This document provides submittal information and technical specifications for the ComfortStar Split System Cooling unit, model CC-VAC014-2PS1.
A graphic representation of the ComfortStar split system cooling unit is provided, showing an outdoor unit with multiple vents and an indoor unit. Note: Graphics are for representation only; actual models may differ in appearance.
The submittal form includes fields for Location, Engineer, Submitted to, Submitted by, Reference, Approval, Date, Construction, Unit #, and Drawing #.
Unit Dimensions
Model | D (mm) | H (mm) | W (mm) |
---|---|---|---|
CC-VAC008-2PS1 | 840 | 1740 | 990 |
CC-VAC010-2PS1 | 840 | 1740 | 990 |
CC-VAC012-2PS1 | 840 | 1740 | 990 |
CC-VAC014-2PS1 | 840 | 1740 | 1340 |
CC-VAC016-2PS1 | 840 | 1740 | 1340 |
CC-VAC018-2PS1 | 840 | 1740 | 1340 |
CC-VAC020-2PS1 | 840 | 1740 | 1340 |
CC-VAC022-2PS1 | 840 | 1740 | 1340 |
CC-VAC024-2PS1 | 840 | 1740 | 1340 |
Specifications for CC-VAC014-2PS1
Feature | Value |
---|---|
Comfortstar Model | CC-VAC014-2PS1 |
HP | 14HP |
Capacity (kW) | 40 |
Capacity (Btu/h) | 136500 |
Capacity (RT) | 11.4 |
EER (W/W) | 3.82 |
Max. input consumption (kW) | 16.9 |
Rate current (A) | 50 |
MAX. current (A) | 55 |
Capacity adjustment range | 50%~130% |
DC Inverter compressor Quantity | 1 |
DC Inverter compressor Type | DC/Twin-rotary |
DC Inverter compressor frequency range | 10~120 rps |
Fan motor Type | DC |
Fan motor Model | DR-310-920-8 |
Fan motor Quantity | 1 |
Fan motor Insulation class | B |
Fan motor Protection class | IP44 |
Fan motor Power output | 920 W |
Fan motor Type | axial-flow |
Fan motor Drive | Direct-driven |
Fan blade Fan Quantity | 1 |
Fan blade Air flow | 13500 m³/h |
Refrigerant Type | R410a |
Refrigerant Volume | 12 kg |
Weight Net/Gross | 260/278 kg |
Outdoor sound level | 60 dB(A) |
Maximum operating pressure | 4.5 MPa |
Pipe size Liquid pipe/Gas pipe | Ø15.9/Ø31.8 mm |
Total pipe length | 1000 m |
Max. pipe length From OU to farthest IU (Actual length) | 190 m |
Max. pipe length From OU to farthest IU (Equivalent length) | 220 m |
Max. pipe length From 1st indoor distributor to farthest IU | 90 m |
Max. vertical length Between OU & IU (OU above IU) | 90 m |
Max. vertical length Between OU & IU (OU below IU) | 110 m |
Max. vertical length Between IUs | 30 m |
Max. vertical length Between OUs | 0 m |
Cooling Outdoor side (°C) | -15~55 |
Cooling Indoor side (°C) | 16~32 |
ComfortStar
12201 N W 107th Avenue
Miami, FL 33178
Toll Free: 1.866.524.9898
Office: 305.500.9898
Fax: 305.500.9896
Website: http://www.comfortstarusa.com
The AHRI mark indicates Comfortstar participation in the AHRI Certification program. Visit ahridirectory.org for verification of individual certified products.
Comfortstar reserves the right to change design and specs without notice. Comfortstar is committed to using environmentally conscious print practices.
Document Date: 12th April 2023
Supersedes: CC-VAC014-2PS1 Apr.2023
© 2023 ComfortStar