CHNT KG316T Series Time Switch User Instruction
Document Number: NO:2022.07
Standard: IEC/EN 60947-5-1
Safety Warning
- Only professional technicians are allowed for installation and maintenance.
- Installation in any damp, condensed-phase environment with inflammable and explosive gas is forbidden.
- When the product is being installed or maintained, the power must be switched off.
- You are prohibited from touching the conductive part when the product is operating.
- The product shall be stored, installed and used in accordance with the rated control power supply voltage and specified conditions indicated in the user instructions.
- The products shall be properly wired in strict accordance with the wiring diagram.
1 Use Purpose
The KG316T series time switch is mainly used in automatic control circuits with AC 50Hz/60Hz, rated control supply voltage up to 380V, for the purpose of timed connect and disconnect control for lamppost, advertising light boxes, etc.
2 Key Technical Parameters
Table 1 Ambient Conditions
Condition | Details |
---|---|
Normal use conditions | Ambient temp.: -5°C~+40°C; average value within 24h not exceeding +35°C; altitude not exceeding 2,000m. |
Atmospheric conditions | RH shall not exceed 50% when maximum temperature is +40°C; in case of lower temperature, higher RH is allowed. Measures should be taken against occasional condensation due to temperature change. |
Installation category | II |
Transport and storage conditions | -25°C~+55°C |
Table 2 Product Specifications and Main Technical Parameters
Parameter | KG316T | KG316T-D |
---|---|---|
Wiring method | Upper terminal wiring | Lower terminal wiring |
Mounting method | Equipped | Equipped, rail mounting, wall mounting |
Operating method | Manual on, manual off, automatic on/off | |
Number of programmable groups | 16 groups | |
Time control range | 1min~168h | |
Timing error | ±2s/d | |
Output method | 1 NO contact | |
Other function | Delayed sleep function, Clock auto calibration function |
3 Installation
3.1 Outline and installation size
Refer to Figure 1 and Figure 2 for overall and installation dimensions.
Figure 1 Overall and installation size of KG316T
Shows the external dimensions and mounting details for the KG316T. Key dimensions include a height of approximately 94mm, width of 53.5mm, and depth ranging from 107.9mm to 121mm. Mounting holes and terminal locations are indicated.
Figure 2 Overall and installation size of KG316T-D
Illustrates the external dimensions and mounting details for the KG316T-D. Key dimensions include a height of approximately 67mm, width of 53.5mm, and depth of approximately 125.5mm. Mounting holes and terminal locations are indicated.
3.2 Installation Commissioning & Operations
3.2.1 Wiring method
3.2.1.1 Single-phase direct control method
For single-phase power supply loads within the switch's rated value, direct control can be used. For loads with high inrush current, use an AC contactor for expanded capacity control. Wiring diagrams are shown in Figure 3 and Figure 7.
3.2.1.2 Single-phase expanded capacity control method
If the operating current exceeds the switch's rated value for a single-phase load, use an AC contactor for expanded capacity control. Wiring diagrams are shown in Figure 4 and Figure 8.
3.2.1.3 Three-phase control method
For three-phase power supply loads, an external AC contactor is required. Wiring diagrams for AC220V and AC380V contactor coils are shown in Figure 5, Figure 6, and Figure 9.
3.2.2 Settings and Usage
Ensure the battery is inserted before use. Keys on the panel include: "RESET/RECALL", "HOUR", "MINUTE", "WEEK", "AUTO/MANU", "TIMER", and "CLOCK". Functions are available after unlocking the keyboard.
3.2.2.1 Unlock Setting
Press "RESET/RECALL" key four times to cancel the keyboard lock function. The lock symbol [lock-symbol] will disappear.
3.2.2.2 Clock Setting
Use the "HOUR", "MINUTE", and "WEEK" keys to set the current time.
3.2.2.3 Timing Setting
Press "TIMER" key to set ON times (e.g., "1 ON"). Use "HOUR", "MINUTE", "WEEK" to adjust. Press "TIMER" again to set OFF times (e.g., "1 OFF"). Repeat for up to 16 ON/OFF groups. Press "RESET/RECALL" to clear unused groups. Press "CLOCK" to confirm.
3.2.2.4 Auto/Manual mode setting
Press "AUTO/MANU" key to switch between "ON" (manual ON), "OFF" (manual OFF), and "Auto" (automatic timing control). The arrow on the LCD indicates the current mode.
3.2.2.5 Sleep delay function setting
When locked, press and hold "AUTO/MANU" and "CLOCK" for 3 seconds. Use "HOUR" or "MINUTE" to set the sleep delay mode (refer to Table 6). Pressing "AUTO/MANU" and "CLOCK" again or waiting 30 seconds exits the setting.
3.2.2.6 Clock auto calibration function
After unlocking, press and hold "RESET/RECALL" and "TIMER" keys. Adjust weekly calibration time using "WEEK". Press "CLOCK" to return. The switch calibrates automatically at 0:01 AM every Saturday.
3.2.2.7 Wiring for use
Wire according to diagrams. Connect power supply. Red indicator light should be on. After connection, green indicator light should be on, and voltage output should be present at the load terminals (220V or 380V).
Figure 10 LCD (after the unlock setting)
Displays current time, for example, "6:36 25".
Figure 11 LCD (time setting 1 ON)
Displays "1 ON" indicating the first ON time setting.
Figure 12 LCD (time setting 1 OFF)
Displays "1 OFF" indicating the first OFF time setting.
Figure 13 LCD (time setting time removal)
Displays "- : - -", used to indicate that a timing group has been removed or is not set.
Figure 14 LCD (sleep function setting closed)
Displays "o F F", indicating that the sleep function is closed or disabled.
Figure 15 LCD (calibration function setting)
Displays calibration settings, such as "-30" for automatic slowdown or "30" for automatic speedup.
Table 5 Operating Mode
No. | Operating Mode | Function Enabled |
---|---|---|
1 | MO TU WE TH FR SA SU | The same operating time for each day |
2 | MO TU WE TH FR SA | The same operating time from Monday to Saturday |
3 | MO TU WE TH FR | The same operating time from Monday to Friday |
4 | SA SU | The same operating time on Saturday and Sunday |
5 | MO TU WE | The same operating time on Monday, Tuesday and Wednesday |
6 | TH FR SA | The same operating time on Thursday, Friday and Saturday |
7 | MO WE FR | The same operating time on Monday, Wednesday and Friday |
8 | TU TH SA | The same operating time on Tuesday, Thursday and Saturday |
9 | Mo/TU/WE/TH/FR/SA/SU | Different operating time for each day |
Note 1: All operating modes only need to be set once to ensure operation according to the set procedure.
Note 2: Mo TU WE TH FR SA Su are the abbreviations of Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday.
4 Maintenance
4.1 Terminal Tightening
The terminal of the time switch should be tightened on a regular basis.
4.2 Power Cut-off
Power should be cut off during regular maintenance to ensure personal safety. Pay attention to the electrode when replacing the battery. After battery replacement, mount the battery cover and connect the power supply.
4.3 Storage
Avoid squeezing the product; the product should be stored in a well-ventilated place.
4.4 Safety Measures
For equipment that may cause material economic losses or personal safety, safety measures such as secondary circuit protection should be taken.
Table 7 Fault Analysis and Troubleshooting
Symptoms | Cause analysis | Troubleshooting method |
---|---|---|
LCD is not bright enough, or does not light up | Low battery level | Replace the battery |
Product running at timed period that is not preset | Timing setting error | Check if timing setting has time removal according to Figure 10 |
5 Environmental Protection
In order to protect the environment, the product or product parts should be disposed of according to the industrial waste treatment process, or be sent to the recycling station for assortment, dismantling and recycling according to local regulations.
[Recycling symbol] [WEEE symbol]
Quality Control
QC PASS
KG316T Series Time Switch
IEC/EN 60947-5-1
JDQ Check 10
Test date: Please see the packing