Friedrich ZoneAire® Select Series PTACS
Cooling with Electric Heat, Heat Pumps
Product Information
Purchaser:
Project:
Engineer:
Submitted By:
P.O. #:
Location:
Architect:
For Approval:
For Reference:
Accessories
Item | Plan Designation | Quantity | Item | Plan Designation | Quantity |
---|---|---|---|---|---|
PDXWSA | Wall Sleeve | Qty | PXSB23020 | Electrical Subbase - 230V 15A and 20A | Qty |
PDXWSEZ | Wall Sleeve | Qty | PXSB23030 | Electrical Subbase - 230V 30A | Qty |
PDXWSEXT18 | Deep Wall Sleeve- For walls up to 17 1/2" deep | Qty | PXSB26515 | Electrical Subase - 265V 15A | Qty |
PDXWSEXT24 | Deep Wall Sleeve- For walls up to 23 1/2" deep | Qty | PXSB26520 | Electrical Subbase - 265V 20A | Qty |
PDXWSEXT | Custom Deep Wall Sleeve, For walls from 13 1/4" to 25 1/2" deep | Qty | PXSB26530 | Electrical Subbase - 265V 30A | Qty |
PXGA | Standard Outdoor Louver | Qty | RT7 | Wired Digital Thermostat | Qty |
PXAA | Architectural Louver, clear | Qty | RT7P | Wired Programmable Digital Thermostat | Qty |
PXBG | Architectural Louver, beige | Qty | EMRTA4 | Wired Thermostat with Occupancy Sensor | Qty |
PXSC | Architectural Louver, color matched | Qty | EMRTB4 | Wired Thermostat with Occupancy Sensor | Qty |
PDXRTB | Remote Thermostat Escutcheon Kit | Qty | EMWRTA4 | Wireless Thermostat with Occupancy Sensor | Qty |
PDXDR10 | Condensate Drain Kit (pkg/10) | Qty | EMWRTB4 | Wireless Thermostat with Occupancy Sensor | Qty |
PXSBA | Sub Base | Qty | WRT2 | Wireless Digital Thermostat | Qty |
PXCJA | Conduit Kit w/ Junction Box | Qty | EMOCT | Online Connection Kit | Qty |
PDXDAA | Lateral Duct Adapter | Qty | EMRAF | Remote Access Fee | Qty |
PDXDEA | Lateral Duct Extension | Qty | EMRHCF | Energy Management Remote Humidity Control Fee | Qty |
PXFTA | Replacement Filters (Set of 10) | Qty | |||
APWM1 | FreshAire® Purification iWaves Series M | Qty |
Features
- Constant room comfort monitoring
- "Instant Heat" heat pump mode quickly heats a room to the desired temperature for increased comfort
- Even heat monitoring checks room temperature and automatically adds heat boost if necessary
- Room freeze protection - heat initiated if temperature falls to 40°F in an unoccupied room, raising temperature to 46°F
- Dual motors for quiet operation
- Durable, powder coat paint finish
- Indoor coil frost sensor protects the compressor to lengthen the life of the unit.
- Random compressor restart protects electrical systems from overload when power is restored
- Separate heat and cool range limits
- Central desk control ready allowing hotel owners to control units from a central location
- Condensate removal systems uses slinger ring technology
- Electronic defrost control ensures more run time in the efficient heat pump mode
- Washable, easy access air filters
- Service error code memory storage
- Emergency heat override
Specifications
ELECTRIC HEAT MODELS, R-32 REFRIGERANT
Models ending in 'K' are 230/208V, models ending in 'R' are 265V
Model | PZE07K3SC | PZE09K3SC | PZEO9R3SC | PZE12K3SC | PZE12R3SC | PZE15K5SC | |
---|---|---|---|---|---|---|---|
PERFORMANCE DATA | |||||||
Cooling Btu | 7,000/6,800 | 9,300/9,100 | 9,000 | 12,000/11,800 | 12,300 | 14,500/14,300 | |
Cooling Watts | 585/565 | 800/785 | 780 | 1,110/1,090 | 1,150 | 1,450/1,430 | |
Energy Efficient Ratio, EER | 12.0/12.0 | 11.6/11.6 | 11.5 | 10.8/10.8 | 10.7 | 10.0/10.0 | |
Heater Size (kW) | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 | 5.0 | |
Moisture Removal (pints/hr.) | 0.69 | 1.37/1.69 | 1.1 | 2.32/2.56 | 2.81 | 4.29/4.44 | |
Sensible Heat Ratio | 89% | 86% | 84% | 77% | 75.7% | 68.1% | |
ELECTRICAL DATA | |||||||
Voltage (1 PHASE, 60 Hz) | 230/208 | 230/208 | 265 | 230/208 | 265 | 230/208 | |
Volt Range | 253-187 | 250-187 | 292-239 | 253-287 | 292-239 | 253-187 | |
Current (Amps) | 2.6/2.7 | 3.48/3.77 | 4.2 | 4.82/5.24 | 5.92 | 6.3/6.87 | |
Electric Heater (Amps) | 15.9 | 15.9 | 13.7 | 15.9 | 13.7 | 21.9 | |
Power Factor | 0.93/0.95 | 0.97/0.98 | 0.98 | 0.99/0.98 | 0.98 | 0.99/0.98 | |
Compressor LRA | 13.4 | 1 | 17.5 | 16.0 | 23.9 | 21.0 | 34.7 |
Compressor RLA | 2.4 | 3.43 | 2.45 | 4.51 | 4.3 | 6.4 | |
Outdoor Fan Motor, HP | 0.07 | 0.07 | 0.07 | 0.07 | 0.07 | 0.07 | |
AIRFLOW DATA | |||||||
Indoor CFM, HIGH | 350 | 390 | 390 | 450 | 450 | 450 | |
Indoor CFM, LOW | 330 | 330 | 330 | 340 | 340 | 340 | |
Vent CFM | 75 | 75 | 75 | 75 | 75 | 75 | |
PHYSICAL DATA | |||||||
Sleeve Dimensions (H x W x D) | 16" x 42" x 13 3/4" (all models) | ||||||
Dimensions with Front (H x W x D) | 16" x 42" x 21 1/2" (all models) | ||||||
Cut Out Dimensions (H x W x D) | 16 1/4" x 42 1/4" (all models) | ||||||
Net Weight (lbs.) | 90 | 94 | 94 | 106 | 94 | 107 | |
Shipping Weight (lbs.) | 103 | 105 | 105 | 117 | 105 | 118 | |
R-32 Charge (oz.) | 17.6 | 18.7 | 19.0 | 21.5 | 22.2 | 27.5 | |
Dimensions with Packaging (inches) | 19 3/4" x 43 1/2" x 23" (all models) |
Receptacles and Fuse Types
Voltage | Heater Size | Receptacles | Plug |
---|---|---|---|
230V | 3.6 kW | NEMA# Receptacle 6-15R | NEMA# Plug 6-15P |
5.0kW | 6-20R | 6-20P |
Heat Pump Models, R-32 Refrigerant
Models ending in 'K' are 230/208V, models ending in 'R' are 265V
Model | PZH07K3SC | PZH09K3SC | PZH09R3SC | PZH12K3SC | PZH12K5SC | PZH12R3SC | PZH15K3SC | PZH15K5SC | |
---|---|---|---|---|---|---|---|---|---|
PERFORMANCE DATA | |||||||||
Cooling Btu | 7,200/6,800 | 7,200/6,800 | 9,200/9,000 | 9,000 | 12,000/11,800 | 12,000/11,800 | 12,300 | 14,500/14,300 | 14,500/14,300 |
Cooling Watts | 720/690 | 605/570 | 805/790 | 780 | 1,130/1,110 | 1,130/1,110 | 1,150 | 1,450/1,430 | 1,450/1,430 |
Energy Efficient Ratio, EER | 11.9/11.9 | 11.9/11.9 | 11.4/11.4 | 11.5 | 10.6/10.6 | 10.6/10.6 | 10.7 | 10.0/10.0 | 10.0/10.0 |
Heater Size (kW) | 3.5 | 2.5 | 3.5 | 3.5 | 3.5 | 5.0 | 3.5 | 3.5 | 5.0 |
Reverse Heating Btu | 6,000/5,800 | 6,000/5,800 | 8,000/7,800 | 8,200 | 10,400/10,200 | 10,400/10,200 | 10,800 | 13,600/13,200 | 13,600/13,200 |
Heating Watts | 500/485 | 500/485 | 690/670 | 685 | 895/880 | 895/880 | 1,005 | 1,245/1,210 | 1,245/1,210 |
COP | 3.5/3.5 | 3.5/3.5 | 3.4/3.4 | 3.5 | 3.4/3.4 | 3.4/3.4 | 3.2 | 3.2/3.2 | 3.2/3.2 |
Moisture Removal (pints/hr.) | 0.69 | TBD | 1.37/1.69 | 1.1 | 2.32/2.56 | 2.32/2.56 | 2.81 | 4.29/4.44 | 4.29/4.44 |
Sensible Heat Ratio | 0.89 | 0.98 | 0.85 | 0.86 | 0.78 | 0.78 | 0.753 | 0.68 | 0.68 |
ELECTRICAL DATA | |||||||||
Voltage (1 PHASE, 60 Hz) | 230/208 | 230/208 | 230/208 | 265 | 230/208 | 230/208 | 265 | 230/208 | 230/208 |
Volt Range | 253-187 | 253-187 | 253-187 | 292-239 | 253-187 | 253-187 | 292-239 | 253-187 | 253-187 |
Current (Amps) | 2.6/2.8 | 2.63/2.74 | 3.6/3.9 | 3.1 | 5.0/5.4 | 4.9/5.3 | 5.1 | 6.3/6.9 | 6.4/7.0 |
Electric Heater (Amps) | 15.9 | 15.9 | 15.9 | 13.7 | 15.9 | 15.9 | 13.7 | 21.9 | 21.9 |
Reverse Heat. Amps | 2.3/2.4 | 2.1/2.3 | 3.1/3.3 | 3.1 | 4.0/4.4 | 3.9/4.2 | 4.5 | 5.4/5.8 | 5.5/6.0 |
Power Factor | 0.93/0.95 | 0.93/0.95 | 0.97/0.98 | 0.98 | 0.99/0.98 | 0.99 | 0.98 | 0.99/0.98 | 0.99/0.98 |
Compressor LRA | 13.4 | 13.4 | 17.5 | 16.0 | 23.9 | 23.9 | 21.0 | 34.7 | 34.7 |
Compressor RLA | 2.4 | 2.4 | 3.43 | 2.45 | 4.51 | 4.51 | 4.3 | 6.4 | 6.4 |
Outdoor Fan Motor, HP | 0.07 | 0.07 | 0.07 | 0.06 | 0.07 | 0.07 | 0.08 | 0.07 | 0.07 |
AIRFLOW DATA | |||||||||
Indoor CFM, HIGH | 350 | 424 | 390 | 390 | 450 | 412 | 450 | 471 | 450 |
Indoor CFM, LOW | 330 | 365 | 330 | 330 | 340 | 365 | 340 | 412 | 340 |
Vent CFM | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 | 75 |
PHYSICAL DATA | |||||||||
Sleeve Dimensions (H x W x D) | 16" x 42" x 13 3/4" (all models) | ||||||||
Dimensions with Front (H x W x D) | 16" x 42" x 21 1/2" (all models) | ||||||||
Cut Out Dimensions (H x W x D) | 16 1/4" x 42 1/4" (all models) | ||||||||
Net Weight (lbs.) | 92.6 | 92.6 | 95 | 94 | 107 | 107 | 94 | 108 | 108 |
Shipping Weight (lbs.) | 104 | 104 | 106 | 105 | 118 | 118 | 105 | 119 | 119 |
R-32 Charge (oz.) | 17.6 | 17.6 | 18.7 | 19.0 | 21.5 | 21.5 | 22.2 | 27.5 | 27.5 |
Dimensions with Packaging (inches) | 19 3/4" x 43 1/2" x 23" (all models) |
Receptacles and Fuse Types
Voltage | Heater Size | Receptacles | Plug |
---|---|---|---|
230V | 3.6 kW | NEMA# Receptacle 6-15R | NEMA# Plug 6-15P |
5.0kW | 6-20R | 6-20P |
Due to continuing research in new energy-saving technology, specifications are subject to change without notice. Warranty limited to installations in the United States, Puerto Rico, Mexico and Canada only. See warranty documentation for full details.