Sauermann Condensate Pumps

Managing condensate for Air Conditioning systems.

Visit us at: www.sauermann.co.uk

Pump Selection Chart

The following chart provides an overview of pump compatibility with different equipment types and installation locations.

Pump Model Wall mounted Cassette Multi cassette Conditioning cabinet Floor standing Ducted unit Suspended ceiling unit Inside the unit Inside ducting Wall mounted Floor mounted False ceiling
OMEGA PACK
Si-20
DELTA PACK
Si-10 UNIVERS'L
Si-30 / Si-33
Si-60
Si-82
Si-83
SI 1805
SI 1830
SI 2052
PE5000
PE5100
PE5200

Actual flow rates: The graph illustrates the relationship between discharge head (in meters) and flow rate (in liters per hour) for various pump models, including Si-33/Si-63, Si-30/Si-60/Si-10 UNIVERS'L, and Si-20.

OMEGA PACK

The under the unit pack for mini-split air conditioning.

Ref: RAL 9003: OP20CE02UN23

Kit contents: Si-20 piston pump with detection unit (0.63 m cable), 2 anti-vibration rubber dampers, clear PVC tubing int. Ø 6 mm fitted with a drain safe device - Power cable 1.5m (2 power wires, 2 safety wires) - Shell (2-part: backplate & cover) - Screws & plugs for affixing backplate 90° rubber elbow Ø int.15 mm x L 152 mm - Vent tube - 3 Double Wire Clamps - 3 Tie Wraps.

Si-20 Piston Pump

For wall mounted and floor standing units.

Ref: SI20CE01UN23

Technical specifications

FeatureSi-20
Maximum flow-rate20 l/h
Maximum discharge head10 m (flow rate= 4 l/h)
Pump sound level @ 1 m22 dBA
Detection levels (mm)ON: 16, OFF: 11, Safety: 19
Mains supply230 V ~ 50 Hz 14 W
Thermal protection115°C (auto-reset)
ProtectionIP20

*To EN ISO 3744. LNE measurement, on pump running with water, out of application.

DELTA PACK Piston pump and trunking system

For wall-mounted air-conditioning units.

Ref: 80x60 mm cream RAL 9001: DP10CE06UN23; 80x60 mm white RAL 9003: DP10CE05UN23

Kit contents: Si-10 UNIVERS'L piston pump - Clear PVC tube int. Ø 6mm – L: 1 m, foam-insulated over 800mm fitted with a "Drain Safe Device" pre-mounted - 1.5m lockable plug-in power cable: 2 power wires, 2 safety contact wires.-2-part elbow (base and cover) - Ceiling duct (covers hole in false ceiling) -Rubber Elbow/Split gasket.-650mm flexible hose int. Ø 15mm (connects to split) -Vent pipe -Sixs crews and plugs for fixing duct and elbow -4 doublewire clamps Ø 16mm, 1 doublewire clamps Ø 6mm-750mm - Duct 80x60 mm

Si-10 UNIVERS'L Replacement pump for trunking corner pieces

For wall-mounted air-conditioning units.

Ref: SI10CE03UN23

Technical specifications

FeatureSi- 10 UNIVERS'L
Maximum flow-rate20 l/h
Maximum discharge head10 m (flow rate= 4 l/h)
Pump sound level @ 1 m22 dBA
Detection levels (mm)ON: 16, OFF: 11, Safety: 19
Mains supply230 V ~ 50 Hz 14 W
Thermal protection115°C (auto-reset)
ProtectionIPX4

*at 1m according to EN ISO3744

Si-30 / Si-33 Mini pumps with float detection

For air conditioning systems.

Ref: SI30: SI30CE01UN23 / Si-33: SI33CE01UN23

Kit contents: Pump - Transparent PVC tube int. Ø 6 mm L 1 m, fitted with "Drain-Safe Device" connector - Anti-vibration mounting bracket - Lockable, plug-in 1.5 m cable with NC safety contact wire - 6 cable ties - Detection block (SI 2958) with installation kit: 90° connector int. Ø 15 mm x L 60 mm, vent pipe, mounting rail, adhesive.

Technical specifications

FeatureSi-30Si-33
Maximum flow-rate20 l/h30 l/h
Maximum suction height3 m3.3 m
Maximum discharge head10 m (flow rate = 4 l/h)> 13 m (flow rate = 8 l/h)
Pump sound level @ 1 m20 dBA34 dBA
Detection levels (mm)ON: 16, OFF: 11, Safety: 19
Mains supply230 V ~ 50 Hz 14W230 V ~ 50 Hz 21 W
ProtectionIP20IP20

*To EN ISO 3744. LNE measurement, on pump running with water, out of application.

Si-60 Piston pump with 0.37 L tank

For ducted air conditioning systems.

Ref: SI60CE01UN23

Kit contents: Pump - Lockable, plug-in 1.5 m cable with NC safety contact wire - Installation kit: adapter int. Ø 15-20-24-32-40 mm, rubber 90° connector int. Ø 15 mm x L 60 mm, plastic 90° connector for 6 mm int. Ø flexible tube, 1 off 2.5 x 100 mm cable tie.

Technical specifications

FeatureSi-60
Maximum flow-rate20 l/h
Maximum discharge head10 m (flow rate = 4 l/h)
Pump sound level @ 1 m< 38 dBA
Detection levels (mm)ON: 28, OFF: 24, Safety: 35
Mains supply230 V ~ 50 Hz 14 W
ProtectionIPX4

* To EN ISO 3744. LNE measurement, on pump running with water, out of application.

PE 5000 / PE 5100 / PE 5200 Peristaltic pumps

For air conditioning applications up to 8 kW.

Ref: PE5000: PE5000SIUN23; PE5100: PE5100SIUN23; PE5200: PE5200SIUN23

Kit contents: Pump - Cable: 1.7 m, including 2 wires for power supply (P &N), 1 wire for compressor signal - Easy «1 screw» sliding plastic bracket - Ø 15 mm to Ø 6 mm adaptor + pale yellow rubber Ø 15 x 35mm (PE5003)
Additional kit for PE 5100 : 2 thermal probes with 3.5m cable: Red cap for ambient air. Blue cap for fresh air.
Additional kit for PE 5200 : detection unit (SI2958, 1.5m cable) - Detection unit installation kit : Pale yellow rubber (Ø 15 x 35mm). Vent tube Øint 4 x L 75 mm. Mounting rail. Adhesive.

Technical specifications

FeaturePE 5000 / PE 5100 / PE 5200
Maximum flow-rate6 l/h
Maximum discharge head2 m
Pump sound level @ 1 m≤ 30 dBA
Detection levels (mm)ON: 16, OFF: 11, Safety: 19
Mains supply230 V~ 50/60 Hz -75 W
ProtectionIP65

* To EN ISO 3744. LNE measurement, on pump running with water, out of application.

Si-82 / Si-83 Centrifugal pumps with tank

For commercial (Si-82) or domestic (Si-83) A/C units.

Ref: SI82CE04UN23; SI83CE01UN23; SI83CE04UN23

Application:
Commercial / Domestic use: The Si-82 is ideal for commercial use. The Si-83 meets domestic needs.

Kit contents:
Si-82: Pump - Integrated barb end check valve (external diameter 10mm or 3/8'') - Plug-in power & safety cords 1,5 m - Straight connector (external diameter 10mm or 3/8» / 6mm or 1/4'') 2 screws + 2 plugs
Si-83: One-piece centrifugal pump with 2 l tank - Integrated barb end check valve, Ø ext. 10 mm - 1.8 m power cord, plug - 2 screws, 2 plugs Straight connector with tube and ziptie for Ø 6 mm int. tubes

Technical specifications

FeatureSi-82Si-83
Maximum flow-rate500 l/h5.4 m
Maximum discharge head5 m (flow rate 50l/h)45 dBA
Pump sound level @ 1 m< 45 dBAON: 40, OFF: 21, AL: 40
Detection levels (mm)ON: 53, OFF: 42, Safety: 64230 V ~ 50 Hz - 115 W - 1.4 A
Mains supply230 V ~ 50/60 Hz - 70 WIP44
ProtectionIP20

* To EN ISO 3744. LNE measurement, on pump running with water, out of application.

SI 1805 / SI 1830 Centrifugal pumps with 0.5 l tank

For cassette and fan coil air-conditioning systems.

Ref: SI 1805: SI1805SIUN23; SI 1830: SI1830SCUN23

Kit contents:
SI 1805: Pump - 2 screws - 2 plugs – Power cable: 2 m, European IEC plug; safety contact cable: 1 m, 2 wires (NC contact).
SI 1830: Pump with 0.5 l tank – Power cable: 1.5 m, European IEC plug; safety contact cable: 1 m, 2 wires (NC contact) - Installation kit: 2 screws + 2 plugs, 5 m of transparent PVC hose 10 mm int. Ø, flexible adapter 15-24-32-40 mm Ø.

Dimensions:
SI 1805: L 195 x W 130 x H 132 mm
SI 1830: L 190 x W 80 x H 100 mm

Technical specifications

FeatureSI 1805SI 1830
Maximum flow-rate500 l/h400 l/h
Maximum discharge head5,4m3,7 m
Pump sound level @ 1 m< 47 dBA< 43 dBA
Detection levels (mm)ON : 27, OFF: 21, Safety : 32ON : 32, OFF : 25, Safety: 39
Mains supply230 V~ 50/60 Hz -90 W230 V~ 50/60 Hz -75 W
ProtectionIP20IPX4

* To EN ISO 3744. LNE measurement, on pump running with water, out of application.

SI 2052 Centrifugal lift pump

For cassette air conditioning systems.

Ref: SI2052SIUN23

Kit contents: Centrifugal pump – 250 mm overmoulded cable – 850 mm cable with hard-wired connector - Detector (DET01550, 900 mm cable) + stainless-steel fixing screw.

Technical specifications

FeatureSI 2052
Maximum flow-rate100 l/h at 200mm
Maximum discharge head0.9 m (24l/h)
Pump sound level @ 1 m≤ 30 dBA
Detection levels (mm)Safety: 18
Mains supply230 V ~ 50/60 Hz - 14 W

* To EN ISO 3744. LNE measurement, on pump running with water, out of application.

ACCESSORIES

Pump Discharge Hoses

Connectors

Spare Parts

For further information, visit www.sauermanngroup.com.

PDF preview unavailable. Download the PDF instead.

maquette-sauermann EN 12P 2025 Adobe PDF Library 17.0 Adobe InDesign 20.1 (Windows)

Related Documents

Preview Sauermann: Professionelle Lösungen für Kondensatmanagement und Raumluftqualitätsmessung
Entdecken Sie die innovativen Messinstrumente und Kondensatpumpen von Sauermann für HLK- und Raumluftqualitätsanwendungen. Präzise, zuverlässig und benutzerfreundlich.
Preview Sauermann: Professionelle Lösungen für Kondensatmanagement und Raumluftqualitätsmessung
Entdecken Sie die professionellen Lösungen von Sauermann für Kondensatmanagement und Raumluftqualitätsmessung. Erfahren Sie mehr über die breite Palette an Messgeräten und Pumpen, die für HLK-Techniker und verschiedene Industriezweige entwickelt wurden.
Preview Sauermann: Professional HVACR Measurement Instruments & Condensate Pumps
Explore Sauermann's comprehensive range of professional solutions for condensate management and indoor air quality measurement, including advanced HVACR instruments, combustion gas analyzers, and reliable condensate pumps.
Preview Sauermann Professional Solutions for Condensate Management and Indoor Air Quality Measurement
Discover Sauermann's comprehensive range of professional solutions for condensate management and indoor air quality (IAQ) measurement. Explore their advanced HVACR instruments, combustion analyzers, and digital manifolds designed for precision, reliability, and ease of use.
Preview Sauermann Professional Solutions for Condensate Management and Indoor Air Quality Measurement
Explore Sauermann's comprehensive range of professional solutions for condensate management and indoor air quality measurement. Discover their high-accuracy instruments, reliable pumps, and advanced technologies designed for HVACR professionals and various industrial applications.
Preview Sauermann HVACR Measuring Instruments: Easy-to-Use Solutions
Explore Sauermann's range of easy-to-use HVACR measuring instruments, including thermometers, anemometers, manometers, and leak detectors. Learn about their applications, technical specifications, and mobile app integration for efficient condensate management and indoor air quality monitoring.
Preview Sauermann Si-RM350 / Si-RM450 Manifold Probes Quick Start Guide
Quick start guide for connecting and using Sauermann Si-RT2, Si-RT5, Si-RT7, Si-TH4, Si-RP4, and Si-RV4 probes with Si-RM350/Si-RM450 manifolds and smartphones.
Preview Sauermann Si-82, SI 1800, SI-1801 Condensate Lift Pump Manual
Technical specifications, installation, operation, and troubleshooting guide for the Sauermann Si-82, SI 1800, and SI-1801 condensate lift pumps.