Midea Mini VRF Atom T Series

Brand: Midea

Product Overview

The Midea Mini VRF Atom T series offers advanced air conditioning solutions for various applications. The series includes outdoor units, as well as models integrated with hydraulic modules and domestic hot water (DHW) tanks.

The visual on the first page depicts a cross-section of a modern multi-story building, showcasing different living environments such as a bedroom, a living room, and a nursery, all benefiting from the climate control provided by the Midea VRF system. An outdoor unit is also visible, representing the external component of the system.

Outdoor Units - Atom T Series

This section details the specifications for the standard Atom T outdoor units.

Model MDV-V80WHN8(At) MDV-V100WHN8(At) MDV-V120WHN8(At) MDV-V140WHN8(At) MDV-V160WHN8(At)
Power Supply (V, Ph, Hz) 230, 1 + N, 50 230, 1 + N, 50 230, 1 + N, 50 230, 1 + N, 50 230, 1 + N, 50
Nominal Cooling Capacity (Btu/h (kW)) 24000 (7.2) 30000 (9.0) 41000 (12.3) 47000 (14.0) 52000 (15.5)
Cooling Power Input (kW) 2.23 2.94 3.84 4.33 5.13
EER 3.23 3.06 3.2 4.33 5.13
Nominal Heating Capacity (Btu/h (kW)) 24000 (7.2) 30000 (9.0) 41000 (12.3) 47000 (14.0) 52000 (15.5)
Heating Power Input (kW) 1.92 2.37 3.28 3.60 4.08
COP 3.75 3.8 3.75 3.89 3.8
SEER/SCOP 5.7 / 4 5.7 / 3.95 7.5 / 4.4 6.9 / 4.6 6.6 / 4.4
Number of Indoor Units 4 6 7 8 9
Indoor Unit Capacity Ratio 50%~130% (50~100%) 50%~130% (50~100%) 50%~130% (50~100%) 50%~130% (50~100%) 50%~130% (50~100%)
Sound Pressure Level (1m)³ (dB(A)) 54 55 57 56 56
Net Dimensions (LxAxP) (mm) 910x712x426 950x840x440 950x840x440 950x840x440 950x840x440
Shipping Dimensions (LxAxP) (mm) 1.045x810x485 1.025x940x510 1.025x940x510 1.025x940x510 1.025x940x510
Net Weight (kg) 49 52.5 62.5 77.5 77.5
Gross Weight (kg) 53 56.5 73 88 88
Factory Refrigerant Charge R32 (kg) 1.4 1.8 2.2 2.4 2.4
Liquid Line (mm (in)) Ø 9.52 (3/8") Ø 9.52 (3/8") Ø 9.52 (3/8") Ø 9.52 (3/8") Ø 9.52 (3/8")
Gas Line (mm (in)) Ø 15.88 (5/8") Ø 15.88 (5/8") Ø 15.88 (5/8") Ø 15.88 (5/8") Ø 15.88 (5/8")
Max Total Pipe Length (m) ≤ 60 (model 80) / ≤ 80 (models 100 and 120) / ≤ 100 (models 140 and 160) ≤ 60 (model 80) / ≤ 80 (models 100 and 120) / ≤ 100 (models 140 and 160) ≤ 60 (model 80) / ≤ 80 (models 100 and 120) / ≤ 100 (models 140 and 160) ≤ 60 (model 80) / ≤ 80 (models 100 and 120) / ≤ 100 (models 140 and 160) ≤ 60 (model 80) / ≤ 80 (models 100 and 120) / ≤ 100 (models 140 and 160)
Max Actual Pipe Length (m) ≤ 35 (models 80, 100 and 120) / ≤ 45 (models 140 and 160) ≤ 35 (models 80, 100 and 120) / ≤ 45 (models 140 and 160) ≤ 35 (models 80, 100 and 120) / ≤ 45 (models 140 and 160) ≤ 35 (models 80, 100 and 120) / ≤ 45 (models 140 and 160) ≤ 35 (models 80, 100 and 120) / ≤ 45 (models 140 and 160)
Max Equivalent Pipe Length (m) ≤ 40 (models 80, 100 and 120) / ≤ 50 (models 140 and 160) ≤ 40 (models 80, 100 and 120) / ≤ 50 (models 140 and 160) ≤ 40 (models 80, 100 and 120) / ≤ 50 (models 140 and 160) ≤ 40 (models 80, 100 and 120) / ≤ 50 (models 140 and 160) ≤ 40 (models 80, 100 and 120) / ≤ 50 (models 140 and 160)
Length from 1st Branch & DHW Module (m) ≤ 20 ≤ 20 ≤ 20 ≤ 20 ≤ 20
Operating Limits - Cooling (°C) -15°C ~ 46°C OAT -15°C ~ 46°C OAT -15°C ~ 46°C OAT -15°C ~ 46°C OAT -15°C ~ 46°C OAT
Operating Limits - Heating (°C) -15°C ~ 55°C OAT -15°C ~ 55°C OAT -15°C ~ 55°C OAT -15°C ~ 55°C OAT -15°C ~ 55°C OAT

Notes:

Certifications & Features: [R32 Refrigerant] [CE Mark] [SG Ready] [Smart Heat Pumps] [Eurovent Certified Performance]

Outdoor Units - Atom T with Hydraulic Module

This section details specifications for Atom T outdoor units paired with hydraulic modules.

Model MDV-V80WHN8(At) MDV-V100WHN8(At) MDV-V120WHN8(At) MDV-V140WHN8(At) MDV-V160WHN8(At)
Hydraulic Module Model SMK-D160N8(At) SMK-D160N8(At) SMK-D160N8(At) SMK-D160N8(At) SMK-D160N8(At)
Power Supply (V, Ph, Hz) 230, 1 + N, 50
Heating Capacity W35 (kW) 24000 (7.2) 30000 (9) 41000 (12.3) 47000 (14.0) 52000 (15.5)
Heating COP W35 3.8 4.2 3.9 4.1 4
Heating Capacity W45 (kW) 23885 (7) 30026 (8.8) 41286 (12.1) 47087 (13.8) 52205 (15.3)
Heating COP W45 2.9 3.2 3.0 3.1 3.0
Heating Capacity W55 (kW) 23202 (6.8) 29003 (8.5) 39239 (11.5) 44357 (13.0) 46063 (13.5)
Heating COP W55 2.25 2.4 2.45 2.15 2.15
Energy Efficiency Class W55 A+ A+ A+ A+ A+
Sound Pressure Level (1m)¹ (dB(A)) 40 43 44 44 44
Net Dimensions (LxAxP) (mm) 420x790x270 420x790x270 420x790x270 420x790x270 420x790x270
Shipping Dimensions (LxAxP) (mm) 525x1.050x360 525x1.050x360 525x1.050x360 525x1.050x360 525x1.050x360
Net Weight (kg) 44 44 44 44 44
Gross Weight (kg) 49 49 49 49 49
Piping Connections
Liquid Line (mm (in)) Ø 25.4 (1")
Water Inlet Pressure (MPa) 0.3
Drain Pipe (mm) Ø 25
Volume (L) 8.0
Water Circuit
Expansion Tank Volume (L) 8.0
Max Water Pressure (MPa) 0.3
Pre-pressure (MPa) 0.1
Manometric Head (m) 9
Water Pump
Min Water Flow Rate (L/min) 10
Internal Water Volume (L) 3.6~8.4
Piping Connections
Liquid Line (mm) Ø 9.52
Gas Line (mm) Ø 15.88
Operating Temperature Limits
Heating (°C) 25 ~ 60
DHW (°C) 25 ~ 60

Certifications & Features: [R32 Refrigerant] [ECE] [CE Mark] [SG Ready] [Eurovent Certified Performance]

Outdoor Units - Atom T with Hydraulic Module and Integrated Tank

This section details specifications for Atom T outdoor units with hydraulic modules and integrated domestic hot water (DHW) tanks.

Model MDV-V80WHN8(At) MDV-V100WHN8(At) MDV-V80WHN8(At) MDV-V100WHN8(At)
Hydraulic Module with Integrated Tank Model SMKT-D100/190CGN8(At) SMKT-D100/190CGN8(At) SMKT-D160/240CGN8(At) SMKT-D160/240CGN8(At)
Power Supply (V, Ph, Hz) 230, 1 + N, 50
Heating Capacity W35 (kW) 24000 (7.2) 30000 (9.0) 24000 (7.2) 30000 (9)
Heating COP W35 3.8 4.2 3.8 4.2
Heating Capacity W45 (kW) 23885 (7.0) 30026 (8.8) 23885 (7) 30026 (8.8)
Heating COP W45 2.9 3.2 2.9 3.2
Heating Capacity W55 (kW) 23202 (6.8) 29003 (8.5) 23202 (6.8) 29003 (8.5)
Heating COP W55 2.25 2.4 2.25 2.4
Energy Efficiency Class W55 A+ A+ A+ A+
Sound Pressure Level (1m)¹ (dB(A)) 40 43 40 43
Net Dimensions (LxAxP) (mm) 600x1.683x600 600x1.683x600 600x1.943x600 600x1.943x600
Shipping Dimensions (LxAxP) (mm) 730x1.920x730 730x1.920x730 730x2.180x730 730x2.180x730
Net Weight (kg) 143 143 160 160
Gross Weight (kg) 164 164 181 181
DHW Tank
Type Stainless Steel
Material SUS 316L
Water Volume (L) 190 190 240 240
Max Water Pressure (bar) 10 10 10 10
Insulation Material Polyurethane Foam
Insulation Thickness (mm) 45
Piping Connections
Piping (mm (in)) Ø 25.4 (1")
Water Inlet Pressure (MPa) 0.3
Drain Pipe (mm) Φ 25
Volume (L) 8.0
Water Circuit
Expansion Tank Volume (L) 8.0
Max Water Pressure (MPa) 0.3
Pre-pressure (MPa) 0.1
Manometric Head (m) 9
Water Pump
Min Water Flow Rate (L/min) 10
Internal Water Volume (L) 3.6~8.4
Piping Connections
Liquid Line (mm) Ø 15.88
Gas Line (mm) Ø 9.52
Operating Temperature Limits
Heating (°C) 25 ~ 60
DHW (°C) 25 ~ 60

Certifications & Features: [R32 Refrigerant] [CE Mark] [SG Ready] [Eurovent Certified Performance]

PDF preview unavailable. Download the PDF instead.

MIDEA@FT Mini VRF AtomT Adobe PDF Library 15.0 Adobe InDesign 15.0 (Macintosh)

Related Documents

Preview Midea Mini VRF Technical Service Manual
This technical service manual provides detailed information on Midea's Mini VRF systems, covering general information, outdoor unit specifications, and installation procedures for models MDV-V105W/DVN1, MDV-V120W/DVN1, MDV-V140W/DVN1, and MDV-V160W/DVN1.
Preview Midea Atom Series VRF Indoor Units Engineering Data
Engineering data for Midea Atom Series Wall-mounted VRF IDU, including specifications, dimensions, installation, piping and wiring diagrams, capacity tables, electrical characteristics, and sound levels for models MDV-D07G/N1-M(At) through MDV-D32G/N1-M(At).
Preview Midea VRF Atom B Outdoor Unit MDV-V60WDHN1(AtB) Specifications and Submittal Data
Detailed specifications and submittal data for the Midea VRF Atom B Outdoor Unit, model MDV-V60WDHN1(AtB). Includes cooling and heating capacity, input power, EER, COP, dimensions, weight, refrigerant type, and operational range.
Preview Midea VRF Atom B Outdoor Unit MDV-V42WDHN1(AtB) - Submittal Data
Technical specifications and dimensional data for the Midea VRF Atom B Outdoor Unit, model MDV-V42WDHN1(AtB). Features, cooling/heating capacity, electrical data, and dimensions.
Preview Midea VRF Atom Indoor Unit MDV-D24DL/VN1-C(At) - Ceiling & Floor Submittal Data
Technical specifications and dimensional data for the Midea VRF Atom Indoor Unit, model MDV-D24DL/VN1-C(At), designed for ceiling and floor installation. Includes capacity, power, airflow, sound levels, and dimensions.
Preview Midea MDV-V230WN1(AU) R410A Mini VRF System Overview
Comprehensive overview of the Midea MDV-V230WN1(AU) R410A Mini VRF system, detailing its features, specifications, and benefits for efficient climate control.
Preview Midea Mini Series VRF Engineering Data
Comprehensive engineering data for the Midea Mini Series VRF, including specifications, dimensions, installation requirements, piping and wiring diagrams, and troubleshooting for models MDV-V230WN1(AU) and MIH200T1HN18(S).
Preview Midea MDV-V235WN1(AU)-A VRF 50Hz Outdoor Unit Engineering Data
This document provides detailed engineering data for the Midea MDV-V235WN1(AU)-A VRF 50Hz outdoor air conditioning unit. It includes specifications, dimensions, installation requirements, piping and wiring diagrams, electrical characteristics, operating limits, sound levels, and standard accessories.