CHNT DDSU666 Series Single-Phase DIN Rail kWh Meter

Summary

The CHNT DDSU666 series electronic energy meter is designed for power control and energy measurement in various systems, including power supply, communication industry, and construction industry. It serves as a programmable intelligent instrument for real-time measurement and visualization of electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, and electrical energy consumption.

1. Main Functions and Features

2. Specifications and Model Selection

Product Function Model DDSU666 DDSU666-E DDSU666-D DDSU666-F
Voltage Input Direct Input 0.8Un ~ 1.2Un 0.8Un ~ 1.2Un 0.8Un ~ 1.2Un 0.8Un ~ 1.2Un
Current Input Direct Input 5 (60) A 5 (80) A 5 (80) A 1.5 (6) A
Voltage, Current, Power, Frequency, Power Factor NO SI NO SI
Energy Bidirectional Active Energy Measurement NO SI NO SI
Others Multi-Rate (Clock) NO SI NO SI
Demand NO SI NO SI
Impulse Power SI SI SI SI
Communication Interface IR NO SI NO SI
RS485 SI SI SI SI
Display Mode Only LCD, 6 digits LCD single line, 7 digits
Dimensions L x W x H (mm) 36 x 85 x 66 76 x 89 x 74 (4 modules)

3. Main Technical Performance and Parameters

Technical Parameters Index Details
Signal Input Voltage Single Phase AC 220V
Wiring Mode Voltage Specification 1.1Un ~ 0.9Un; Extended working voltage range: ~0.8Un 1.2Un
Voltage Circuit Power Consumption ≤5VA/1W
Resistance > 500KΩ
Nominal Value (Current) Direct Input: AC5 (60) A / AC5 (80) A; Input via CT/PT: AC1.5 (6) A
Actual Overload Actual Overload (CT/PT Input) Instantaneous: 20Imax, application time 0.5s
Actual Overload (Direct Input) Instantaneous: 30Imax, application time: half cycle of rated frequency
Current Circuit Power Consumption ≤2VA
Resistance <20 mW
Frequency Input Range (50/60 ± 5%) Hz
Clock Clock Battery Capacity ≥1200mAh
Clock Accuracy (Daily Error) <0.5 s/d (23 °C)
Measurement Parameters and Grade Monitor LCD segment
Voltage Class, Current Class, Power Factor Class Voltage Class 0.5; Current Class 0.5; Power Factor Class 1;
Frequency Class, Active Current Class, Reactive Current Class Frequency Class 0.5; Active Current Class 1; Reactive Current Class 1;
Active Energy Class Active Energy Class 1;
Multi-Rate Energy Supports measurement of multi-rate passive, total active power negative.
Max. Demand Record Supports Max. demand record of passive, negative total active power; Demand interval and sliding time can be adjusted.
Energy Output Legitimate Constant AC200V: AC1.5 (6) A, 6400imp/kWh
AC220V: AC5 (60) A / AC5 (80) A, 800imp/kWh
Pulse Signal Output Provides 1 set (active energy) optical signal output, and isolated optocoupler open collector electrical pulse output. Pulse length: 80 ms ± 16 ms.
Communication RS485 Supports DL/T645-2007 communication protocol, adaptable for MODBUS-RTU communication protocol. Transmission speed: 1200bps, 2400bps, 4800bps, 9600bps can be set, default is 2400bps.
IR Communication Supports DL/T645-2007 communication protocol, customizable for MODBUS-RTU communication protocol. Infrared wavelength: 900nm ~ 1000nm. Communication transmission speed: 1200bps. Communication angle: ≥ ± 15°. Communication distance: ≥4m.

Wiring Diagrams

The document includes wiring diagrams for '储能' (Energy Storage) and 'BOOST' configurations, showing RJ45 connections and terminal assignments for CHNT meters. The diagrams illustrate the connections for N, N', L, and L' terminals, as well as RS485 communication ports (485A, 485B).

PDF preview unavailable. Download the PDF instead.

DDSU666-series-DIN-Rail-Kwh-Meter-Single-Phase.en .esp ?srsltid=AfmBOoqJoRuJ2WIjK0xdj4J67Vxx646eI8wUt5zV3qyuM Lno8FzCOtF GPL Ghostscript 9.55.0

Related Documents

Preview CHNT DTSU666/DSSU666 Series Digital Three-Phase Energy Meter Quick Operation Manual
Quick operation manual for CHNT DTSU666-series and DSSU666-series Digital Three-Phase Energy Meters, covering technical parameters, wiring, programming, installation, and communication protocols.
Preview Integrating CHNT DTSU666 Smart Meter with Home Assistant via Elfin-EW11
A step-by-step guide to connecting a CHNT DTSU666 smart energy meter to a Home Assistant system using an Elfin-EW11 device for wireless Modbus communication. Covers hardware setup, device configuration, and Home Assistant YAML integration for various sensor readings.
Preview CHNT KG316T Series Time Switch User Instruction Manual
Comprehensive user instruction manual for the CHNT KG316T Series Time Switch, covering installation, operation, settings, maintenance, and technical specifications. Features include automatic control for lighting and other circuits.
Preview CHNT JTX Miniature Power Relay Specifications and Features
Detailed specifications, features, contact and coil data, characteristics, and socket information for the CHNT JTX Miniature Power Relay series, including ordering information and dimensions.
Preview CHNT PES-700Pro/PES-1200Pro/PES-2400Pro Portable Energy Storage User Instruction
User instruction manual for CHNT PES-700Pro, PES-1200Pro, and PES-2400Pro portable energy storage devices. Covers safety warnings, product specifications, structure, display screen functions, troubleshooting, maintenance, and after-sales service.
Preview CHNT NXZ(H)B, NXZ(H)M Series ATS: Automatic Transfer Switch Equipment
Comprehensive technical documentation for CHNT NXZ(H)B and NXZ(H)M Series Automatic Transfer Switch (ATS) equipment. Details include scope of application, applicable standards, working conditions, model definitions, functions, characteristics, and installation dimensions. Suitable for industrial, commercial, and residential power applications.