Split System Cooling
Model: CC-VAC024-2PS1
Note: Graphics in this document are for representation only. Actual model may differ in appearance.
Location: [Not Specified]
Engineer: [Not Specified]
Submitted to: [Not Specified]
Submitted by: [Not Specified]
Reference: [Not Specified]
Approval: [Not Specified]
Date: [Not Specified]
Construction: [Not Specified]
Unit #: [Not Specified]
Drawing #: [Not Specified]
Unit Dimensions
The unit dimensions are provided through diagrams and a table. The diagrams illustrate the unit's front, side, and top views, indicating key measurements.
Diagram Description:
- Front View: Shows the main facade of the unit with visible louvers and branding.
- Side View: Displays the profile of the unit, indicating depth and height.
- Top View: Illustrates the top of the unit, showing fan grilles and other components.
Model | Dimension (mm) D | Dimension (mm) H | Dimension (mm) W |
---|---|---|---|
CC-VAC008-2PS1 | 840 | 1740 | 990 |
CC-VAC010-2PS1 | 840 | 1740 | 990 |
CC-VAC012-2PS1 | 840 | 1740 | 990 |
CC-VAC014-2PS1 | 840 | 1740 | 1340 |
CC-VAC016-2PS1 | 840 | 1740 | 1340 |
CC-VAC018-2PS1 | 840 | 1740 | 1340 |
CC-VAC020-2PS1 | 840 | 1740 | 1340 |
CC-VAC022-2PS1 | 840 | 1740 | 1340 |
CC-VAC024-2PS1 | 840 | 1740 | 1340 |
Specifications
Feature | Details | CC-VAC024-2PS1 |
---|---|---|
Capacity | HP | 24HP |
kW | 67 | |
Btu/h | 228604 | |
RT | 19.05032698 | |
EER | W/W | 3.03 |
Max. input consumption | kW | 27 |
Rate current | A | 80 |
MAX. current | A | 90 |
Capacity adjustment range | 50%~130% | |
DC Inverter compressor | Quantity | 2 |
Type | DC/Twin-rotary | |
frequency range | 10~120 rps | |
Model | DR-310-560-8-1 | |
Fan motor | Quantity | 2 |
Insulation class | B | |
Protection class | IP44 | |
Power output | 560 W | |
Type | axial-flow | |
Fan blade | Drive | Direct-driven |
Fan Quantity | 2 | |
Air flow | m³/h | 16500 |
Refrigerant | Type | R410a |
Volume | 15 kg | |
Weight | Net/Gross | 306/324 kg |
Outdoor sound level | dB(A) | 63 |
Maximum operating pressure | MPa | 4.5 |
Pipe size | Liquid pipe/Gas pipe | Ø15.9/Ø31.8 mm |
Total pipe length | 1000 m | |
Max. pipe length | From OU to farthest IU(Actual length) | 190 m |
From OU to farthest IU(Equivalent length) | 220 m | |
From 1st indoor distributor to farthest IU | 90 m | |
Between OU & IU(OU above IU) | 90 m | |
Between OU & IU(OU below IU) | 110 m | |
Max. vertical length | Between IUs | 30 m |
Between OUs | 0 m | |
Cooling | ||
Outdoor side | -15~55 °C | |
Indoor side | 16~32 °C |
Company Information & Certifications
ComfortStar
12201 N W 107th Avenue
Miami, FL 33178
Toll Free: 1.866.524.9898
Office: 305.500.9898
Fax: 305.500.9896
Website: http://www.comfortstarusa.com
Certifications:
- AHRI CERTIFIED® (AHRI Standard 210/240) - Certification applies only when the complete system is listed with AHRI. Visit ahridirectory.org for verification of individual certified products.
- CULUS LISTED
The AHRI mark indicates Comfortstar participating in the AHRI Certification program.
Comfortstar reserves the right to change design and specs without notice. Comfortstar has a policy of updating data continuously and is committed to using environmentally conscious print practices.
Document Date: 12th April 2023
Supersedes: CC-VAC024-2PS1 Apr.2023
© 2023 ComfortStar