VLT® Midi Drive FC 280

Operating Guide

vlt-drives.danfoss.com

1 Introduction

This operating guide provides information for safe installation and commissioning of the VLT® Midi Drive FC 280 frequency converter.

The operating guide is intended for use by qualified personnel. To use the frequency converter safely and professionally, read and follow the operating guide. Pay particular attention to the safety instructions and general warnings. Always keep this operating guide with the frequency converter.

VLT® is a registered trademark.

1.1 Purpose of the Manual

Provides information for safe installation and commissioning of the VLT® Midi Drive FC 280 frequency converter.

1.2 Additional Resources

Resources available to understand advanced frequency converter functions, programming, and maintenance:

Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/technical-documentation/ for listings.

1.3 Document and Software Version

This manual is regularly reviewed and updated. All suggestions for improvement are welcome. The document version and corresponding software version are shown in Table 1.1.

Table 1.1 Document and Software Version
Edition Remarks Software version
MG07A302 More information for single-phase and 3-phase 200–240 V frequency converters introduced. 1.2

1.4 Product Overview

1.4.1 Intended Use

The frequency converter is an electronic motor controller intended for:

The frequency converter can also be used for motor overload protection. It is allowed for use in residential, industrial, and commercial environments in accordance with local laws and standards. In residential environments, it may cause radio interference requiring mitigation measures.

Foreseeable misuse: Do not use the frequency converter in applications non-compliant with specified operating conditions and environments. Ensure compliance with chapter 9 Specifications.

1.4.2 Block Diagram of the Frequency Converter

Illustration 1.1 shows a block diagram of the internal components:

1.4.3 Enclosure Sizes and Power Ratings

Refer to chapter 9.9 Enclosure Sizes, Power Ratings, and Dimensions.

1.4.4 Safe Torque Off (STO)

The VLT® Midi Drive FC 280 supports Safe Torque Off (STO). See chapter 6 Safe Torque Off (STO) for details.

1.5 Approvals and Certifications

Compliance with standards like IEC/EN 61508 SIL2, IEC/EN 61800-5-2 SIL2, IEC/EN 62061 SILCL of SIL2, IEC/EN 61326-3-1, and EN ISO 13849-1 Category 3 PL d for STO function.

For compliance with the European Agreement concerning International Carriage of Dangerous Goods by Inland Waterways (ADN), refer to chapter ADN-compliant Installation in the VLT® Midi Drive FC 280 Design Guide.

The frequency converter complies with UL 508C thermal memory retention requirements.

1.6 Disposal

Do not dispose of equipment containing electrical components with domestic waste. Collect it separately in accordance with local and valid legislation.

2 Safety

2.1 Safety Symbols

2.2 Qualified Personnel

Correct and reliable operation requires qualified personnel for transport, storage, installation, operation, and maintenance. Qualified personnel are trained staff authorized to install, commission, and maintain equipment in accordance with pertinent laws and regulations, and are familiar with the instructions and safety measures in this guide.

2.3 Safety Precautions

Table 2.1 Discharge Time
Voltage [V] Power range [kW (hp)] Minimum waiting time (minutes)
200–240 0.37–3.7 (0.5–5) 4
380–480 0.37–7.5 (0.5–10) 4
11–22 (15–30) 15

3 Mechanical Installation

3.1 Unpacking

3.1.1 Items Supplied

Verify that supplied items and nameplate information correspond to the order confirmation. Check packaging and unit visually for damage. File claims with the carrier and retain damaged parts.

Product Nameplate (Example): Illustration 3.1 shows a typical product nameplate with details like product logo, name, ordering number, type code, power rating, input/output voltage/current/frequency, IP rating, country of origin, serial number, EAC logo, CE mark, TÜV logo, UL logo, and disposal information.

NOTICE: Do not remove the nameplate (loss of warranty).

3.1.2 Storage

Ensure storage requirements are fulfilled. Refer to chapter 9.4 Ambient Conditions.

3.2 Installation Environment

NOTICE: In environments with airborne liquids, particles, or corrosive gases, ensure the IP/Type rating matches the environment. Failure to meet ambient condition requirements can reduce lifetime. Ensure air humidity, temperature, and altitude requirements are met.

Vibration and shock: The frequency converter complies with requirements for units mounted on walls and floors, and in panels bolted to walls or floors.

For detailed ambient conditions specifications, refer to chapter 9.4 Ambient Conditions.

3.3 Mounting

NOTICE: Improper mounting can result in overheating and reduced performance.

3.3.1 Side-by-side Installation

All VLT® Midi Drive FC 280 units can be installed side by side. Units do not require extra side ventilation.

NOTICE: If an IP21 conversion kit is used, mounting units side by side could lead to overheating. Avoid this if the IP21 kit is used.

3.3.2 Bus Decoupling Kit

This kit ensures mechanical fixation and electrical shielding for control cassette variants (PROFIBUS, PROFINET, CANopen, Ethernet). It includes horizontal and optional vertical decoupling plates.

Mounting the bus decoupling kit:

  1. Place the horizontal decoupling plate on the control cassette and fasten with 2 screws (torque 0.7–1.0 Nm).
  2. Optional: Mount the vertical decoupling plate by removing springs/clamps from the horizontal plate, mounting them on the vertical plate, and fastening with 2 screws (torque 0.7–1.0 Nm).
  3. Push cable connectors into sockets.
  4. Place PROFIBUS/CANopen/PROFINET/Ethernet cables between spring-loaded metal clamps for fixation and shielding.

NOTICE: If the IP21 top cover is used, do not mount the vertical decoupling plate as its height affects proper installation.

4 Electrical Installation

4.1 Safety Instructions

See chapter 2 Safety for general instructions.

4.2 EMC-compliant Installation

Follow instructions in chapters 4.3 Grounding, 4.4 Wiring Schematic, 4.6 Motor Connection, and 4.8 Control Wiring.

4.3 Grounding

WARNING: LEAKAGE CURRENT HAZARD Leakage currents exceed 3.5 mA. Failure to ground properly can result in death or serious injury. Ensure correct grounding by a certified electrical installer.

NOTICE: POTENTIAL EQUALIZATION Risk of burst transient due to ground potential differences. Install equalizing cables between system components. Recommended cross-section: 16 mm² (6 AWG).

4.4 Wiring Schematic

Illustration 4.2 shows the basic wiring schematic for power input (terminals 91-99), motor connection (terminals 96-98), DC bus connection (terminals 88, 89), brake resistor connection (terminal 81), and control wiring (terminals 12, 13, 18, 19, 27, 29, 32, 33, 37, 38, 42, 50, 53, 54, 55, 61, 68, 69). Terminal functions and default settings are in Tables 4.1 and 4.2.

Illustration 4.3 shows a typical electrical connection layout, highlighting separation of motor, mains, and control cables, and the grounding rail.

4.5 Access

Remove the cover plate with a screwdriver to access terminals. Tighten terminals according to chapter 9.7.

4.6 Motor Connection

WARNING: INDUCED VOLTAGE Run output motor cables separately and use shielded cables. Comply with codes for cable sizes. Follow motor manufacturer requirements. Do not wire starting or pole-changing devices between the converter and motor.

Procedure:

  1. Strip outer cable insulation.
  2. Position cable under clamp for mechanical fixation and electrical contact of the shield.
  3. Connect ground cable to the nearest grounding terminal (chapter 4.3).
  4. Connect 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W) (Illustration 4.5).

Illustrations 4.6, 4.7, and 4.8 show mains, motor, and grounding connections for single-phase and 3-phase units.

4.7 AC Mains Connection

Size wiring based on input current (chapter 9.1). Comply with codes.

Procedure:

  1. Connect AC input power cables to terminals N/L (single-phase) or L1/L2/L3 (3-phase) (Illustrations 4.6, 4.7).
  2. Connect input power to mains input terminals or disconnect switch.
  3. Ground cable per chapter 4.3.
  4. For isolated mains sources (IT mains, floating delta) or TT/TN-S mains with grounded leg, remove the RFI filter screw to prevent damage and reduce ground capacity currents per IEC 61800-3.

4.8 Control Wiring

4.8.1 Control Terminal Types

Illustration 4.9 shows removable connectors. Terminal functions and default settings are in Tables 4.1 and 4.2. See chapter 9.6 for terminal ratings.

4.8.2 Wiring to Control Terminals

Control terminal connectors are unplugged for ease of installation. Keep control cables short and separate from high-power cables. Wire terminals by inserting sleeved cables and fastening screws. Ensure firm contact.

4.8.3 Enabling Motor Operation (Terminal 27)

A jumper wire is required between terminal 12 (or 13) and terminal 27 for operation with factory default settings. Terminal 27 is a 24 V DC external interlock command input. If no interlock device is used, wire a jumper from terminal 12 (recommended) or 13 to terminal 27.

NOTICE: UNABLE TO START The frequency converter cannot operate without a signal on terminal 27 unless reprogrammed.

4.8.4 Mechanical Brake Control

In hoisting/lowering applications, control an electro-mechanical brake using a relay or digital output (terminal 27). Keep the output closed (voltage-free) while the converter cannot hold the motor at standstill. Select [32] Mechanical brake control in parameter group 5-4*. The brake releases when motor current exceeds parameter 2-20 Release Brake Current and engages when output frequency is below parameter 2-22 Activate Brake Speed [Hz] during a stop command. The brake closes immediately in alarm or overvoltage situations. The converter is not a safety device; system designer must integrate safety devices per regulations.

Illustration 4.11 shows connecting the mechanical brake.

4.8.5 USB Data Communication

NOTICE: USB bus has no address-setting capacity. Connecting multiple converters via USB can cause issues. It is advised to connect only 1 converter via USB to a PC.

4.8.6 RS485 Serial Communication

Connect RS485 serial communication wiring to terminals (+)68 and (-)69. Shielded cable is recommended. See chapter 4.3 for grounding. Set protocol type (8-30), address (8-31), and baud rate (8-32) in parameter group 8-3*.

4.9 Installation Checklist

Inspect the installation as detailed in Table 4.3:

CAUTION: POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE Before applying power, ensure all safety covers are in place and securely fastened.

5 Commissioning

5.1 Safety Instructions

See chapter 2 Safety. WARNING: HIGH VOLTAGE Qualified personnel only. Before applying power:

  1. Close cover properly.
  2. Tighten cable glands.
  3. Ensure input power is off and locked out.
  4. Verify no voltage on input/output terminals.
  5. Confirm motor continuity.
  6. Check proper grounding.
  7. Inspect for loose connections.
  8. Confirm supply voltage matches unit and motor voltage.

5.2 Applying Power

  1. Confirm input voltage balance is within 3%.
  2. Ensure optional equipment wiring is correct.
  3. Ensure operator devices are OFF. Close panel doors and fasten covers.
  4. Apply power. Do not start yet. Turn disconnect switch ON if equipped.

5.3 Local Control Panel Operation

The converter supports Numeric Local Control Panel (NLCP), Graphic Local Control Panel (GLCP), and blind cover. Programming is also possible via MCT 10 Set-up Software (downloadable from Danfoss website).

5.3.1 Numeric Local Control Panel (NLCP)

The NLCP has 4 sections:

Illustration 5.1 shows the NLCP view. Illustration 5.2 details display information. Table 5.2 lists indicator lights, Table 5.3 navigation keys, and Table 5.4 operation keys.

Right-key Function: Pressing [] allows editing individual digits of a parameter value.

NOTICE: LCP shows INITIALISING during start-up. Converter is ready when this message disappears.

5.3.3 Quick Menu on NLCP

Provides access to frequently used parameters. Navigate via [Menu] key, select QM1 or QM2, browse parameters with arrows, press [OK] to select, change values, press [OK] to accept. Exit via [Back] or [Menu].

Illustration 5.4 shows the Quick Menu structure.

5.3.4 Main Menu on NLCP

Provides access to all parameters. Navigate through parameter groups and parameters using arrow keys and [OK]. Change values using arrows, press [OK] to accept. Exit via [Back] or [Menu]. Illustrations 5.5, 5.6, 5.7 and Tables 5.5, 5.6, 5.7 describe parameter value changes for continuous, enumerated, and array parameters.

5.3.5 GLCP Layout

The GLCP has 4 functional groups:

Illustration 5.8 shows the GLCP layout.

NOTICE: Adjust display contrast using [Status] and arrow keys.

5.3.6 Parameter Settings

Correct programming requires setting related parameters. Details are in chapter 10.2 Parameter Menu Structure. Data is stored internally; upload to LCP memory for backup.

5.3.7 Changing Parameter Settings with GLCP

Access and change settings via Quick Menu or Main Menu. Navigate using arrow keys and [OK]. Change values with arrows, shift digits with [], press [OK] to accept. Exit via [Back] or [Main Menu]. Quick Menu Q5 - Changes Made lists modified parameters.

5.3.8 Uploading/Downloading Data to/from the GLCP

  1. Press [Off] to stop the motor.
  2. Go to Main Menu, parameter 0-50 LCP Copy, press [OK].
  3. Select [1] All to LCP (upload) or [2] All from LCP (download).
  4. Press [OK]. A progress bar shows status.
  5. Press [Hand On] or [Auto On] to return to operation.

5.3.9 Restoring Default Settings with LCP

NOTICE: Restoring defaults may erase programming and data. Upload data to LCP before initialization for backup.

Initialization is done via parameter 14-22 Operation Mode (recommended) or manually. Initialization does not reset parameter 1-06 Clockwise Direction.

5.4 Basic Programming

5.4.1 Asynchronous Motor Set-up

Enter motor data from the nameplate into parameters 1-20 to 1-26. For optimum VVC+ performance, enter advanced data (1-30 to 1-35) from the motor datasheet. Run Automatic Motor Adaptation (AMA) via parameter 1-29.

5.4.2 PM Motor Set-up in VVC+

Set parameter 1-10 Motor Construction to a PM motor option ([1] PM, non salient SPM, [2] PM, salient IPM, non Sat, or [3] PM, salient IPM, Sat). Select [0] Open Loop in parameter 1-00 Configuration Mode. NOTICE: Encoder feedback is not supported for PM motors.

Program PM motor data (1-24, 1-26, 1-25, 1-39, 1-30, 1-37, 1-40) from motor nameplate and datasheet. Measure or calculate values as described.

Test motor operation: Start at low speed. Check installation, programming, and data. Table 5.13 provides recommendations for different inertia applications.

5.4.3 Automatic Motor Adaptation (AMA)

Run AMA to optimize converter-motor compatibility in VVC+ mode. It builds a mathematical model of the motor. Select [2] Enable reduced AMA if the complete test fails. For best results, run on a cold motor.

To run AMA using LCP:

  1. Connect terminals 13 and 27 (if not already connected).
  2. Enter Main Menu, go to parameter group 1-** Load and Motor.
  3. Set motor parameters (1-2*).
  4. Set motor cable length (1-42).
  5. Go to parameter 1-29 Automatic Motor Adaption (AMA).
  6. Select [1] Enable complete AMA, press [OK].
  7. The test runs automatically (3–10 minutes).

NOTICE: AMA function does not cause motor to run and does not harm the motor.

5.5 Checking Motor Rotation

Press [Hand On], set positive speed reference, and check speed display. Verify wiring and motor direction matches parameter 1-06 Clockwise Direction.

5.6 Checking Encoder Rotation

If encoder feedback is used: Set parameter 1-00 to [0] Open Loop, 7-00 to [1] 24 V encoder. Press [Hand On], set positive speed reference. Check parameter 16-57 Feedback [RPM] for positive feedback. NOTICE: NEGATIVE FEEDBACK If feedback is negative, reverse encoder connection or use parameter 5-71 Term 32/33 Encoder Direction.

5.7 Local-control Test

Press [Hand On], accelerate to full speed using [], note acceleration issues. Press [Off], note deceleration issues. See chapter 8.5 Troubleshooting. Reset after trip per chapter 8.2.

5.8 System Start-up

After application setup: Press [Auto On], apply external run command, adjust speed reference, remove command. Check sound and vibration. Reset after warnings/alarms.

5.9 STO Commissioning

Refer to chapter 6 Safe Torque Off (STO) for installation and commissioning.

6 Safe Torque Off (STO)

The STO function is part of a safety control system, preventing motor rotation in emergency situations. It complies with IEC/EN 61508 SIL2, IEC/EN 61800-5-2 SIL2, IEC/EN 62061 SILCL of SIL2, and EN ISO 13849-1 Category 3 PL d.

A thorough risk analysis is required to determine if STO and safety levels are sufficient. STO is controlled via terminals 37 and 38, cutting off power to IGBT gate driving circuits (Illustration 6.1).

Table 6.1 shows STO status based on terminal energization.

Test pulse filtering: Test pulses on STO lines below 1.8 V for max 5 ms are ignored (Illustration 6.2).

Asynchronous input tolerance: Discrepancy longer than 12 ms between signals at terminals 37/38 causes STO fault alarm (188). Valid signals require both terminals low for 80 ms to activate STO, and both high for 20 ms to deactivate.

6.1 Safety Precautions for STO

6.2 Safe Torque Off Installation

Follow chapter 4 Electrical Installation for power connections. Enable STO by removing the jumper between terminals 12, 37, and 38 (Illustration 6.3).

Connect a dual-channel safety device (safety PLC, light curtain, etc.) to terminals 37 and 38. The device must comply with required safety levels. Illustrations 6.4 and 6.5 show wiring schematics for STO applications.

NOTICE: STO signal must be PELV supplied.

6.3 STO Commissioning

6.3.1 Activation of Safe Torque Off

Activate STO by removing 24 V DC supply from terminals 37 and 38. This issues alarm 68 (Safe Torque Off), trips the unit, and coasts the motor. Use STO for emergency stops; use standard stop for normal operation.

NOTICE: If STO is activated during DC undervoltage, alarm 68 is skipped, but STO operation is unaffected.

6.3.2 Deactivation of Safe Torque Off

Follow Table 6.2 to deactivate STO and resume operation based on restart mode.

WARNING: RISK OF INJURY OR DEATH Reapplying 24 V DC can start the motor. Ensure all safety measures are taken before reapplying supply.

6.3.3 STO Commissioning Test

Perform a commissioning test after installation and before first operation, and after any modification. Follow instructions in 6.3.4 or 6.3.5 based on restart mode.

NOTICE: Successful commissioning test is mandatory.

6.3.4 Test for STO Applications in Manual Restart Mode

For parameter 5-19 set to [1] Safe Torque Off Alarm:

  1. Set parameter 5-40 Function Relay to [190] Safe Function active.
  2. Remove 24 V DC from terminals 37/38 while motor is driving.
  3. Verify: motor coasts, alarm 68 shows on LCP.
  4. Reapply 24 V DC to 37/38. Motor remains coasted.
  5. Send reset signal. Motor becomes operational.

Test is successful if all steps pass.

6.3.5 Test for STO Applications in Automatic Restart Mode

For parameter 5-19 set to [3] Safe Torque Off Warning:

  1. Remove 24 V DC from terminals 37/38 while motor is driving.
  2. Verify: motor coasts, Warning 68 shows on LCP.
  3. Reapply 24 V DC to 37/38. Motor becomes operational.

Test is successful if all steps pass.

NOTICE: See warning on restart behavior in 6.1.

6.4 Maintenance and Service for STO

6.5 STO Technical Data

Table 6.3 lists technical data for STO, including safety standards, safety function, performance, reaction time, and proof test interval.

7 Application Examples

7.1 Introduction

Examples provide quick reference for common applications. Parameter settings are regional defaults unless specified. Terminal settings are shown next to drawings. NOTICE: If STO is not used, a jumper is required between terminals 12, 37, and 38.

7.2 Application Examples

8 Maintenance, Diagnostics, and Troubleshooting

8.1 Maintenance and Service

Under normal conditions, the frequency converter is maintenance-free. Examine at regular intervals. Replace worn parts with original spares. Contact local Danfoss supplier for service.

WARNING: UNINTENDED START Prevent unintended motor start during service by disconnecting from mains, pressing [Off/Reset], and ensuring all equipment is wired/assembled before connecting to mains.

8.2 Warning and Alarm Types

8.3 Warning and Alarm Display

Alarms/trips show text and code on the display. Indicator lights: Yellow [Warn] for warnings, Red flashing [Alarm] for alarms (Illustration 8.3).

8.4 List of Warnings and Alarms

Table 8.1 lists warnings and alarms with their descriptions, types (Warning, Alarm, Trip lock), and causes. Table 8.2 describes Alarm Word, Warning Word, and Extended Status Word bits.

8.5 Troubleshooting

Table 8.3 provides troubleshooting guidance for common symptoms like 'Motor not running', 'Motor wrong direction', 'Max speed not reached', 'Unstable speed', 'Rough running', 'No brake', 'Open fuses/breaker', 'Current imbalance', and 'Noise/vibration'. It includes possible causes, tests, and solutions.

9 Specifications

9.1 Electrical Data

Tables 9.1, 9.2, 9.3, and 9.4 provide detailed electrical data for different mains supplies (3x380-480 V AC, 3x200-240 V AC, 1x200-240 V AC), including output current, kVA, input current, cable sizes, power loss, weight, and efficiency.

9.2 Mains Supply

Details supply voltage tolerances, frequency, phase imbalance, power factor, and switching on input supply.

9.3 Motor Output and Motor Data

Specifies output voltage, frequency, torque characteristics, and starting current.

9.4 Ambient Conditions

Lists requirements for enclosure protection, vibration, humidity, ambient temperature (with and without derating), altitude, and EMC standards.

9.5 Cable Specifications

Provides maximum motor cable lengths (shielded/unshielded), control terminal cable sizes, and STO input cable length.

9.6 Control Input/Output and Control Data

Details digital inputs (PNP/NPN), STO inputs, analog inputs (voltage/current), pulse inputs, digital/pulse outputs, analog outputs, control card outputs (+24V DC, +10V DC), RS485/USB communication, and relay outputs, including their specifications and isolation.

9.7 Connection Tightening Torques

Table 9.5 lists recommended tightening torques for mains, motor, DC connection, brake, ground, and control terminals for different enclosure sizes.

9.8 Fuses and Circuit Breakers

Recommends fuses and circuit breakers for branch circuit protection according to national/international regulations and UL 508C / IEC 61800-5-1 compliance. Table 9.6 lists specific fuse/breaker types for different power ratings and enclosure sizes.

9.9 Enclosure Sizes, Power Ratings, and Dimensions

Table 9.7 and Illustrations 9.2, 9.3, 9.4, 9.5 detail enclosure sizes (K1-K5), power ratings, dimensions (Height A, Width B, Depth C), weight, and mounting hole specifications for IP20, IP21, and NEMA Type 1 configurations.

10 Appendix

10.1 Symbols, Abbreviations, and Conventions

Table 10.1 lists symbols and abbreviations used in the manual. Conventions for illustrations, parameters, and text formatting are also provided.

10.2 Parameter Menu Structure

Provides a comprehensive list of all parameters organized by group, detailing their function and typical settings.

PDF preview unavailable. Download the PDF instead.

0900766b815521e6 AH XSL Formatter V6.2 MR8 for Windows (x64) : 6.2.10.20473 (2015/04/14 10:00JST) Antenna House PDF Output Library 6.2.680 (Windows (x64))

Related Documents

Preview VLT Midi Drive FC 280 Operating Guide - Danfoss
Comprehensive operating guide for the Danfoss VLT Midi Drive FC 280 variable frequency drive, covering installation, operation, safety, and technical specifications.
Preview VLT® Midi Drive FC 280 Installation Guide
Comprehensive installation guide for the Danfoss VLT® Midi Drive FC 280 frequency converter, covering safety precautions, installation procedures, wiring, power specifications, and EMC compliance for industrial applications.
Preview Danfoss VLT® Adjustable Frequency Drive Safe Torque Off (STO) Instruction Manual
Comprehensive instruction manual for Danfoss VLT® Adjustable Frequency Drives featuring the Safe Torque Off (STO) function. Covers installation, commissioning, safety, technical data, and compliance with EN ISO 13849-1, IEC 61508, and EN 60204-1 standards.
Preview Danfoss VLT Safe Torque Off Operating Guide
This operating guide provides comprehensive information on the Safe Torque Off (STO) function for Danfoss VLT FC Series frequency converters, covering installation, commissioning, safety, and application examples.
Preview VLT® Midi Drive FC 280: Flexible, Communicative, Easy to Use AC Drive | Danfoss
Explore the Danfoss VLT® Midi Drive FC 280, an advanced AC drive engineered for flexibility, communication, and user-friendliness. Ideal for machine builders in food & beverage, material handling, and processing industries, it offers high efficiency, integrated functional safety, and a compact design for simplified installation and operation.
Preview Danfoss DrivePro® Retrofit Design Guide: VLT® 2800 to VLT® Midi Drive FC 280 Conversion
This Danfoss DrivePro® Retrofit Design Guide provides comprehensive instructions and technical details for replacing VLT® 2800 variable frequency drives with the VLT® Midi Drive FC 280. It details product lifecycle changes, advantages of the FC 280, and offers practical guidance on conversion strategies, installation, and configuration.
Preview Danfoss VLT Midi Drive FC 280 Terminal Torque Instructions
This guide provides essential information on terminal torque specifications for the Danfoss VLT Midi Drive FC 280, ensuring proper installation and preventing damage.
Preview Danfoss VLT® HVAC Drive FC 102 Operating Guide - Installation, Operation, and Safety
Official operating guide for the Danfoss VLT® HVAC Drive FC 102 (1.1-90 kW). Covers safe installation, commissioning, operation, maintenance, specifications, and troubleshooting for HVAC applications.