Midea VRF Atom B Outdoor Unit
MDV-V60WDHN1(AtB) – Heat Pump
1-phase, 220-240V, 50/60Hz
Submittal Data
Job name:
Tag:
Location:
Date:
Specifications
Model | MDV-V60WDHN1(AtB) | |
---|---|---|
Cooling1 | Capacity (kBtu/h) | 59 |
Capacity (kW) | 17.5 | |
Input (kW) | 6.12 | |
EER (kW/kW) | 2.86 | |
Heating2 | Capacity (kBtu/h) | 66 |
Capacity (kW) | 19.5 | |
Input (kW) | 5.57 | |
COP (kW/kW) | 3.50 | |
Total capacity | 45~130% of outdoor unit capacity | |
Connectable indoor unit | 1~9 | |
Compressor | Type | DC Inverter |
Quantity | 1 | |
Fan motor | Type | DC motor |
Quantity | 1 | |
Outdoor air flow (m³/h) | 5300 | |
Sound pressure level3 (dB(A)) | 57 | |
Net/Packed dimensions (W×H×D) (mm) | 1040×865×523 | |
Packed dimensions (W×H×D) (mm) | 1120×980×560 | |
Net/Gross weight (kg) | 91/99 | |
Refrigerant type/factory charge (kg) | R410A/4.6 | |
Liquid/Gas pipe (mm) | Φ9.53/Φ19.1 | |
Minimum Circuit Amps (MCA) (A) | 40 | |
Recommended Fuse Size (MFA) (A) | 40 |
Notes:
- Indoor temperature 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent refrigerant piping length 7.5m with zero level difference.
- Indoor temperature 20°CDB; outdoor temperature 7°CDB, 6°CWB; equivalent refrigerant piping length 7.5m with zero level difference.
- Sound pressure level is measured 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
Product specifications change from time to time as product improvements and developments are released and may vary from those in this document.
Dimensional Drawing
Unit (mm)
A diagram shows the dimensions of the outdoor unit. The front view shows a width of 1040mm and a height of 865mm. The top view shows a width of 1053mm and a depth of 523mm. Another view shows a depth of 410mm and a height of 452mm. Other dimensions indicated are 191mm and 656mm for the top view, and 463mm for the side view.