Rinnai Inverter Multi Split System Models

Outdoor Units: MON3H07B, MON4H09B, MON5H11B

Indoor Wall Units: HINRP20M, HINRP26M, HINRP35M, HINRP50M, HINRP60M, HINRP70M

Indoor Ducted Units: DINSD26MB, DINSD35MB, DINSD50MB, DINSD70MB

Indoor Cassette Units: CIN020MB, CIN026MB, CIN035MB, CIN050MB

Refrigerant: R32

Multi Split Type Air Conditioner Installation Manual

Important Safety Information

Read this manual and the SAFETY MANUAL carefully before installing or operating your new air conditioning unit. Save this manual for future reference.

Please check the applicable models, technical data, and manufacturer information from the "Operation Manual" included with the outdoor unit.

This appliance must be installed in accordance with:

This appliance must be installed, maintained, and removed only by an Authorised Person.

For continued safety, the appliance must be installed and maintained according to the manufacturer's instructions.

The design and specifications are subject to change without prior notice for product improvement. Consult the Dealer or manufacturer for details. Any updates to the manual will be uploaded to the service website; please check for the latest version.

Safety Precautions

Warning: This symbol indicates the possibility of personnel injury or loss of life.

Caution: This symbol indicates the possibility of property damage or serious consequences.

Warnings for Product Use

Cleaning and Maintenance Warnings

Cautions

Electrical Warnings

Fuse Specifications

The circuit board has a fuse for overcurrent protection. Specifications are printed on the board (e.g., T20A/250VAC for units <24000Btu/h, T30A/250VAC for units >24000Btu/h). For R32 or R290 refrigerant units, only blast-proof ceramic fuses are permitted.

Warnings for Product Installation

  1. Installation must be performed by an authorized dealer or specialist to prevent water leakage, electrical shock, or fire.
  2. Improper installation can cause water leakage, electrical shock, or fire.
  3. Contact an authorized service technician for repair or maintenance. Installation must comply with national wiring regulations.
  4. Use only included or specified parts; non-standard parts can cause leaks, shock, fire, or unit failure.
  5. Install the unit in a firm location capable of supporting its weight to prevent injury or damage from drops.
  6. Install drainage piping correctly to prevent water damage.
  7. If the unit has an auxiliary electric heater, keep it at least 1 meter (3 feet) from combustible materials.
  8. Do not install near potential combustible gas leaks.
  9. Do not turn on power until all work is completed.
  10. Consult experienced service technicians for moving or relocating the unit.
  11. Refer to "indoor unit installation" and "outdoor unit installation" sections for support details.

Note on Fluorinated Gases

This unit contains fluorinated greenhouse gases. Refer to the unit label or Owner's Manual for gas type and amount. Installation, service, maintenance, and repair must be performed by a certified technician. Uninstallation and recycling also require a certified technician. Units with 5 tonnes or more of CO2 equivalent of fluorinated gases require leak checks every 24 months if a leak-detection system is installed. Record-keeping of checks is recommended.

Warning for Refrigerant (Including R32)

Certain refrigerants, including R32, require minimum room sizes for standard installations. Consult AS/NZS 60335.2.40 for safe minimum floor area if larger refrigerant charges are used.

Warning for Using R32 Refrigerant

For R32 refrigerant models, the appliance shall be installed, operated, and stored in a well-ventilated area with a floor area corresponding to specified room sizes. Do not install in unventilated spaces if the area is smaller than specified.

Disposal Guidelines

This appliance contains refrigerant and other hazardous materials. Dispose of it according to law, requiring special collection and treatment. Do not dispose of as household or unsorted municipal waste. Improper disposal endangers health and the environment, as hazardous substances may leak into groundwater.

Mandatory Inspection Prior to Installation

Report any damage or discrepancies to the Supplier immediately. Inspect the exterior for shipping damage upon receipt. Ensure the appliance is correctly labeled for gas and electrical supply. Damaged or incorrect appliances must not be installed or operated, as this may contravene local regulations. Rinnai disclaims liability for installation or operation of damaged appliances.

Technical Specifications

Multi Outdoor Unit

MON3H07B MON4H09B MON5H11B
Number of Indoor Units 3 4 5
Power Supply (To Outdoor Unit) 220~240-1-50 220~240-1-50 220~240-1-50
Cooling Rated Capacity (Range) 7.5 (1.7-9.8) kW 9.15 (1.7-11.5) kW 12.0 (1.7-12.3) kW
Cooling Rated Input Power 1.98 kW 2.38 kW 3.42 kW
Cooling Rated Input Current 8.90 A 10.09 A 15.65 A
Cooling AEER 3.79 W/W 3.84 W/W 3.51 W/W
Heating Rated Capacity 7.4 (1.8-9.6) kW 9.6 (1.8-12.0) kW 12.5 (1.8-12.9) kW
Heating Rated Input Power 1.59 kW 2.25 kW 3.10 kW
Heating Rated Input Current 7.28 A 10.30 A 14.19 A
Heating ACOP 3.80 W/W 3.86 W/W 3.43 W/W
Maximum Input Current 17.5 A 19.0 A 19.0 A
Compressor Type Inverter Twin Rotary
Sound Power Level 65 dB(A) 68 dB(A) 72 dB(A)
Dimensions (Net W x D x H) 890 x 342 x 673 mm 946 x 410 x 810 mm 946 x 410 x 810 mm
1030 x 438 x 750 mm 1090 x 500 x 885 mm 1090 x 500 x 885 mm
Net / Gross Weight 48 / 51 kg 66 / 72 kg 76 / 82 kg
Refrigerant Type R32
Connection Size: Liquid Line 3 x 6.35 mm 4 x 6.35 mm 5 x 6.35 mm
Connection Size: Gas 3 x 9.52 mm 3 x 9.52 + 1 x 12.7 mm 4 x 9.52 + 1 x 12.7 mm
Maximum Total System Pipe Length 60 m 80 m 80 m
Pre-Charged Length 30 m 40 m 50 m
Maximum Length Per Indoor Unit 30 m 35 m 35 m
Maximum Vertical Separation Outdoor Unit ABOVE Indoor Unit 10 m 10 m 10 m
Maximum Vertical Separation Outdoor Unit BELOW Indoor Unit 15 m 15 m 15 m
Maximum Height Difference Between Indoor Units 10 m 10 m 10 m
Ambient Temperature Limits (Cooling) -15~50 C -15~50 C -15~50 C
Ambient Temperature Limits (Heating) -25~30 C -25~30 C -25~30 C

Wall Mounted Split System

HINRP20M HINRP26M HINRP35M HINRP50M HINRP60M HINRP70M
Power Supply 220~240-1-50 V-Ph-Hz
Cooling Rated Capacity 2.0 kW 2.6 kW 3.5 kW 5.0 kW 6.0 kW 7.0 kW
Cooling Rated Input Power 415 W 530 W 820 W 1300 W 1800 W 1950 W
Cooling Rated Input Current 1.8 A 2.5 A 3.8 A 5.8 A 8.0 A 8.7 A
Heating Rated Capacity 2.2 kW 2.7 kW 4.0 kW 5.2 kW 6.2 kW 7.5 kW
Heating Rated Input Power 460 W 920 W 920 W 1350 W 1700 W 1950 W
Heating Rated Input Current 2 A 2.5 A 5 A 6 A 7.5 A 8.7 A
Airflow (Turbo/ Hi / Med / Lo / Min) 153/128/94/75/47 L/s 175/139/100/83/56 L/s 183/147/106/86/58 L/s 264/222/167/139/89 L/s 264/222/167/139/89 L/s 382/303/250/229/147 L/s
Sound Pressure (Turbo/ Hi / Med / Lo / Min) @1.0m 43/38/31/30/25 dB(A) 46/39/32/30/24 dB(A) 46/39/32/30/24 dB(A) 47/44/38/34/28 dB(A) 47/44/38/34/28 dB(A) 57/39/33/29 dB(A)
Dimensions (Net W x D x H) 729 x 200 x 291 mm 802 x 200 x 295 mm 802 x 200 x 295 mm 971 x 228 x 321 mm 971 x 228 x 321 mm 1082 x 234 x 337 mm
965 x 282 x 370 mm 1010 x 385 x 312 mm 1010 x 385 x 312 mm 1067 x 312 x 385 mm 1067 x 312 x 385 mm 1205 x 317 x 400 mm
Net / Gross Weight 8 / 10 kg 8 / 11 kg 8 / 11 kg 11 / 14 kg 11 / 14 kg 13 / 17 kg
Refrigeration Pipe Size: Liquid / Gas Φ6.35 / Φ9.52 mm Φ6.35 / Φ9.52 mm Φ6.35 / Φ12.7 mm Φ6.35 / Φ12.7 mm Φ6.35 / Φ12.7 mm Φ9.52 + Φ15.9 mm
Controller Type Wireless Remote Control
Operating Range (Cooling) 16~32 C
Operating Range (Heating) 0~30 C
Wi-Fi Compatibility Standard

Slim Ducted

DINSD26MB DINSD35MB DINSD50MB DINSD70MB
Power Supply 220~240-1-50 V-Ph-Hz
Cooling Rated Capacity 2.6 kW 3.5 kW 5.2 kW 7.1 kW
Cooling Rated Input Power 180 W 185 W 200 W 200 W
Cooling Rated Input Current 1.1 A 1.1 A 1.3 A 1.3 A
Heating Rated Capacity 2.9 kW 3.8 kW 5.5 kW 7.3 kW
Heating Rated Input Power 180 W 185 W 200 W 200 W
Heating Rated Input Current 1.1 A 1.1 A 1.3 A 1.3 A
Airflow (Hi / Med / Lo) 500/340/230 L/s 500/340/230 L/s 600/480/300 L/s 880/650/350 L/s
Maximum External Static Pressure (Hi) 60 Pa 60 Pa 100 Pa 160 Pa
Sound Pressure (Hi / Med / Lo) @1.0m 40/34/27 dB(A) 40/34/27 dB(A) 40/34/27 dB(A) 41/38/33 dB(A)
Dimensions (Net W x D x H) 700 x 506 x 200 mm 700 x 506 x 200 mm 880 x 674 x 210 mm 1100 x 774 x 249 mm
860 x 540 x 285 mm 860 x 540 x 285 mm 1070 x 725 x 280 mm 1305 x 805 x 315 mm
Net / Gross Weight 18 / 22 kg 18 / 22 kg 24 / 29 kg 32 / 39 kg
Supply Air Duct Connection (W x H) 537 x 152 mm 537 x 152 mm 706 x 136 mm 926 x 175 mm
Return Air Duct Connection (W x H) 599 x 186 mm 599 x 186 mm 782 x 190 mm 1001 x 228 mm
Refrigeration Pipe Size: Liquid / Gas Φ6.35 / Φ9.52 mm Φ6.35 / Φ9.52 mm Φ6.35 / Φ9.52 mm Φ9.52 / Φ15.9 mm
Condensate Drain Pump Connection OD25mm
Controller Type Wired Controller - 12m Cable
Operating Range (Cooling) 17~32 C
Operating Range (Heating) 0~30 C
Wi-Fi Compatibility Optional

Compact Cassette

CIN20RMB CIN26RMB CIN35RMB CIN50RMB
Fascia Panel Model No. CINFASM
Power Supply 220~240-1-50 V-Ph-Hz
Cooling Rated Capacity 2.1 kW 2.6 kW 3.5 kW 5.2 kW
Cooling Rated Input Power 40 W 40 W 40 W 102 W
Cooling Rated Input Current 0.18 A 0.18 A 0.18 A 0.44 A
Heating Rated Capacity 2.3 kW 2.9 kW 4.1 kW 5.4 kW
Heating Rated Input Power 40 W 40 W 40 W 102 W
Heating Rated Input Current 0.18 A 0.18 A 0.18 A 0.44 A
Airflow (Hi / Med / Lo) 580/500/450 L/s 580/500/450 L/s 569/485/389 L/s 680/584/479 L/s
Sound Pressure (Hi / Med / Lo) @1.0m 38/33/29 dB(A) 38/33/29 dB(A) 41/37/34 dB(A) 44/42/41 dB(A)
Dimensions (Net - Body W x D x H) 570 x 570 x 260 mm
Gross - Body (W x D x H) 662 x 662 x 317 mm
Net - Fascia (W x D x H) 650 x 650 x 60 mm
Gross - Fascia (W x D x H) 700 x 700 x 110 mm
Net / Gross Weight - Body 14 / 17 kg 14 / 17 kg 16 / 20 kg 16 / 21 kg
Net / Gross Weight - Fascia 2 / 4 kg 2 / 4 kg 2 / 4 kg 2 / 4 kg
Refrigeration Pipe Size: Liquid / Gas Φ6.35 / Φ9.52 mm Φ6.35 / Φ9.52 mm Φ6.35 / Φ9.52 mm Φ6.35 / Φ12.7 mm
Condensate Drain Pump Connection OD25mm
Controller Type Wireless Remote Control
Operating Range (Cooling) 17~32 C
Operating Range (Heating) 0~30 C
Wi-Fi Compatibility Optional

Specifications

Number of units that can be used together Connected units: 1-5 units
Compressor stop/start frequency Stop time: 3 min or more
Power source voltage Voltage fluctuation: within ±10% of rated voltage
Voltage drop during start: within ±15% of rated voltage
Interval unbalance: within ±3% of rated voltage
Piping Lengths (Unit: m) 3 Head | 4 Head | 5 Head
Max. length for all rooms 60/197 | 80/262 | 80/262
Max. length for one indoor unit 30/98 | 35/115 | 35/115
Max. height different between indoor and outdoor unit 15/49 | 15/49 | 15/49
Max. height different between indoor units 10/33 | 10/33 | 10/33

Note: For units with quick connectors, no more than two pipes can be connected, and the maximum length for each pipe is 7.5 meters.

When installing multiple indoor units with a single outdoor unit, ensure the refrigerant pipe length and drop height between indoor and outdoor units meet the requirements illustrated in the diagram. The diagram shows an outdoor unit connected to multiple indoor units, with dimensions for height difference (15m max) and pipe lengths (10m, 15m).

Accessories

Use all provided installation parts and accessories. Improper installation can lead to water leakage, electrical shock, fire, or equipment failure. Items not included must be purchased separately.

Included Accessories

Name of Accessories Qty (pc) Shape Description Name of Accessories Qty (pc) Shape Description
Manual 2-4 Booklet Drain joint (some models) 1 Pipe fitting
Installation plate (some models) 1 Mounting plate Seal ring (some models) 1 Rubber seal
Plastic expansion sheath (some models) 5-8 (depending on models) Protective sheath for pipes Magnetic ring (some models) Varies by model Ring for cable management
Self-Tapping Screw A (some models) 5-8 (depending on models) Fasteners Cord protection rubber ring (supplied with accessories) 1 Rubber ring for cord securing
Transfer connector (packed with indoor or outdoor unit, depending on models) Optional part (one piece/one indoor unit) Adapter for pipe connection

Note on Pipe Size: Pipe size may vary. A transfer connector may be needed for different pipe sizes.

Optional Accessories

Two types of remote controls are available: wired and wireless. Select based on customer preference and requirements. Refer to catalogues and technical literature for guidance.

Connecting Pipe Assembly

Side Size Quantity (PC)
Liquid side Φ6.35 (1/4in) Parts must be purchased separately. Consult dealer for proper pipe size.
Φ9.52 (3/8in)
Gas side Φ9.52 (3/8in)
Φ12.7 (1/2in)
Φ16 (5/8in)

Installation Instructions

Installation Summary

Installation Order:

  1. Install the outdoor unit.
  2. Connect the refrigerant pipes.
  3. Connect the wires.
  4. Evacuate the refrigeration system.
  5. Perform a test run.

Installation Diagram

The diagram illustrates a typical multi-split system installation. It shows an outdoor unit connected to multiple indoor units (3, 4, or 5 head configurations indicated by lines). Key clearances are shown for indoor units (e.g., >12cm from walls, >30cm for air out, >200cm for air out, >60cm clearance).

Safety Precautions:

Note: Installation must comply with local and national standards. Installation may vary by region.

Outdoor Unit Installation

Install the unit following local codes and regulations, which may differ by region.

Installation Instructions – Outdoor unit

Step 1: Select Installation Location

Choose an appropriate location based on the following standards:

Locations to Avoid (DO NOT install):

Special Considerations for Extreme Weather

Step 2: Install Drain Joint (Heat pump unit only)

Install the drain joint at the bottom of the unit before anchoring.

In Cold Climates: Ensure the drain hose is vertical for swift drainage. Slow drainage can cause freezing and flooding.

Step 3: Anchor Outdoor Unit

Anchor the unit to the ground or a wall-mounted bracket using M10 bolts. Prepare the installation base according to the unit's dimensions and mounting feet distances shown in the "Unit Mounting Dimensions" table.

The table provides dimensions (W x D x H) and mounting distances (A, B) for different outdoor unit sizes (7kW, 9/11kW).

Refrigerant Piping Connection

Notes On Drilling Hole In Wall

Drill a hole in the wall for refrigerant piping and signal cable. Determine hole location based on outdoor unit placement. Use a 65-mm core drill. Install a protective wall cuff to seal the hole edges.

Note: Avoid wires, plumbing, and sensitive components when drilling.

Connecting Pipe Sizes

For a 7.0kW Indoor Unit:

Connective Pipe Size (unit: mm):

Indoor Unit Capacity (kW) Liquid Gas
2.0 / 2.6 / 3.5 6.35 9.53
3.5 / 5.0 / 6.0 6.35 12.70
7.0 9.53 15.88

Connection Instructions - Refrigerant Piping

Note: For quick-connect models, refer to the internal machine manual. Do not let foreign substances or gases enter the unit.

Cautions:

Step 1: Cut Pipes

DO NOT DEFORM PIPE WHILE CUTTING: Be careful not to damage or deform the pipe, as this reduces heating efficiency.

Step 2: Remove Burrs

Remove all burrs from the cut section using a reamer or deburring tool. Hold the pipe downward to prevent burrs from falling in.

Step 3: Flare Pipe Ends

Proper flaring is essential for an airtight seal.

Piping Extension Beyond Flare Form Table: Lists pipe gauge, tightening torque, flare dimension (min/max), and flare shape for various pipe sizes.

Step 4: Connect Pipes

Caution: Wrap insulation around piping to prevent burns/frostbite. Ensure proper connection; over-tightening can damage the flare, under-tightening can cause leaks.

Note on Minimum Bend Radius: Bend tubing carefully, not more than 90° or more than 3 times. Minimum bend radius is 10cm (3.9").

Caution: Check for refrigerant leaks after installation. If a leak is found, ventilate the area immediately and evacuate the system.

Wiring

Before Performing Any Electrical Work, Read These Regulations

Warning

BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.

Note on Air Switch

Diagram shows basic wiring connections for outdoor and indoor units, including optional air switch.

Outdoor Unit Wiring

Diagrams (B & C) illustrate wiring configurations for different setups.

Outdoor Unit Wiring Diagram (3 Head models)

This diagram shows the detailed wiring connections for a 3-head model, including connections to the main board, auxiliary board, compressor, fan motor, sensors, valves, and power supply terminals (L, N, S) for indoor units A, B, and C. It indicates optional components with a specific symbol.

Outdoor Unit Wiring Diagram (4 Head models)

This diagram details the wiring for a 4-head model, showing connections to the IPM board, DR board, main board, compressor, DC fan, sensors, electronic expansion valves, and power supply terminals for indoor units A, B, C, and D. It also notes optional components and magnetic rings for EMC compliance.

Outdoor Unit Wiring Diagram (5 Head models)

This diagram illustrates the wiring for a 5-head model, similar to the 4-head diagram but including connections for indoor units A, B, C, D, and E. It also specifies connections for DC and AC fan motors and notes optional components.

Caution

Note on EMC Regulations: Apply correct magnetic rings as per the wiring diagram to comply with CISPR 14-1:2005/A2:2011. Contact your distributor for information on purchasing magnetic rings.

Air Evacuation

Preparations and Precautions

Air and foreign matter in the refrigerant circuit can cause pressure rises, damaging the unit, reducing efficiency, and causing injury. Use a vacuum pump and manifold gauge to remove non-condensable gas and moisture.

Evacuation should be done upon initial installation and relocation.

Before Performing Evacuation

Evacuation Instructions

Read vacuum pump and manifold gauge manuals before use.

Diagram shows manifold gauge connected to outdoor unit service port (low pressure valve) and vacuum pump.

Note On Adding Refrigerant

Caution: Refrigerant charging must occur after wiring, vacuuming, and leak testing. Do not exceed maximum allowable refrigerant quantity. Use only appropriate refrigerant. Open refrigerant containers slowly and wear protective gear. Do not mix refrigerants. For R32 models, ensure the area is safe from flammable materials.

Additional Refrigerant per Pipe Length:

Connective Pipe Length (m) Air Purging Method Additional Refrigerant (R32)
Less than Standard pipe length x N Vacuum Pump N/A
More than Standard pipe length x N Vacuum Pump Liquid Side: Φ6.35 (1/4") (Total pipe length - pre-charge pipe length x N) x15g/m
Liquid Side: Φ9.52 (3/8") (Total pipe length - pre-charge pipe length x N) x30g/m

Note: Standard pipe length is 10m. Remove additional refrigerant charge according to rated volume (5m piping) for market/government verification tests.

Safety and Leakage Check

Note: Illustrations for leakage check points (A, B, C, D, E) are examples; actual machine layout may differ.

Test Run

Before Test Run

Confirm the following before performing the test run:

Caution

Failure to perform the test run may result in unit damage, property damage, or personal injury.

Test Run Instructions

  1. Open both liquid and gas stop valves.
  2. Turn on the main power switch and allow the unit to warm up.
  3. Set the air conditioner to COOL mode.
  4. For the Indoor Unit:
    • Ensure remote control and buttons work.
    • Ensure louvers move correctly via remote control.
    • Verify room temperature registration is accurate.
    • Check indicators on remote and indoor unit display.
    • Ensure manual buttons on the indoor unit work.
    • Check drainage system for smooth operation.
    • Ensure no vibration or abnormal noise during operation.
  5. For the Outdoor Unit:
    • Check for refrigeration system leaks.
    • Ensure no vibration or abnormal noise.
    • Ensure unit noise, wind, and water do not disturb neighbors or pose a safety hazard.

Note: If malfunctions occur, refer to the Troubleshooting section of the Owner's Manual before contacting customer service.

Automatic Correction Function

Automatic Wiring/Piping Correction Function

Recent models feature automatic correction for wiring/piping errors. Press the "check switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE". The "CE" disappears after 5-10 minutes, indicating the error is corrected and connections are proper.

Diagram shows a PCB with a check switch and LED display, and examples of correct vs. incorrect wiring.

How To Activate This Function

  1. Ensure outside temperature is above 5°C (function does not work below this temperature).
  2. Check that the liquid and gas stop valves are open.
  3. Turn on the breaker and wait at least 2 minutes.
  4. Press the check switch on the outdoor PCB board; the LED display should show "CE".

Contacts

Rinnai Australia Pty Ltd

ABN: 74 005 138 769 | AU45204

Address: 100 Atlantic Drive, Keysborough, Victoria 3173

P.O. Box: 460, Braeside, Victoria 3195

Tel: (03) 92716625 | Fax: (03) 92716622

National Help Line:

Tel: 1300 555 545* | Fax: 1300 555 655

Monday to Friday, 8:00 am to 5:00 pm EST.

*Cost of a local call may be higher from a mobile phone. (National calls from public phones in Australia are free.)

For further information, visit www.rinnai.com.au or email enquiry@rinnai.com.au.

Rinnai offers a Service and Spare Parts network. For service, call the National Help Line. Rinnai recommends annual servicing.

Rinnai reserves the right to change specifications or designs without notice due to continuous improvement.

Document ID: B065468

Models: Multi Split Type Air Conditioner

File Info : application/pdf, 32 Pages, 6.50MB

PDF preview unavailable. Download the PDF instead.

Inverter-Multi-Split-System-Installation-Manual

References

Adobe PDF Library 16.0.7 Adobe InDesign 17.2 (Windows)

Related Documents

Preview Rinnai Multi Split Type Air Conditioner Installation Manual
Comprehensive installation manual for Rinnai Multi Split Type Air Conditioners, covering outdoor and indoor unit installation, refrigerant piping, electrical connections, testing, and commissioning. Includes detailed specifications and safety precautions.
Preview Rinnai Pro Series High Wall Split Heat Pump / Air Conditioner Installation Guide
Comprehensive installation guide for Rinnai Pro Series High Wall Split Heat Pump and Air Conditioner models. Covers safety, positioning, installation steps, refrigerant handling, evacuation, electrical and gas leak checks, test run, and error code summaries.
Preview Rinnai J Series Split Type Air Conditioner Installation Manual
This Rinnai J Series Split Type Wall Mounted Air Conditioner Installation Manual provides essential guidance for installing models HSNRJ25B through HSNRJ80B. It covers critical safety procedures, electrical connections, refrigerant handling (R32), and best practices for optimal performance, ensuring compliance with Australian and New Zealand standards.
Preview Rinnai Air Conditioning: Extended 7-Year Warranty Announcement
Rinnai Australia announces an extended 7-year warranty for its air conditioning products, effective April 1st, 2025. This document details the warranty coverage, benefits for homeowners and installers, and Rinnai's commitment to quality and customer peace of mind.
Preview Rinnai PB Series Split Type Wall Mounted Air Conditioner Installation Manual
Comprehensive installation guide for Rinnai PB Series split type wall-mounted air conditioners, covering indoor and outdoor unit installation, refrigerant piping, air evacuation, electrical connections, and testing. Includes model specifications and safety warnings.
Preview Rinnai CJ Series Split Type Wall Mounted Air Conditioner Installation Manual
Comprehensive installation manual for Rinnai CJ Series Split Type Wall Mounted Air Conditioners, covering safety, regulatory compliance, component identification, location selection, electrical connections, refrigerant piping, testing, and final checks.
Preview Rinnai T Series Split Type Wall Mounted Air Conditioner Installation Manual
Comprehensive installation guide for Rinnai T Series split type wall-mounted air conditioners, covering safety, components, location, electrical connections, refrigerant piping, and final checks. Features R32 refrigerant.
Preview Rinnai CJ1 Series Split Type Wall Mounted Air Conditioner Operation Manual
This comprehensive operation manual provides detailed instructions for the Rinnai CJ1 Series Split Type Wall Mounted Air Conditioner. Learn about its features, modes, controls, safety precautions, installation guidelines, maintenance, and warranty information for optimal performance and user satisfaction.