Carrier 52C and 52P Series Owner's Manual

PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS

7,000-15,000 Btuh

General

Thank you for choosing Carrier. This manual provides information for the installation, operation, and maintenance of the 52C and 52P units. These units offer high standards of quality in performance, workmanship, durability, and appearance for year-round heating and cooling.

The following units are covered:

  • 52CE 60 Hz cooling with electric heat
  • 52CQ 60 Hz cooling, electric heat, and heat pump
  • 52PE 60 Hz cooling with electric heat
  • 52PQ 60 Hz cooling, electric heat, and heat pump
  • 52PC 60 Hz cooling only

All models are designed for through-the-wall installation. Separate installation instructions are included with accessory components.

Unit Inspection

Examine the unit for damage incurred during shipment and file a claim with the transit company if damage is found. The data information plate, typically found on the front panel, lists important electrical and model information.

Front Panel

To remove the front panel, grasp it firmly at the center top and bottom and pull upward at the bottom and forward at the top to release magnetic latches. Note that screws may be located behind the indoor air inlet filters, requiring filter removal first. The front panel must be removed for installation procedures and checks.

Figure 1: Sample Data Information Plate - This plate displays the model number, voltage ranges, and other critical electrical data for the unit.

Figure 2: Removing Front Panel - Illustrates the method for detaching the front panel, showing how to disengage magnetic latches and partition hooks.

Model Number Nomenclature

Figure 3: Model Number Nomenclature - This diagram breaks down the model number structure, indicating Series Designation (PTAC), Comfort Series (CE, CQ), Premier Series (PC, PE, PQ), Latest Revision, Electric Heater Size (kW), Cooling Capacity (Btuh), Chassis Options (Standard, Corrosion Protection, Thermostat Control), Packaging, Non-Performance Changes, and Electrical Data (Voltage, Hz).

To install the front panel:

  1. Hold the front panel at a 5-10 degree angle from vertical, engaging the top posts into the unit slots.
  2. Lower the panel flat against the unit, ensuring the power cord is routed through the notch. Magnetic latches will secure it.

To install the locking feature:

  1. Remove indoor air inlet filters to expose engagement holes.
  2. Secure the front panel with two field-supplied screws into the engagement holes.
  3. Replace the filters.

Figure 4: Front Panel Installation with Locking Feature - Depicts the process of securing the front panel using screws into designated engagement holes.

Electrical Data

WARNING: ELECTRICAL SHOCK HAZARD Do not alter the cord or plug, and do not use an extension cord, as this may result in personal injury or unit damage.

Ensure your outlet matches the plug's blade configuration and is within reach of the service cord. A hardwire kit is available as an accessory.

IMPORTANT: All standard cord-connected 265-v units require a field-installed electrical sub-base accessory.

All Units

Wire Size

Use the recommended wire size from Table 1 and install a single branch circuit. All wiring must comply with local and national codes. Copper conductors are required.

Grounding

The unit is grounded through the service cord plug or a separate ground wire. Ensure the branch circuit or outlet is grounded.

TABLE 1 – SUGGESTED BRANCH CIRCUIT WIRE SIZES*
NAMEPLATE AMPSAWG WIRE SIZE†
7.0 to 1214
12.1 to 1612
16.1 to 2410

LEGEND: AWG - American Wire Gage; *Single circuit from main box; †Based on copper wire at 60 C temperature rating.

Voltage Supply

Verify the voltage supply at the outlet is within the ranges specified on the unit's data information plate.

Cord-Connected Units

The 250-v outlet must match the plug for 208/230-v units. For 265-v units, an accessory electrical subbase is required. Refer to Table 2 for proper receptacle and fuse types.

Power Cord Protection

The power cord for 230/208-v units includes shock and fire prevention. It automatically disconnects under unsafe conditions and can be reset via the button on the plug head. Perform an operational check using the TEST/RESET buttons after installation.

NOTE: 265-v models do not have this feature and require the electrical subbase accessory.

TABLE 2 – RECEPTACLES AND FUSE TYPES – 250,265 VOLTS
RATED VOLTS250265
15 Amps20 Amps30 Amps15 Amps20 Amps30 Amps
TIME-DELAY TYPE FUSE (or HACR Circuit Breaker)1520*30152030

LEGEND: HACR - Heating, Air Conditioning, Refrigeration; *May be used for 15-amp applications if fused for 15 amp.

Installation

Chassis Installation

Units are shipped without a sleeve. For replacement installations, using a Carrier sleeve and grille is recommended. The 52C and 52P units can retrofit sleeves/grilles from General Electric, Amana, Trane, and Friedrich. Carrier Corporation approval is required for other retrofit applications.

For competitive retrofits, ensure factory-installed foam seals on tube sheets create a good seal between the outdoor grille and outdoor coil tube sheets to prevent air recirculation.

CAUTION: For retrofit applications, foam seals on outdoor coil tube sheets must make a seal between the coil and the grille to prevent performance loss and premature component damage.

TABLE 3 – RETROFIT WALL SLEEVES
MANUFACTURERWALL SLEEVE PART NUMBER
General ElectricMetal Sleeve RAB71, Plastic Sleeve RAB77
AmanaMetal Sleeve WS900B
TraneMetal Sleeve SLV149
FriedrichT-Series Metal 11½-in. deep wall sleeve*
Standard depth wall sleeve 16 x 42 x 13¾-in. PXWS

*FR-SLEEVE-EXT accessory is required for retrofit into Friedrich (T-Series) wall sleeves.

Figure 5: Unit Components - Diagram labeling key parts: Indoor-Air Inlet Filters, Discharge Grille, Wire Screen, Outdoor Orifice, Coil Tube Sheets, Front Panel, Indoor Coil, Plug Test/Reset Buttons, Basepan, Outdoor Grille, Wall Sleeve, Vent Door, Shipping Tape, Vent Door Cable.

Competitive Sleeve Preparation

IMPORTANT: Inspect the wall sleeve thoroughly before installation. The manufacturer is not responsible for costs or damages due to sleeve defects or improper installation.

WARNING: Disconnect all power to the unit to avoid electrical shock during installation.

Remove any existing foam baffles from the outdoor grille if present.

  • GE Sleeves Only: Remove the metal clip on the mounting rail of metal sleeves (Figure 7) and the bottom seal from plastic sleeves (Figure 8).

Installation of a Carrier Wall Sleeve Using a Non-Carrier Grille: This scenario requires an Accessory Baffle Kit (Figure 9) to ensure a proper seal and prevent air recirculation, which degrades performance.

Figure 6: Remove Existing Baffles on Competitive Outdoor Grilles - Shows baffles to be removed from competitive outdoor grilles.

Figure 7: Remove Metal Clip on GE Metal Sleeve - Illustrates removing a metal clip from a GE metal sleeve.

Figure 8: Remove Bottom Seal from GE Plastic Sleeve - Shows removing the bottom seal from a GE plastic sleeve.

Figure 9: Accessory Baffle Kit - Image of the accessory baffle kit.

Figure 10: Installation Complete - Visual representation of a completed installation.

Install Chassis in Sleeve

Inspect foam gaskets on the chassis and replace if torn or missing. These gaskets create a weather barrier with the sleeve face.

WARNING: The chassis weighs up to 150 lb. Seek assistance when lifting the unit.

If retrofitting into GE, Amana, Trane, or Friedrich sleeves, remove any existing foam seals from the manufacturer's grille before installing the unit.

Remove shipping tape from the vent door (Figure 11). Failure to do so may prevent the door from opening and cause damage.

Carefully remove and discard power cord packing material.

Lift the chassis level with the wall sleeve and slide it in until the foam gaskets rest firmly against the front of the wall sleeve (Figure 12).

Secure the chassis to the wall sleeve using four 1¾-in. screws taped to the control box. Align screw holes on the chassis with those in the sleeves. For Carrier sleeves, use the top-most and bottom-most holes. For competitive sleeves, align the correct attachment holes.

Figure 11: Location of Shipping Tape on Vent Door - Pinpoints the location of shipping tape on the unit's vent door.

Figure 12: Unit Gaskets and Tube Sheets - Diagram showing the unit's gaskets and tube sheets.

Figure 13: Chassis Mounting - Illustrates the chassis mounting points, including specific holes for Carrier sleeves and general attachment holes for competitive sleeves.

Wall Thermostat Installation

These instructions apply to RC and RP units only. Carrier thermostats are recommended.

IMPORTANT: Only trained, qualified personnel should install electrical accessories.

Thermostat Wire Routing

Use 18 to 20 gage solid thermostat wire. Route the wire around or under the wall sleeve, not through it. Then, route it behind the front panel to the terminal connector.

Install Thermostat

  1. Ensure power to the unit is disconnected.
  2. Pull the terminal connector to remove it for easier wiring.
  3. Connect thermostat wires to the chassis terminal board connector.
  4. Reinstall the terminal connector.
  5. Restore power to the unit.

Refer to the thermostat's installation instructions for specific details.

Figure 14: Control Box Terminal Connector for Wall Thermostat Models - Shows the terminal connector on the control box.

Figure 15: Terminal Connector Removal and Replacement - Illustrates the process of removing and replacing the terminal connector.

Figure 16: Wiring Connections - Details the terminal designations (R, G, Y, W, O, C) and their functions, with notes for heat pump connections and digital thermostats.

Operation

IMPORTANT: During initial startup, high humidity may cause condensation on the discharge grille. Keep doors and windows closed.

Comfort Controls

Adjust Airflow Direction

The discharge air grille directs air forward. For upward discharge, remove the grille from the front panel, rotate it 180 degrees, and reinstall it.

Adjust Vent

The vent handle, located on the left side, opens or closes the vent. The vent stays in the last position set until the handle is turned again. A magnet ensures positive closure.

Figure 17: Vent Door - Shows the unit's vent door, vent filter, and vent handle, with a magnet indicated for closure.

Setting Temperature Limits

Setting temperature limits restricts the user's temperature control range. This adjustment is optional and not applicable to remote control units.

Factory settings are 60 F to 90 F. To restrict the temperature control knob's rotation:

  1. Remove the front panel.
  2. Remove the temperature control knob to access the temperature limiter.
  3. Remove standoff pins from the 60 F and 90 F indicator holes.
  4. Replace standoff pins in the desired minimum and maximum temperature holes.
  5. Reinstall the temperature control knob and front panel.

NOTE: Temperature indicators are approximate.

Figure 18: Operating Controls - Diagram showing the unit's operating controls, including temperature control, fan cycle switch, and outdoor thermostat (for heat pump units).

Operating Controls

Controls are located on the front of the control box door, under the front panel.

Fan Cycle Switch

This switch, often on a wall thermostat for RC/RP units, offers two fan modes:

  • CON (Continuous): Fan runs continuously for consistent temperature.
  • CYC (Cycle): Fan cycles on/off with the compressor, leading to wider temperature/humidity variations.

Outdoor Thermostat (52CQ and 52PQ Heat Pump Units Only)

The setscrew position determines operation. If set to heat pump mode, the unit uses reverse cycle heating. When outdoor coil temperature drops, the electric heater engages. If set to electric heat mode only, the compressor is disabled for heating and cooling (or just heating if a wall thermostat is used).

Operating Modes

  • Outside Air: Turn the vent handle fully open to bring in outside air.
  • OFF: Terminates unit operation.
  • FAN: Circulates air at high speed.
  • HIGH HEAT OR HIGH COOL: Select mode and rotate knob for maximum heating/cooling to quickly adjust room temperature.
  • LOW HEAT OR LOW COOL: Select mode and rotate knob for minimum heating/cooling, providing quiet operation and dehumidification.

Fan Speed Control for 52P and 52C Wall Thermostat Models

Fan speed is user-selectable at the unit for maximum comfort.

Figure 19: 52P Unit Controls Shown - Illustrates the controls on the 52P unit.

Figure 20: 52P Unit with Wall Thermostat Control Shown - Shows the 52P unit with a wall thermostat control interface.

Care and Maintenance

Regular cleaning is essential for proper performance, efficiency, and longevity. Clean the fan, outdoor coil, blower wheel, blower scroll, electric heater, and drain passages at least annually. Air inlet filters should be cleaned monthly.

More frequent cleaning may be needed in dusty environments or those prone to fungus growth.

CAUTION: Fungus growth inside the unit can be a fire hazard. Clean the unit according to instructions.

Indoor-Air Inlet Filters

Indoor-Air Inlet Filters

Clean indoor-air inlet filters once each month. Clogged filters restrict airflow, potentially causing severe component damage and efficiency loss.

Cleaning Indoor-Air Inlet Filter

Two filters are located on the backside of the front panel. To clean:

  1. Grasp each filter with both hands.
  2. Gently pull the filter up and away from the unit (Figure 21).
  3. Clean using a vacuum or a soft bristle brush with mild detergent. Rinse with clean water if detergent is used.
  4. Allow filters to air dry completely.
  5. Re-insert dry filters into the front panel.

Additional filters are available.

Figure 21: Indoor-Air Inlet Filter Removal - Shows how to grasp and pull out an indoor air inlet filter.

External Parts

External parts, including the polymer sleeve and grilles, should be cleaned with household detergent and water.

Internal Parts

Internal parts should be cleaned at least once a year. The outdoor vent filter should be cleaned at least once per cooling or heating season.

Internal parts to clean include:

  • Outdoor vent filter
  • Basepan
  • Outdoor orifice and fan
  • Indoor and outdoor refrigeration coils
  • Indoor blower wheel
  • Wire screen
  • Scroll
  • Wall sleeve internal surfaces
  • Outdoor grille

Figure 22: Outdoor Vent Filter (Left Side of Chassis) - Shows the location of the outdoor vent filter.

Figure 23: Blower Wheel and Scroll - Diagram illustrating the blower wheel and scroll.

Preventative Maintenance

Preventative maintenance ensures proper unit operation, efficiency, and longevity. Check and verify equipment operation several times a year.

During regular inspection and maintenance, follow these guidelines:

  • Wash both sides of the outdoor coil.
  • Wash the basepan and outdoor vent filter.
  • Wash the indoor coil.
  • Clean the blower wheel and front panel.
  • Clean or install new indoor-air inlet filters.
  • Ensure knobs are secure and operable.
  • Inspect cord and receptacle.
  • Secure electrical connections.
  • Ensure the front panel is properly mounted and not damaged.
  • Ensure the wall sleeve is installed properly.
  • Ensure heat and cool cycles operate properly.
  • Check the power cord protective device by pressing the TEST button, then the RESET button.

Troubleshooting

TROUBLESHOOTING
POSSIBLE CAUSESSOLUTIONS
UNIT DOES NOT START
  • Check that plug is securely in wall receptacle.
  • Check RESET button on cord or plug. See Note 1.
  • Replace the fuse. See Note 1.
  • Reset circuit breaker. See Note 1.
  • Switch mode dial to an operating mode.
UNIT NOT COOLING/HEATING ROOM
  • Make sure that curtains, blinds or furniture are not restricting or blocking unit airflow.
  • Reset to a lower or higher temperature setting.
  • Remove and clean filters.
  • Allow sufficient amount of time for unit to heat or cool the room. Start heating or cooling early before outdoor temperature, cooking heat or gatherings of people make room uncomfortable.
  • Close vent door.
UNIT MAKING NOISESClicking, gurgling and whooshing noises are normal during operation of the unit.
WATER DRIPPING OUTSIDEIf a drain kit has not been installed, condensation run-off during very hot and humid weather is normal. See Note 2. If a drain kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs.
WATER DRIPPING INSIDEWall sleeve must be installed level for proper drainage of condensation. Check that installation is level and make any necessary adjustments.
ICE OR FROST FORMS ON INDOOR COILWhen outdoor temperature is approximately 55 F or below, frost may form on the indoor coil when unit is in Cooling mode. Switch unit to FAN operation until ice or frost melts.
Dirty filtersRemove and clean filters.

NOTES:

  1. If a circuit breaker is tripped, fuse is blown or RESET button on cord or plug is tripped more than once, contact a qualified electrician.
  2. If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be installed and connected to the drain system.

Accessories

ACCESSORIES
ACCESSORYFORM NUMBERPART NUMBERDESCRIPTION
Wall Sleeves52S-48SIWALL-SLEEVE-1PKNon-Insulated Polymer Wall Sleeve, 1 per pack
52S-50SIWALL-SLEEVE-9PKNon-Insulated Polymer Wall Sleeve, 9 per pack
52S-49SISLEEVE-INSUL-1PKInsulated Polymer Wall Sleeve, 1 per pack
52C,P-26SISLEEVE-STEEL-1PKInsulated Metal Wall Sleeve, 1 per pack
52S-55SISLEEVE-EXT24-1PKExtended Metal Wall Sleeve for Deep Wall Applications (24 in. deep), 1 per pack
52S-65SISLEEVE-EXT26-1PKExtended Metal Wall Sleeve for Deep Wall Applications (26 in. deep), 1 per pack
52S-60SISLEEVE-EXT28-1PKExtended Metal Wall Sleeve for Deep Wall Applications (28 in. deep), 1 per pack
52S-59SISLEEVE-MOLDINGMolding kit to trim the wall sleeve to the wall
FR-SLEEVE-EXTFriedrich wall sleeve extension to retrofit Carrier PTAC unit into Friedrich 11½"deep (T Series) wall sleeve. 1 per pack
Exterior Grilles*GRILLE-ALU-STAMPStamped Aluminum Exterior Grille, Clear Finish
GRILLE-PLA-BROWNPolymer Architectural Rear Grille, Brown
GRILLE-PLA-BEIGEPolymer Architectural Rear Grille, Beige
GRILLE-ALU-CLEARAluminum Architectural Exterior Grille, Clear Finish
GRILLE-ALU-WHITEAluminum Architectural Exterior Grille, White
GRILLE-ALU-BRONZAluminum Architectural Exterior Grille, Light Bronze
GRILLE-ALU-MBRNZAluminum Architectural Exterior Grille, Medium Bronze
GRILLE-ALU-BROWNAluminum Architectural Exterior Grille, Brown (Dark Bronze)
GRILLE-ALU-BEIGEAluminum Architectural Exterior Grille, Beige
GRILLE-ALU-ALPINAluminum Architectural Exterior Grille, Alpine (matches Carrier Wall Sleeves)
GRILLE-ALU-PEACHAluminum Architectural Exterior Grille, Peach
GRILLE-ALU-MELONAluminum Architectural Exterior Grille, Melon
GRILLE-ALU-LGREYAluminum Architectural Exterior Grille, Light Grey
GRILLE-ALU-SGREYAluminum Architectural Exterior Grille, Slate Gray
GRILLE-ALU-RDBRKAluminum Architectural Exterior Grille, Red Brick
GRILLE-ALU-BLUEAluminum Architectural Exterior Grille, Blue
GRILLE-ALU-GREENAluminum Architectural Exterior Grille, Green
Subbase52C,P-31SIBAFFLE-KIT-1PKEnsures good air seal and prevents air recirculation when Carrier sleeve is used with a non-Carrier grille.
52C,P-1SISUBBASE-NON-ELECNon-electrical Subbase
52C,P-2SISUBBASE-230V-15AElectrical subbase with factory-installed 208/230V, 15 amp receptacle
SUBBASE-230V-20AElectrical subbase with factory-installed 208/230V, 20 amp receptacle
SUBBASE-230V-30AElectrical subbase with factory-installed 208/230V, 30 amp receptacle
52C,P-17SISUBBASE-265V-15AElectrical subbase with factory-installed 265V, 15 amp receptacle
SUBBASE-265V-20AElectrical subbase with factory-installed 265V, 20 amp receptacle
SUBBASE-265V-30AElectrical subbase with factory-installed 265V, 30 amp receptacle
52C,P-3SISUBBASE-HARDWIREElectrical subbase with factory-installed hardwire kit (230/208V and 265V)
Subbase Field-Installed Kits52C,P-4SISUBBASE-SWITCHField-Installable Switch kit for an electrical subbase
52C,P-5SISUBBASE-FUSE-15AField-Installed Fuse Kit (15 amp) for electrical subbase
SUBBASE-FUSE-20AField-Installed Fuse Kit (20 amp) for electrical subbase
SUBBASE-FUSE-30AField-Installed Fuse Kit (30 amp) for electrical subbase
Electrical Connections52C,P-11SIHARDWIRE-KIT-1PKPermanent power connection to the unit (includes 36" of flexible conduit and unit-mounted connector, 230/208V and 265V) 1 per pack
52C,P-19SICONDUIT-INTF-4PKInterface kit for field-supplied conduit to provide permanent power connection (230/208V and 265V) to the unit. Kit includes Molex connector for easy connect/disconnect. 4 per pack
Condensate Drain Kit52S-53SIDRAIN-KIT-4PKAttaches to wall sleeve for controlled internal or external disposal of condensate 4 per pack
Wall ThermostatsN/AHH01AD045Electro-mechanical Wall Thermostat (Heat/Cool and Heat Pump)
TSTATCCBPC01-BValue Series Electronic Thermostat w/Digital display (Heat/Cool Models)
TSTATCCBPH01-BValue Series Electronic Thermostat w/Digital display (Heat Pump Models)
TSTATCCPAC01-B7-Day Programmable Electronic Thermostat (Heat/Cool Models)
TSTATCCPHP01-B7-Day Programmable Electronic Thermostat (Heat Pump Models)
Wall Thermostat Interface Retrofit Kit52C,P-30SIRC-FIELDKIT230HCField-installed wall thermostat retrofit kit to convert a standard 230V Heat/Cool unit to an RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
RC-FIELDKIT230HPField-installed wall thermostat retrofit kit to convert a standard 230V Heat Pump unit to an RC unit. Wall thermostat sold separately.
RC-FIELDKIT265HCField-installed wall thermostat retrofit kit to convert a standard 265V Heat/Cool unit to an RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
RC-FIELDKIT265HPField-installed wall thermostat retrofit kit to convert a standard 265V Heat Pump unit to a RC unit. Wall thermostat sold separately.
52C,P-34SI2SPEED-TSTAT-KITField-installed automatic heat/cool changeover thermostat with 2-speed fan control at thermostat.
Replacement FiltersN/ATSTAT-COVER-6X7Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with non-programmable and electro-mechanical thermostats. Outside dimensions: 6½" x 7½" x 2¹⁵/₁₆". 1 per pack
TSTAT-COVER-7X10Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with programmable thermostats. Outside dimensions: 7¼" x 9¾" x 3³/₈". 1 per pack
52C,P-24SIAIR-FILTER-10PKReplacement air filters in package of 10
Energy Management52C,P-23SIEM-KITAllows unit to be turned on and off from a remote location (includes freeze guard protection)
Locking Security Control Door52C,P-25SISECURITY-DOORKey-locking security door to prevent access to heating and cooling controls
Lateral Duct Kit52C,P-25SILATERAL-DUCTDuctwork to allow one unit to heat and cool two rooms (plenum plus extension duct and registers)
Power Vent Retrofit Kit52C,P-32SIPWR-VENT-DOOR230Power vent with automatic door that opens and closes when the fan turns on and off (230V).
PWR-VENT-DOOR265Power vent with automatic door that opens and closes when the fan turns on and off (265V).
Air/Curtain Deflector52C,P-9SIDEFLECTOR-1PKLateral air deflector, with individually adjustable louvers, to enhance air circulation, 1 per pack
CURTDFL-52CP-1PKCurtain deflector for 52C and 52P models prevents curtains from blowing into discharge air stream. 1 per pack.
Touch-Up PaintN/ACARRIER-TOUCH-UPTouch up paint for repainting scratches or chips.

*Custom colors are also available.

Carrier Packaged Terminal Air Conditioner Warranty

This warranty provides coverage for the Carrier Packaged Terminal Air Conditioner.

Full One-Year Warranty

Carrier will repair or replace defective parts free of charge during the first year after purchase.

Full Extended Four-Year Warranty on Sealed Refrigeration System Only

During the second through fifth years after original purchase, Carrier will repair or replace the compressor, condenser, evaporator, or connecting tubing if defective.

Limited Extended Four-Year Warranty on Non-Sealed Refrigeration System Only

During the second through fifth years after original purchase, Carrier will repair or replace non-sealed system parts (motor, solenoid, etc.) if defective. This warranty excludes labor costs.

Limitation of Warranties

Implied warranties are limited to the duration of the express warranties. Express warranties are exclusive and cannot be altered by distributors or dealers.

Carrier Will Not Be Responsible For:

  • Cleaning required prior to warranty repair.
  • Standard maintenance failures.
  • Instruction on control and use after installation.
  • Faulty installation or application.
  • Failure to start due to electrical service issues.
  • Misapplication, abuse, unauthorized alteration, or improper servicing.
  • Damage from floods, winds, fires, lightning, accidents, or corrosive environments (except for units with corrosion protection, identified by a 'CP' suffix).
  • Replacement parts or repair services not supplied or designated by Carrier.
  • Products installed outside the continental U.S.A., Alaska, Hawaii, and Canada.
  • Shipping damage or damage during transport.
  • Special, indirect, or consequential damages.
  • Warranty coverage of accessory items (thermostats, sleeves, etc.).

NOTE: Service and maintenance items may be covered by a separate service agreement.

*Authorized independent dealers or service stations are registered with Carrier Air Conditioning.

This warranty grants specific legal rights, which may vary by state.

If Your Air Conditioner Does Not Work

Follow these steps in order:

  1. Check things you can do yourself: Ensure the unit is plugged in, check fuses/breakers, and reread the manual. This can save money by avoiding unnecessary service calls.
  2. Contact your dealer or recommended Carrier Authorized Service Center: They are equipped to handle most service problems.
  3. Contact the Carrier Distributor serving your area: Your dealer can provide contact information.
  4. Contact Carrier if a satisfactory solution is not reached: Carrier Air Conditioning, Consumer Relations Department, Carrier Parkway, P.O. Box 4808, Syracuse, New York 13221. Telephone: 1-800-894-6449.
Models: 52C Series, 52P Series, Packaged Terminal Air Conditioners and Heat Pumps

File Info : application/pdf, 18 Pages, 1.30MB

PDF preview unavailable. Download the PDF instead.

Manual-de-Usuario-52C-CP Goby Monitor Application version 3, 2, 1, 4

Related Documents

Preview Carrier PAD4, WPA4 Packaged Air Conditioner System Owner's Manual - Operation and Maintenance Guide
Owner's information manual for Carrier PAD4 and WPA4 packaged air conditioner systems. Covers safe operation, maintenance procedures, filter replacement, troubleshooting, and warranty information. Includes model specifications and dealer contact details.
Preview Carrier 50EZ-A and 50VT-A Heat Pump Owner's Information Manual
Owner's information manual for Carrier Comfort and Performance 13 and 14 SEER Single Packaged Heat Pump Systems (50EZ-A and 50VT-A) with Puron refrigerant. Covers operation, safety, maintenance, and troubleshooting.
Preview Carrier 40MK*B High-Wall Ductless Split System Owner's Manual
Comprehensive owner's manual for the Carrier 40MK*B High-Wall Ductless Split System, covering operation, maintenance, and troubleshooting for models sized 018 to 036.
Preview Carrier GH5S Single-Stage Heat Pump Product Data & Specifications
Comprehensive product data, features, specifications, and installation guidelines for the Carrier GH5S Single-Stage Heat Pump, designed with Puron® refrigerant for 1-1/2 to 5 tons applications.
Preview Carrier PH5ZNB 13.4 SEER2 Single-Packaged Heat Pump System Owner's Manual
Comprehensive owner's information manual for the Carrier PH5ZNB 13.4 SEER2 single-packaged heat pump system with R-454B refrigerant. Includes safety, operation, maintenance, and troubleshooting guides.
Preview Carrier 40MAQ High Wall Ductless System Owner's Manual
Owner's manual for the Carrier 40MAQ High Wall Ductless System, covering safety, general information, part names, remote control operation, cleaning, maintenance, and troubleshooting.
Preview Carrier PHR5 15+ SEER2 Packaged Heat Pump Installation Guide
Comprehensive installation instructions for the Carrier PHR5 15+ SEER2 2-Stage Packaged Heat Pump System, covering single and three-phase units from 2-5 nominal tons with R-410A refrigerant. Includes safety, receiving, installation, wiring, and maintenance procedures.
Preview Carrier 45MUAAQ Crossover Air Handler Owner's Manual
Comprehensive owner's manual for the Carrier 45MUAAQ Crossover Air Handler (18K-60K). Provides detailed information on installation, operation, maintenance, safety, troubleshooting, and error codes for this HVAC system.