Owner's Manual

Metered Rack PDUs

Low-Voltage Models: PDUMH15, PDUMH15S, PDUMH20

High-Voltage Models: PDUMH20HV, PDUMH30HV, PDUMH32HV

Important Safety Instructions

SAVE THESE INSTRUCTIONS

This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these instructions may affect your warranty.

Important Warnings

Installation

Note: The illustrations may differ somewhat from your PDU model.

1 Determine Installation Configuration

The PDUs covered by this owner's manual support these installation configurations: 2U, 1U and 0U rackmount; wall-mount and under-counter. See below for installation configurations pertaining to your specific model. Choose a configuration and follow the installation instructions in the appropriate section of Step 1 before proceeding to Step 2.

Note: Regardless of installation configuration, the user must determine the fitness of hardware and procedures before mounting. The PDU and included hardware are designed for common rack and rack enclosure types and may not be appropriate for all applications. Exact mounting configurations may vary.

1-1 2U Rack Installation

Attach the included brackets to the side of the PDU with the included screws (A). After installing the brackets, position the PDU in the rack and install four user-supplied screws through the unit's brackets and into the rack rails (B).

1-2 1U Rack Installation

Attach the PDU to the rack by inserting four user-supplied screws (A) through the PDU mounting brackets (B) and into the mounting holes of the rack rail as shown.

1-3 0U Rack Installation

Part 1: Remove the screws (C) attaching the mounting brackets to the PDU, change the orientation of the brackets as shown and reattach the brackets. Use only the screws supplied by the manufacturer or their exact equivalent (#6-32, 1/4" flat head). Part 2: Attach the PDU vertically by inserting two or more user-supplied screws (A) through the PDU mounting brackets (B) and into mounting points in the rack or rack enclosure.

1-4 Wall Installation

After repeating Part 1 above, attach the PDU to a stable mounting surface by inserting two or more user-supplied screws (A) through the PDU mounting brackets (B) and into secure mounting points on the mounting surface.

1-5 Under-Counter Installation

After repeating Part 1 above, attach the PDU to a stable mounting surface by inserting four user-supplied screws (A) through the PDU mounting brackets (B) and into secure mounting points on the mounting surface.

2 Attach the input plug of the PDU to a grounded outlet

Insert the plug directly into a grounded outlet that does not share a circuit with a heavy electrical load (such as an air conditioner or refrigerator).

Note: Select models include an input plug adapter that converts plug types for various applications. See below for details.

2-1 NEMA Adapter Connection (Optional - PDUMH20HV Only)

The PDUMH20HV includes a plug adapter that adds a NEMA L6-20P plug to the input power cord. Use this adapter only if you will be connecting the PDUMH20HV to a NEMA L6-20R outlet. Insert the IEC 60320 C19 connector A of the adapter into the IEC 60320 C20 connector B of the input power cord. Secure the connection with the retention bracket C by using the included bolts to fasten the two halves of the bracket around the connection as shown.

Caution: To avoid the risk of electric shock, ensure that the Neutral (L2) conductor has been identified before connecting the PDU.

2-2 Input Power Cord Connection (PDUMH20HV Only)

Insert the IEC 60320 C19 connector A of the input power cord into the IEC 60320 C20 inlet B of the PDU. Connect the other end of the input power cord C to a compatible source of AC power, such as a UPS system, PDU or utility outlet. The PDU should be provided with over-current protection. PDUMH20HV should be provided with a maximum 20A branch-rated over-current protection device.

Note: The AC power source should not share a circuit with a heavy electrical load (such as an air conditioner or refrigerator).

3 Attach equipment to the PDU

Do not exceed the load rating of the PDU. The total electrical current used by the PDU will be displayed on the digital meter in amperes.

Features

1 Input Plug (Varies by Model)

Description of various input plug types shown in diagrams: NEMA 5-15P, NEMA L5-20P, NEMA L6-20P/L6-30P, IEC-320-309P.

2 Outlets (Vary by Model)

During normal operation, the outlets distribute AC power to connected equipment. Description of outlet types shown in diagrams: NEMA 5-15R, NEMA 5-15/20R, IEC-320-C13, IEC-320-C19.

3 Circuit Breaker

If the current drawn by the equipment connected to the PDU exceeds the Maximum Load Rating, the circuit breaker will trip to prevent possible damage. When a circuit breaker trips, its plunger will pop up. Disconnect excess equipment and allow the breaker to cool at least one minute before depressing the plunger to reset the breaker. Description of breaker types shown: Magnetic, 2-Pole Branch-Rated Breaker (PDUMH30HV); Thermal 2-Pole Breaker (PDUMH32HV).

4 Ammeter

The total electrical current used by the PDU will be displayed on the digital meter in amperes.

5 Grounding Lug

Use this screw to connect the PDU to ground.

6 Power Inlet (Select Models)

The IEC-320-C20 power inlet connects to the included power cord or a compatible user-supplied power cord. The inlet includes a bracket to secure the cord connection.

7 Input Plug Adapter (Select Models)

Converts plug types for various applications. Description of adapter shown.

8 Longer 1U Mounting Brackets

Use these brackets to mount the 1U PDU horizontally in a standard rack or rack enclosure. The mounting depth can be adjusted by attaching the brackets to different positions on the PDU.

9 Shorter 0U Mounting Brackets

Use these brackets to mount the PDU in a 0U rack, wall or under-counter configuration for 1U PDU models.

10 2U Mounting Brackets

Use these brackets to mount the 2U PDU horizontally in a standard rack or rack enclosure, or in an under-counter configuration.

11 Cord Retention Shelves (Optional)

When installed on the PDU, these shelves provide secure attachment points for connected equipment power cords. Use the included cable ties to secure cords to the shelf.

Warranty & Warranty Registration

LIMITED LIFETIME WARRANTY

Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for its lifetime. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, at its sole discretion. Service under this Warranty can only be obtained by delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609. Seller will pay return shipping charges. Call Tripp Lite at (773) 869-1234 before sending any equipment back for repair.

THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).

WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.

WARRANTY REGISTRATION

Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*

* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)

Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:

The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Models: PDUMH32HV Metered Rack PDUs, PDUMH32HV, Metered Rack PDUs, Rack PDUs, PDUs

File Info : application/pdf, 20 Pages, 3.40MB

PDF preview unavailable. Download the PDF instead.

TRIPP LITE PDUMH20HV (01)

References

Related Documents

Preview Tripp Lite PDU3MV6L2130: 3-Phase Metered Rackmount PDU - Technical Specifications
Detailed specifications and features for the Tripp Lite PDU3MV6L2130, a 3-phase metered rackmount power distribution unit with 48 outlets, 8.6kW capacity, and digital load metering.
Preview Tripp Lite PDU3EVN6G30B 3-Phase Monitored 0U Vertical PDU - Technical Specifications
Detailed technical specifications and features for the Tripp Lite PDU3EVN6G30B, a 3-Phase Monitored 0U Vertical Power Distribution Unit with 48 outlets, 10kW capacity, HTML5 network interface, and rackmount compatibility.
Preview Tripp Lite PDUV30HV Basic Rackmount PDU - 38 Outlets, 30A
Specifications and features of the Tripp Lite PDUV30HV, a 30A, 38-outlet basic rackmount power distribution unit for server, network, and telecom racks. Includes 0U vertical mounting and L6-30P input.
Preview Tripp Lite Single-Phase Power Distribution Units (PDUs) Visio Stencil Index
An index of Tripp Lite Visio stencils for Single-Phase Power Distribution Units (PDUs), featuring a comprehensive list of models and visual representations for network and IT infrastructure planning.
Preview Tripp Lite PDUMH30HVATNET: Single-Phase Switched Rack-Mount ATS PDU
Explore the features and specifications of the Tripp Lite PDUMH30HVATNET, a 5-5.8kW single-phase switched rack-mount Automatic Transfer Switch (ATS) PDU designed for reliable power distribution in IT environments.
Preview Tripp Lite PDU1215 / PDU121506 Rack PDU Technical Specifications and Dimensions
Detailed technical drawing and specifications for Tripp Lite PDU1215 and PDU121506 rack-mountable power distribution units, including dimensions, outlet configuration, and material tolerances.
Preview Tripp Lite Single-Phase Power Distribution Units (PDUs) Stencil Guide
This document serves as a visual stencil guide for Tripp Lite's comprehensive range of single-phase power distribution units (PDUs). It lists numerous model numbers, providing a reference for their physical configurations.
Preview Tripp Lite Single-Phase Power Distribution Units (PDUs) Visio Stencil Guide
A comprehensive catalog of Tripp Lite Single-Phase Power Distribution Units (PDUs) and their corresponding Visio stencil shapes, detailing front, rear, and side views for each model.