Hoymiles HMS-500-1T Series Quick Installation Guide

1. Accessories

The following accessories are applicable to HMS-300/350/400/450/500-1T microinverters. Note: All accessories listed below are not included in the package and should be purchased separately.

ItemDescription
AAC Trunk Cable, 12/10 AWG Cable
BM8 x 25 screws (Prepared by the installer)
CGrounding Electrode
DAC Trunk Connector
EAC Trunk Port Cap
FAC Trunk Port Disconnect Tool
GAC Trunk End Cap
HAC Trunk Connector Unlock Tool

Diagram showing the placement of accessories A through H relative to the microinverter and mounting rail.

2. Installation Steps

The order of Step 1 and Step 2 can be reversed according to your planned needs.

Step 1. Plan and install the Microinverter

A) Mark the position of each microinverter on the rail, according to the PV module layout.

B) Fix the screw on the rail. Mounting Torque: 9 N-m.

C) Hang the microinverter on the screws, and tighten the screws. The silver cover side of the microinverter should be facing the panel.

Note:

Step 2. Plan and build the AC Bus Cable

AC Trunk Cable is used to connect the microinverter to the distribution box. Hoymiles provides AC Trunk Cable with different AC Trunk Connector spacing.

A) Select the appropriate AC Trunk Cable according to the spacing between microinverters. The connector spacing of the AC Trunk Cable should be close to the spacing between microinverters to ensure they are well-matched.

B) Determine how many microinverters you plan to install on each AC branch and prepare AC Trunk Connectors accordingly.

C) Take out segments of AC Trunk Cable as you need to make an AC branch.

  1. Disassemble the AC Trunk Connector and remove the cable: Use the AC Trunk Connector Unlock Tool to unlock the connector upper cover. Loosen the three screws with a screwdriver. Untighten the cap and remove the cable.
  2. Install the AC Trunk End Cap at one side of the AC Trunk Cable (the end of the AC Trunk Cable): Insert the AC Trunk End Cap and screw the cap back to the port, then tighten the cap. Plug the upper cover back to the Trunk connector.
  3. Install AC end cable on the other side of AC Trunk Cable (connected to the distribution box): Unlock the port upper cover, loosen the screws with a screwdriver, and remove the extra cable (skip this step if there is no cable at this side). Prepare a segment of AC cable with suitable length to connect to the distribution box, with stripping requirements fulfilled. Insert the cable into the cap in a way that the L, N, and PE lines are in corresponding slots. Tighten the screws and tighten the cap back to the port. Plug the upper cover back to the Trunk connector. Torque: 4.0±0.5N·m.

Note:

D) Repeat the above steps, lay out the cable on the rail as appropriate so that the microinverters can be connected to the Trunk connectors.

E) Attach the AC Trunk Cable to the mounting rail and fix the cable with tie wraps.

Step 3. Complete the AC Connection

A) Push the AC Sub Connector from the microinverter to the AC Trunk Connector until it clicks. [click symbol]

B) Connect the AC end cable to the distribution box, and wire it to the local grid network.

C) Please plug the AC Trunk Port Cap in any vacant AC Trunk Port to make it water and dust-proof. [click symbol]

Note:

Step 4. Create an Installation Map

A) Peel the removable serial number label from each microinverter.

B) Affix the serial number label to the respective location on the installation map (please refer to the User Manual).

Step 5. Connect PV Modules

A) Mount the PV modules above the microinverter.

B) Connect the PV modules' DC cables to the DC input side of the microinverter.

Step 6. Energize the System

A) Turn on the AC breaker for the branch circuit.

B) Turn on the main AC breaker for the house. Your system will start to generate power in about two minutes.

Step 7. Set up Monitoring System

Please refer to the DTU User Manual or DTU Quick Installation Guide, and Quick Installation Guide for S-Miles Cloud to install the DTU and set up the monitoring system.

Product information is subject to change without notice. Please download reference manuals at www.hoymiles.com.

Models: 700-2T, 500-1T Series, HMS-500-1T Series Solar Micro Inverter, HMS-500-1T Series, Solar Micro Inverter, Micro Inverter, Inverter

File Info : application/pdf, 2 Pages, 1.19MB

PDF preview unavailable. Download the PDF instead.

Quick Installation Guide HMS-500-1T Series Global EN REV1.2 compressed ?v=1737123283

References

Adobe Illustrator 24.0 (Windows) iLovePDF

Related Documents

Preview Hoymiles Single-Phase Microinverter User Manual (HMS-400/450/500-1T)
Comprehensive user manual for Hoymiles single-phase microinverters, including models HMS-400-1T, HMS-450-1T, and HMS-500-1T. Covers installation, operation, maintenance, and troubleshooting.
Preview Hoymiles HMS-500-1T Series Quick Installation Guide
A comprehensive quick installation guide for the Hoymiles HMS-500-1T Series microinverters, covering accessories, installation steps, AC connection, system energization, and monitoring setup. Includes detailed instructions and safety notes.
Preview Hoymiles HMS-500-1T Series Quick Installation Guide
Concise guide for installing Hoymiles HMS-500-1T series microinverters, covering accessories, step-by-step installation, AC connection, and system energization. Includes detailed textual descriptions of diagrams and components.
Preview Hoymiles HMS-1000-2T-NA Series Quick Installation Guide
Concise installation guide for Hoymiles HMS-1000-2T-NA series microinverters, detailing accessories, AC bus cable setup, and system connection steps for solar power systems.
Preview Hoymiles HMS-2000DW-4T Series Quick Installation Guide | Solar Microinverter Setup
Comprehensive quick installation guide for Hoymiles HMS-2000DW-4T Series solar microinverters. Learn about accessory parts, step-by-step installation, AC trunk cable connection, PV module integration, and system monitoring setup.
Preview Hoymiles HMS-2000-4T Series Microinverter Quick Installation Guide
Step-by-step installation guide for Hoymiles HMS-2000-4T series solar microinverters. Covers accessory identification, microinverter mounting, AC bus cable assembly, system connection, PV module integration, power-up procedures, and monitoring setup.
Preview Hoymiles HMS-1000-2T Series Quick Installation Guide
A concise guide for installing Hoymiles HMS-1000-2T series microinverters, detailing accessory lists, step-by-step installation procedures for microinverters and AC bus cables, AC connection, system energization, and monitoring setup.
Preview Hoymiles HMS-2000C-4T-NA Series Quick Installation Guide
A quick installation guide for the Hoymiles HMS-2000C-4T-NA Series microinverters, detailing accessories, installation steps, AC connection, and system setup.