ADDRESSABLE CO DETECTOR

INSTALLATION AND OPERATION MANUAL

1. Introduction

1.1. Overview

The NFA-T01CD Detector is designed for continuous monitoring of carbon monoxide concentration in the surrounding environment. When the gas concentration reaches the preset alarm threshold, the Detector triggers audible and visual alarms, activates its output function, and transmits a signal to the combustible gas early warning control system. This proactive response helps to effectively mitigate the risk of serious incidents caused by carbon monoxide leaks. The Detector is well-suited for use in residential homes, hotels, apartments, underground parking areas, and similar settings.

NFA-T01CD Addressable CO Detector

1.2. Feature and Benefits

1.3. Technical Specifications

Input voltage 24V DC (15V~28V pulse voltage)
Current consumption Stand by 1.5mA. Alarm 15mA
Output method Active output, output current < 5mA.
Target gas carbon monoxide (CO)
Measurement/Sensor Range 0~240×10^-6 ppm
Alarm Set Value 150×10^-6 ppm
Sensor Lifetime 5 years
LED Indicator Normal monitoring state: The green light flashes and the buzzer does not sound.
Alarm state: The red light remains constantly illuminated and the buzzer sounds.
Fault state: The yellow light remains constantly illuminated and the buzzer sounds intermittently.
Sensor service life expiry: The yellow light flashes and the buzzer sounds intermittently.
Operating Temperature: -10°C~+55°C.
Humidity 0 to 95% Relative Humidity, non-condensing
Colour beige
Weight 96g
Dimension/Height Diameter 100mm/49mm

2. Structural Features and Operational Principles

2.1. Structural Features

The overall and installation dimensions of the NFA-T01CD detector are shown in diagrams, providing measurements in millimeters for diameter and height.

2.2 Operational Principles

This product employs a high-sensitivity electrochemical carbon monoxide sensor with excellent selectivity, allowing for real-time monitoring of carbon monoxide levels in the environment. When the detected concentration exceeds the preset alarm threshold, the detector triggers audible and visual alarm signals and activates the control output. At the same time, the alarm information is transmitted to the controller via the communication bus for prompt response.

3. Installation and Wiring

Warning: Prior to installing the Detector, ensure that the controller is powered off or the circuit power is disconnected, and verify that all bases are securely installed.

The Detector should be installed in locations where the target gas is likely to occur or accumulate. It is recommended to refer to the suggested positions in Fig. 3 and ensure the device is installed and operated in accordance with the specific requirements of the application environment.

Fig. 3 Installation Location of NFA-T01CD

A diagram illustrates the recommended installation location for the NFA-T01CD detector, suggesting placement near potential carbon monoxide sources such as a gas stove, with a recommended height range of 1m to 2m from the floor, and showing proximity to a range hood and ceiling.

Installation method: The installation procedure for the Detector is illustrated in Fig. 4.

Fig. 4 Installation Diagram of NFA-T01CD

This diagram details the installation procedure for the detector, showing how to align the detector with its base using a protruding mark, rotate it clockwise for mounting, and secure it with an anti-loosening screw, referencing a pre-embedded box, wall, and wiring conduit.

Wiring requirements: The bus connection line should be made of 2×1.0mm^2 or 1.5mm^2 wire; these lines should be laid through metal conduits (cable trays) or flame-retardant PVC conduits.

Fig. 5 Wiring Method for NFA-T01CD

Two diagrams illustrate the wiring method for the NFA-T01CD detector, showing the bus connections and output ports.

4. Detector Configuration

4.1. Self-Check and Muting

Under normal monitoring conditions of the Detector, briefly press the "Self-Check/Mute" button, and the yellow, green, and red lights will flash once each, cycling three times. When the lights are on, the buzzer will sound; when the lights are off, the buzzer will cease. When the Detector is in an alarm/fault state, briefly press the "Self-Check/Mute" button to halt the buzzer and enter the mute state.

4.2. Preparation

The NFA-T01PT programming tool is used to configure CO detectors soft address and parameter. This Programming tool is not included, must be purchased separately. The programming tool is packed with twin 1.5V AA battery and cable, ready for usage once received.

It is mandatory for the commissioning personnel to have programming tool in order to adjust the detector conferring to the site situation and environmental requirements.

Program a unique address number for each device according to the project layout before placing from the Terminal Base.

Warning: Disconnect the loop connection whilst connecting to the programming tool.

4.3. Write: Addressing

Note: If display "Success”, means the entered address is confirmed. If display "Fail”, means failure to program the address (Figure 9).

Fig.6

Fig.7

Fig.8

Fig.9

Illustrations depict the NFA-T01PT programming tool and its interface. Figure 6 shows the tool connected to the detector. Figures 7, 8, and 9 display the programming tool's screen during address configuration, showing options like 'Read', 'Write', 'Power', 'Exit', and the outcome of address programming as 'Success' or 'Fail'.

Press "Exit" key to go back Main Menu. Press “Power” key to switch-off the programming tool.

5. Handling and Storage

When transporting, handling, and storing the Detector, it must be in the packaged state. During loading and unloading, handle with care to prevent damage from impact, dropping, or compression. The storage environment should be well-ventilated and dry, and the product must not be stored in the open air.

6. Precautions

7. General Maintenance

Appendix 1

Limitation of CO Detectors

The CO detector cannot last forever. To keep the detector working in good condition, please maintain the equipment continuously according to recommendations from manufacturers and relative nation codes and laws. Take specific maintenance measures on the basis of different environments.

The CO detector contains electronic parts. Even though it is made to last for a long period of time, any of these parts could fail at any time. Therefore, test your CO detector at least every half-year according to national codes or laws. Any CO detectors, fire alarm devices or any other components of the system must be repaired and/or replaced immediately if they fail.

Models: NFA-T01CD, NFA-T01CD Addressable CO Detector, Addressable CO Detector, CO Detector, Detector

File Info : application/pdf, 10 Pages, 471.90KB

PDF preview unavailable. Download the PDF instead.

NFA-T01CD-User-Manual6880bc00248ec

References

Related Documents

Preview Norden NFA-T03DH Duct Detector Housing: Installation and Operation Manual
Comprehensive installation and operation manual for the Norden NFA-T03DH Duct Detector Housing. Learn about product features, technical specifications, location requirements, installation procedures, and maintenance.
Preview Norden NFA-T02WB Sounder Strobe Waterproof Box: Installation and Operation Manual
Comprehensive installation and operation manual for the Norden NFA-T02WB Sounder Strobe Waterproof Box. Details features, technical specifications, and installation guidelines for fire detection systems in outdoor environments.
Preview Norden NFA-T01IB Isolator Base: Installation and Operation Manual
Comprehensive installation and operation manual for the Norden NFA-T01IB Isolator Base, detailing its features, technical specifications, installation procedures, maintenance, and troubleshooting. Compliant with EN 54-17.
Preview Norden NFA-T01WB Fire Button Waterproof Box: Installation and Operation Manual
Comprehensive installation and operation guide for the Norden NFA-T01WB Fire Button Waterproof Box. Covers product safety, features, technical specifications, and detailed installation steps for outdoor and harsh environments.
Preview NORDEN NFA-T01RI Remote Indicator Installation and Operation Manual
This manual provides detailed instructions for the installation, operation, and maintenance of the NORDEN NFA-T01RI Remote Indicator, a fire alarm accessory designed to signal alarm status.
Preview NORDEN ENC-HHP7Z-300R-34 IP Dual Sensor Thermal PTZ Camera | Technical Specifications
Detailed specifications for the NORDEN ENC-HHP7Z-300R-34 IP Dual Sensor Thermal PTZ Camera, featuring 384x288 thermal resolution, 25mm motorized focus lens, 40x optical zoom, IP67 rating, and PoE++ support for advanced surveillance applications.
Preview Norden NVS-AC10006VC 120W Volume Controller - Datasheet
Discover the Norden NVS-AC10006VC, an elegant and compact 120W volume controller with a 24V override function and 5 selectable volume positions. Ideal for commercial audio installations in hotels, offices, and showrooms, it integrates seamlessly with 100V line speakers and supports fire fighting linkage. View detailed specifications, dimensions, and ordering information.
Preview Norden ENC-STPGH-00R-30 IP Thermal Panoramic Camera Specifications and Ordering Information
Detailed specifications, features, and ordering information for the Norden ENC-STPGH-00R-30 IP Thermal Panoramic Camera. This device features a 640x512 uncooled infrared detector, 25mm fixed thermal lens, and IP66 rating for robust environmental protection.