too high b. Reset c. Defective contactor c. Check for 24 volts at contactor coil replace if contacts are open d. Blown fuses or tripped breaker d. Replace fuse or reset breaker Check wiring replace transformer e. Transformer defective f. High or low pressure control open (Optional) f. Reset high pressure control or check unit charge High pressure control opens at 610 psig g. Compressor overload contacts open Low pressure control opens at 22 psig g. Replace compressor NOTE: Wait at least 2 hours for overload to reset a. Loose connection a. Check for unit voltage at compressor check & tighten all connections b. Compressor stuck, grounded or open winding open internal overload b. Wait at least 2 hours for overload to reset If still open, replace the compressor. c. Low voltage connection c. At compressor terminals, voltage must be within 10 % of nameplate volts when unit is operating d. Capacitor weak, open, or shorted d. Check capacitor. If defective, replace. a. Low indoor airflow a. Defective overload protector b. Unit cycling on low pressure control a. Increase speed of blower or reduce restriction - replace air filters a. Replace - check for correct voltage b. Check refrigerant charge and / or airflow c. High pressure switch cuts out c. Check airflow (Indoor & outdoor) a. Low airflow a. Excessive load b. Defective compressor c. Reversing valve not seating properly. a. Improperly sized unit b. Improper airflow a. Increase speed of blower or reduce restriction replace air filters a. Recheck load calculation b. Replace c. Replace a. Recalculate load b. Check - should be approximately 400 CFM per ton c. Incorrect refrigerant charge. d. Incorrect voltage a. Low airflow b. Low refrigerant charge c. Operating unit in cooling mode below 65°F outdoor temperature 24 c. Charge per procedure attached to unit service panel d. At compressor terminals, voltage must be within 10% of nameplate volts when unit is operating a. Check - should be approximately 400 CFM per ton, dirty air filters, all duct outlets open b. Properly charge unit c. Install or check low ambient control, should be open below 65°F outdoor temperature *PHM3[24-60]31** BLOWER PERFORMANCE DATA Model Motor Compresor Tap Stage Volts T1 Single Stage 230 *PHM36031** *PHM34831** *PHM34231** *PHM33631** *PHM533031** *PHM32431** T2/T3 Single Stage 230 T4/T5 Single Stage 230 T1 Single Stage 230 T2/T3 Single Stage 230 T4/T5 Single Stage 230 T1 Single Stage 230 T2/T3 Single Stage 230 T4/T5 Single Stage 230 T1 Single Stage 230 T2/T3 Single Stage 230 T4/T5 Single Stage 230 T1 Single Stage 230 T2/T3 Single Stage 230 T4/T5 Single Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts Horizontal Flow E.S.P. (In. of H O) 0.1 0.2 0.3 0.4 0.5 847 792 728 638 - 76 84 94 102 - 1043 1020 922 906 856 166 168 179 185 194 1371 1306 1281 1240 1186 235 243 252 261 266 877 821 758 674 596 84 92 99 110 118 1276 1223 1175 1128 1077 221 232 241 250 257 1463 1419 1376 1329 1282 284 294 302 309 317 850 795 726 640 559 76 85 93 103 110 1399 1360 1288 1240 1190 281 291 298 305 313 1604 1560 1507 1468 1415 396 402 408 424 426 1003 937 887 837 773 100 106 116 129 142 1487 1447 1407 1363 1318 269 279 291 302 309 1799 1754 1712 1672 1630 419 430 442 453 462 1177 1123 1077 1031 972 142 151 162 173 185 1838 1794 1749 1711 1672 448 458 468 479 490 1984 1947 1975 1864 1823 567 578 590 596 603 1499 1447 1404 1376 1130 268 278 290 300 311 2001 1958 19008 1865 1822 569 583 595 600 613 2199 2161 2126 2090 2056 801 809 817 828 838 0.6 - 713 203 1133 275 531 125 1025 264 1235 325 1136 322 1364 433 699 154 1274 321 1582 469 1626 497 1781 610 1280 325 1774 622 2018 851 0.7 - 623 209 1072 284 481 130 985 271 1183 333 1083 329 1321 444 631 162 1229 332 1534 475 1576 503 1741 618 1230 338 1729 629 1918 858 0.8 - 635 206 1000 293 914 279 1126 340 1017 336 1276 454 574 171 1165 340 1482 481 1528 510 1694 623 1145 353 1680 638 1949 873 NOTES: · Data shown is dry coil. Wet coil pressure drop is approximately: 0.1" H2O, for two-row indoor coil; 0.2" H2O, for three-row coil; and 0.3" H2O, for four-row indoor coil. · Data shown does not include filter pressure drop, approx. 0.08" H2O. · Reduce airflow by 2% for 208-volt operation. 25 *PHM3[24-60]31** BLOWER PERFORMANCE DATA Model Motor Compresor Tap Stage Volts T1 Low Stage 230 *PHM36031** *PHM34831** *PHM34231** *PHM33631** *PHM533031** *PHM32431** T2/T3 High Stage 230 T4/T5 High Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 T1 Low Stage 230 T2/T3 High Stage 230 T4/T5 High Stage 230 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts Down Flow 0.1 828 75 1086 157 1355 244 859 83 1303 225 1439 288 825 77 1321 285 1595 382 981 100 1458 266 1786 419 1168 144 1841 438 2004 564 1464 247 1999 546 2067 821 0.2 767 85 993 169 1300 253 797 92 1236 236 1396 297 762 87 1319 291 1555 391 918 113 1418 277 1728 432 1101 155 1786 451 1949 577 1408 264 1957 563 2031 829 E.S.P. (In. of H O) 0.3 0.4 0.5 680 574 - 95 104 - 963 852 768 176 187 194 1254 1201 1147 260 268 276 719 619 552 101 111 118 1178 1123 1075 247 254 262 1341 1294 1246 305 313 322 686 577 523 97 105 111 1222 1170 1119 300 309 319 1506 1462 1415 399 408 418 850 761 687 126 138 153 1379 1336 1291 288 299 307 1678 1629 1577 445 457 468 1045 979 913 168 182 197 1735 1691 1646 463 473 485 1892 1837 1782 587 594 603 1364 1326 1285 281 292 305 1904 1862 1822 577 587 598 1999 1964 1932 838 849 859 0.6 - 672 205 1084 285 497 122 1015 271 1185 330 1077 324 1370 426 613 161 1249 318 1517 474 1598 493 1728 612 1240 317 1769 606 1897 872 0.7 - 637 215 1007 294 437 127 956 279 1119 339 1005 333 1319 435 553 171 1204 330 1453 482 1544 500 1674 620 1201 334 1732 615 1863 880 0.8 - 621 228 899 303 884 287 1047 347 930 342 1260 444 488 179 1141 337 1385 490 1489 508 1616 628 1140 351 1688 625 1832 895 NOTES: · Data shown is dry coil. Wet coil pressure drop is approximately: 0.1" H2O, for two-row indoor coil; 0.2" H2O, for three-row coil; and 0.3" H2O, for four-row indoor coil. · Data shown does not include filter pressure drop, approx. 0.08" H2O. · Reduce airflow by 2% for 208-volt operation. 26 UNIT DIMENSIONS Model *PHM32431 *PHM33031 *PHM33631 *PHM34231 *PHM34831 *PHM36031 Unit Dimensions Height WD A B Chassis Size 47 51 32 34 3/4 Medium 47 51 32 34 3/4 Medium 47 51 32 34 3/4 Medium 47 51 40 42 3/4 Large 47 51 40 42 3/4 Large 47 51 40 42 3/4 Large Model *PHM32431 *PHM33031 *PHM33631 *PHM34231 *PHM34831 *PHM36031 Duct Openings Supply Return WHW H 16 16 16 16 16 16 16 16 16 16 16 16 16 18 16 18 16 18 16 18 16 18 16 18 27 WIRING DIAGRAM *PHM3[24-42]31* HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL PS2 YL R-PS1 C BL C BK C-RV PU CNT BK O-RV OR O PU Y WH W RD R BR DFT BR R-DFT RD DF1 PU DF2 DEFROST CONTROL PCB RDS RDS ALARM PLM1 NOT USED 1 1 EEV/10V_IN 2 2 WH EEV/10V_OUT 3 3 GY CTM/OD_OUT 4 4 GY R_ID_OUT 5 5 RD COM 6 6 RD COM 7 7 BL 24VAC 8 8 PK PORT1 5V 2 1 C R32 SENSOR SEE NOTE 3 BK 240V PU COM TR BL GR PK BL WH A B WH WH WH GY BL BL BL BL C D LVTB BL BL PU RD RC RD BR F C O M RD RD YL H YL SA SEE NOTE 4 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 PLM PLF BK BK BR YL YL BR PU PU BK BK BR YL YL BR PU PU BK BK YL/PK YL/PK BR BR BL/PK BL/PK RVC LPS DFT HPS PU BK PLF PLM PU BK EHK EHK PLM PLF 11 22 33 4 4 BL 5 5 BR 6 6 WH 77 88 99 BL WH BR BL GY YL GR BL WH BR BL WH YL GR PU BR BK PU BR BK BL BK PU PU GR C L GN 1 2 3 45 GR BM SEE NOTE 2 GR YL WH BR BK CM YL BK RD S CR COMP SEE NOTE 7 CC RD T2 L2 PU RD PU T1 L1 BK BK BK BK A2 A1 BL PU YL LINE VOLTAGE 208V/230V/1PH/60Hz SEE NOTE 1 GND LVJB RD BL WH BR GR OR PU R C W1 THERMOSTAT W2 SEE NOTE 5 G O Y CONTROL BOX NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C). USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. 2. TO CHANGE BLOWER MOTOR SPEED MOVE YELLOW AND WHITE LEADS FROM BM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED 5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE 6. CRANKCASE HEATER (OPTIONAL) 7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION. SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION COMPONENT LEGEND BM CC CH CHS CM COMP CS DFT ECON EHK GND HPS BLOWER MOTOR LPS LOW PRESSURE SWITCH COMPRESSOR CONTACTOR LVJB LOW VOLTAGE JUNCTION BOX CRANKCASE HEATER LVTB LOW VOLTAGE TERMINAL BLOCK CRANKCASE HEATER SWITCH OWV ONE WAY VALVE CONDENSER MOTOR PLF FEMALE PLUG/CONNECTOR COMPRESSOR PLM MALE PLUG/CONNECTOR COMP SOLENOID (2ND STG COOLING) RC RUN CAPACITOR DEFROST THERMOSTAT RDS REFRIGERANT DETECTION SYSTEM ECONOMIZER RVC REVERSING VALVE COIL ELECTRIC HEATER KIT SA START ASSIST EQUIPMENT GROUND TR TRANSFORMER HIGH PRESSURE SWITCH JUNCTION EQUIPMENT GROUND TERMINAL FIELD GROUND SWITCH (PRESS.) FIELD SPLICE CONNECTOR SWITCH (TEMP) LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL FOR MORE DETAILS. RED LED'S STATUS MODE CHECK 1 FLASH STARTUP MODE - SLOW LED FLASHING NORMAL OPERATION - FAST LED FLASHING R-32 LEAK ALARM LEAK DETECTED. FIND AND REPAIR THE SOURCE OF THE LEAK. LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES. FAST LED FLASHING SYSTEM VERIFICATION MODE USER ACTIVATED TEST MODE. 2 FLASHES INTERNAL FAULT REPLACE CONTROL BOARD. 3 FLASHES R-32 SENSOR COMMUNICATION FAULT VERIFY REFRIGERANT SENSOR WIRING. REPLACE SENSOR. REPLACE CONTROL BOARD. 4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR. WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW BL/PNK BLUE/PINK STRIPE WIRING HIGH VOLTAGE LOW VOLTAGE FIELD INSTALLED POWER FIELD INSTALLED CONTROL OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE 0140G04671-A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 28 WIRING DIAGRAM *PHM34831* HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL PS2 YL R-PS1 C BL C BK C-RV PU CNT BK O-RV OR O PU Y WH W RD R BR DFT BR R-DFT RD DF1 PU DF2 DEFROST CONTROL PCB RDS RDS ALARM PLM1 NOT USED 1 1 EEV/10V_IN 2 2 WH EEV/10V_OUT 3 3 GY CTM/OD_OUT 4 4 GY R_ID_OUT 5 5 RD COM 6 6 RD COM 7 7 BL 24VAC 8 8 PK PORT1 5V 2 1 C R32 SENSOR SEE NOTE 3 BK 240V PU COM TR BL GR PK BL WH A B WH WH WH GY BL BL BL BL C D LVTB BL BL BR PU RD RC RD BR F C O M RD RD YL H YL SA SEE NOTE 4 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 PU BK GR BK BK BR YL YL BR PU PU GR PLM PLF PU BK GR BK BK BR YL YL BR PU PU BK PU CH GR RD RD BK CHS BK BK YL/PK YL/PK BR BR BL/PK BL/PK RVC LPS DFT HPS PU BK PLF PLM PU BK EHK EHK PLM PLF 11 22 33 4 4 BL 5 5 BR 6 6 WH 77 88 99 BL WH BR BL GY YL GR BL WH BR BL WH YL GR PU BR BK PU BR BK BL BK PU PU GR C L GN 1 2 3 45 GR BM SEE NOTE 2 GR YL WH BR BK CM YL BK RD S CR COMP SEE NOTE 7 CC PU RD T2 L2 PU RD PU T1 L1 BK BK BK BK A2 A1 BK BL PU YL LINE VOLTAGE 208V/230V/1PH/60Hz SEE NOTE 1 GND LVJB RD BL WH BR GR OR PU R C W1 THERMOSTAT W2 SEE NOTE 5 G O Y CONTROL BOX NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C). USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. 2. TO CHANGE BLOWER MOTOR SPEED MOVE YELLOW AND WHITE LEADS FROM BM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED 5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE 6. CRANKCASE HEATER (OPTIONAL) 7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION. SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION COMPONENT LEGEND BM CC CH CHS CM COMP DFT ECON EHK GND HPS LPS BLOWER MOTOR COMPRESSOR CONTACTOR CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMPRESSOR DEFROST THERMOSTAT ECONOMIZER ELECTRIC HEATER KIT EQUIPMENT GROUND HIGH PRESSURE SWITCH LOW PRESSURE SWITCH LVJB LVTB PLF PLM RC RDS RVC SA TR LOW VOLTAGE JUNCTION BOX LOW VOLTAGE TERMINAL BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR RUN CAPACITOR REFRIGERANT DETECTION SYSTEM REVERSING VALVE COIL START ASSIST TRANSFORMER JUNCTION EQUIPMENT GROUND TERMINAL FIELD GROUND SWITCH (PRESS.) FIELD SPLICE CONNECTOR SWITCH (TEMP) LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL FOR MORE DETAILS. RED LED'S STATUS MODE CHECK 1 FLASH STARTUP MODE - SLOW LED FLASHING NORMAL OPERATION - FAST LED FLASHING R-32 LEAK ALARM LEAK DETECTED. FIND AND REPAIR THE SOURCE OF THE LEAK. LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES. FAST LED FLASHING SYSTEM VERIFICATION MODE USER ACTIVATED TEST MODE. 2 FLASHES INTERNAL FAULT REPLACE CONTROL BOARD. 3 FLASHES R-32 SENSOR COMMUNICATION FAULT VERIFY REFRIGERANT SENSOR WIRING. REPLACE SENSOR. REPLACE CONTROL BOARD. 4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR. WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW/PINK STRIPE BL/PK BLUE/PINK STRIPE TN TAN WIRING HIGH VOLTAGE LOW VOLTAGE FIELD INSTALLED POWER FIELD INSTALLED CONTROL OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE 0140G04686-A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 29 WIRING DIAGRAM *PHM36031* HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. GR PU RD RD CHS YL PS2 YL R-PS1 C BL C BK C-RV PU CNT BK O-RV OR O PU Y WH W RD R BR DFT BR R-DFT RD DF1 PU DF2 DEFROST CONTROL PCB RDS RDS ALARM PLM1 NOT USED 1 1 EEV/10V_IN 2 2 WH EEV/10V_OUT 3 3 GY CTM/OD_OUT 4 4 GY R_ID_OUT 5 5 RD COM 6 6 RD COM 7 7 BL 24VAC 8 8 PK PORT1 5V 2 1 C R32 SENSOR SEE NOTE 3 BK 240V PU COM TR BL GR PK BL WH A B WH WH WH GY BL BL BL BL C D LVTB BL BL BL PU RD RC RD BR F C O M RD RD YL H YL SA SEE NOTE 4 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 11 22 33 44 55 66 77 88 99 10 10 11 11 12 12 PU BK GR BK BK BR YL YL BR PU PU PLM PLF PU BK GR BK BK BR YL YL BR PU PU BK CH GR BK BK YL/PK YL/PK BR BR BL/PK BL/PK BK RVC LPS DFT HPS PU BK PLF PLM PU BK EHK EHK PLM PLF 11 22 33 4 4 BL 5 5 BR 6 6 WH 77 88 99 BL WH BR BL GY YL GR BL WH BR BL WH YL GR PU BR BK PU BR BK BL BK PU PU GR C L GN 1 2 3 45 GR BM SEE NOTE 2 GR YL WH BR BK CM SEE NOTE 7 CC PU RD T2 L2 PU RD PU T1 L1 BK BK BK BK A2 A1 BK BL YL PU YL 42 YL YL CSR 31 BL CSR LVJB RD BL WH BR GR OR PU YL YL BK RD S CR BL COMP SOL YL LINE VOLTAGE 208V/230V/1PH/60Hz SEE NOTE 1 GND R C W1 THERMOSTAT W2 SEE NOTE 5 G O Y1 Y2 CONTROL BOX NOTES: 1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105°C). USE COPPER CONDUCTORS ONLY. USE NEC CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS. 2. TO CHANGE BLOWER MOTOR SPEED MOVE YELLOW AND WHITE LEADS FROM BM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED 5. USE COPPER CONDUCTORS ONLY USE N.E.C. CLASS 2 WIRE 6. CRANKCASE HEATER (OPTIONAL) 7. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION. SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION COMPONENT LEGEND BM CC CH CHS CM COMP CSR DFT ECON EHK GND HPS LPS BLOWER MOTOR COMPRESSOR CONTACTOR CRANKCASE HEATER CRANKCASE HEATER SWITCH CONDENSER MOTOR COMPRESSOR COMPRESSOR SOLENOID RELAY DEFROST THERMOSTAT ECONOMIZER ELECTRIC HEATER KIT EQUIPMENT GROUND HIGH PRESSURE SWITCH LOW PRESSURE SWITCH LVJB LVTB PLF PLM RC RDS RVC SA SOL TR LOW VOLTAGE JUNCTION BOX LOW VOLTAGE TERMINAL BLOCK FEMALE PLUG/CONNECTOR MALE PLUG/CONNECTOR RUN CAPACITOR REFRIGERANT DETECTION SYSTEM REVERSING VALVE COIL START ASSIST SOLENOID TRANSFORMER JUNCTION EQUIPMENT GROUND TERMINAL FIELD GROUND SWITCH (PRESS.) FIELD SPLICE CONNECTOR SWITCH (TEMP) LEAK DETECTION SYSTEM INSTALLED. UNIT MUST BE POWERED EXCEPT FOR SERVICE. SEE USER MANUAL FOR MORE DETAILS. RED LED'S STATUS MODE CHECK 1 FLASH STARTUP MODE - SLOW LED FLASHING NORMAL OPERATION - FAST LED FLASHING R-32 LEAK ALARM LEAK DETECTED. FIND AND REPAIR THE SOURCE OF THE LEAK. LED ON CONTINUOUSLY DELAY MODE MODE WILL CLEAR AFTER 5 MINUTES. FAST LED FLASHING SYSTEM VERIFICATION MODE USER ACTIVATED TEST MODE. 2 FLASHES INTERNAL FAULT REPLACE CONTROL BOARD. 3 FLASHES R-32 SENSOR COMMUNICATION FAULT VERIFY REFRIGERANT SENSOR WIRING. REPLACE SENSOR. REPLACE CONTROL BOARD. 4 FLASHES R-32 SENSOR FAULT REPLACE SENSOR. WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL/PK YELLOW/PINK STRIPE BL/PK BLUE/PINK STRIPE TN TAN WIRING HIGH VOLTAGE LOW VOLTAGE FIELD INSTALLED POWER FIELD INSTALLED CONTROL OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE 0140G04678-A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. 30 PACKAGE UNITS - HEAT PUMP AND AC UNITS HOMEOWNER'S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. Replace or Clean Filter WARNING HIGH VOLTAGE! Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire. Aluminum Indoor Coil Cleaning (Qualified Servicer Only) This unit is equipped with an aluminum tube evaporator coil. The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential cooling coils. An alternate cleaning method is to use one of the products listed in the technical publication TP-109 (shipped in the literature bag with the unit) to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is available on the web site in Partner Link > Service Toolkit. A return air filter is not supplied with this unit; however, there must be a means of filtering the return air. An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort system clean. A dirty coil could cause poor operation and/ or severe equipment damage. The installer of your unit can tell you where your filter(s) are and how to clean or replace them. Check your return filter(s) at least once every two months. When they are dirty, replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned. NOTE: Reusable type filters should be washed with warm water, dried completely and sprayed with an adhesive according to the manufacturers recommendations. You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic types. These filters can do a better job of catching small airborne particles. NOTE: Ensure coils are rinsed well after use of any chemical cleaners. Annual Inspection (Qualified Servicer Only) Your package unit should be inspected by a qualified installer, or service agency at least twice every year. This check should be performed before the heating and cooling seasons begin. This will ensure that the system is performing properly and safely. Repair as necessary. · Check physical support of the unit. Ensure it is sound without any sagging, cracks, or gaps, around the base. · Check for obvious signs of deterioration of the unit. · Check both condenser and evaporator coil to make sure each are clean. · Return Air Connection. Check for physical soundness and ensure that the connection is firmly sealed to the package unit casing. · Wiring. Check wires for damage. Check electrical connections for tightness and/or corrosion. · Filters. Check that filters are clean and in the proper placement in the unit or duct system. · Louvers. Inspect air inlet louvers inside the heat exchanger compartments. Ensure the area is clean and free of dirt and debris. Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as required. When replacing a filter, it must be replaced with a filter of the same type and size and always make certain the air flow arrows on the filter point in the proper direction. Before Calling Your Servicer · Check the thermostat to confirm that it is properly set. · Check the disconnect switch near the unit to confirm that it is closed. · Check the electrical panel for tripped circuit breakers or open fuses. Reset the circuit breakers or replace fuses as necessary. · Check for blockage of the indoor air inlets and outlets. Condenser and Evaporator Motors The bearings on the air circulating blower motor and condenser motor are permanently lubricated and require no further lubrication. Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture). · Check for obstructions on the unit. Confirm that it has not been covered on the sides or the top. Remove any obstruction that can be safely removed. If the unit Compressor The compressor motor is hermetically sealed and does not require additional oiling. 31 is covered with dirt or debris, call a qualified servicer to clean it. · Check the filter. If it is dirty, clean or replace it. START-UP CHECKLIST Residential Package - (Indoor Section) ELECTRICAL Line Voltage (Measure L1 and L2 Voltage) Secondary Voltage (Measure Transformer Output Voltage) Blower Amps Heat Strip 1 - Amps Heat Strip 2 - Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static Pressure Total External Static Pressure (Ignoring +/- from the reading above, add total here) TEMPERATURES Return Air Temperature (Dry bulb / Wet bulb) Cooling Supply Air Temperature (Dry bulb / Wet bulb) Heating Supply Air Temperature Temperature Rise Delta T (Difference between Supply and Return Temperatures) GAS PRESSURES Gas Inlet Pressure Gas Manifold Pressure (Low Fire) Gas Manifold Pressure (High Fire) Model Number Serial Number L1 - L2 R - C Gas Type (NG) = Natural Gas / (LP) = Liquid Propane Residential Package - (Outdoor Section) ELECTRICAL Supply Voltage (Measure L1 and L2 Voltage) Compressor Amps Condenser Fan Amps PRESSURES / TEMPERATURES Suction Circuit (Pressure / Suction Line Temperature) Liquid Circuit (Pressure / Liquid Temperature) Outdoor Air Temperature (Dry bulb / Wet bulb) SUPERHEAT / SUBCOOLING L1 - L2 PSIG PSIG SH Additional Checks Check wire routings for any rubbing Check product for proper draining Check for kinked pressure switch tubing. Check flue elbow for alignment and clamp tightness. Check screw tightness on blower wheel. Check factory wiring and wire connections. Check screw tightness on Outdoor Motor and Blade Check product for proper clearances as noted by installation instructions °F to °C formula: (°F - 32) divided by 1.8 = °C °C to °F formula: (°C multiplied by 1.8) + 32 = °F IN. W.C. IN. W.C. IN. W.C. DB °F DB °F DB °F DB °F DB °F IN. W.C. IN. W.C. IN. W.C. WB °F WB °F TEMP TEMP DB °F SC °F °F WB °F 32 THIS PAGE IS LEFT INTENTIONALLY BLANK. 33 THIS PAGE IS LEFT INTENTIONALLY BLANK. 34 THIS PAGE IS LEFT INTENTIONALLY BLANK. 35 CUSTOMER FEEDBACK We are very interested in all product comments. Please fill out the feedback form on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page. GOODMAN® BRAND AMANA® BRAND Our continuing commitment to quality products may mean a change in specifications without notice. © 2024-2025 Daikin Comfort Technologies Manufacturing, L.P. 19001 Kermier Rd. Waller, TX 77484 www.goodmanmfg.com · www.amana-hac.com is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved. 36