Specification KSID012-H115Q KSID016-H214Q KSID022-H215Q KSID032-H214Q
Power supply 115 / 1 / 60 208-230 / 1 / 60 208-230 / 1 / 60 208-230 / 1 / 60
Nominal Cooling Capacity 12000 Btu/h 16500 Btu/h 21000 Btu/h 32000 Btu/h
Cooling Frequency Range 32 - 76 Hz 29 - 87 Hz 30 - 87 Hz 30 - 87 Hz
Nominal Cooling Inverter Capacity Range 6390-14870 Btu/h 7975-21200 Btu/h 10800-30900 Btu/h 15835-43400 Btu/h
Cooling Input 1400 W 1940 W 2460 W 4000 W
Cooling Rated current 12,4 A 8,6 A 11,1 A 17,8 A
Cooling SEER 15 Btu/w 14 Btu/w 14,5 Btu/w 14 Btu/w
Nominal Heating Capacity 11500 Btu/h 18000 Btu/h 21000 Btu/h 33000 Btu/h
Heating Frequency Range 32 - 76 Hz 29 - 87 Hz 30 - 87 Hz 30 - 87 Hz
Nominal Heating Inverter Capacity Range 6130-14460 Btu/h 8700-26100 Btu/h 10500-30450 Btu/h 16500-47850 Btu/h
Heating Input 1340 W 1700 W 2210 W 3470 W
Heating Rated current 11,9 A 7,6 A 10 A 15,5 A
Heating HSPF 8,2 Btu/w 8,2 Btu/w 8,2 Btu/w 8,2 Btu/w
Minimum Circuit Ampacity 16 A 12 A 15 A 20 A
Max. Overcurrent Protection 25 A 20 A 25 A 30 A
Moisture Removal 40,6 oz/h 54,1 oz/h 74,4 oz/h 115 oz/h
Compressor Type Rotary Rotary Twin-rotary Twin-rotary
Compressor Capacity 11021 Btu/h 13443 Btu/h 15286 Btu/h 33711 Btu/h
Compressor Input 855 W 1005 W 1150 W 3010 W
Compressor Rated current (RLA) 5,5 A 6,87 A 6,87 A 13,5 A
Compressor Refrigerant oil / oil charge ESTER OIL VG74 / 16.2 oz ESTER OIL VG74 / 16.2 oz ESTER OIL VG74 / 16.9 oz FV50S / 36.2 oz
Indoor fan motor Input 46 W 58,5 W 80,5 W 113 W
Indoor fan motor RLA 0,4 A 0,28 A 0,38 A 0,78 A
Indoor fan motor LRA 0,54 A 0,356 A 0,56 A 0,8 A
Indoor fan motor Winding Resistance 75/150 Ω 183.6/206 Ω 118.5/78.5 Ω 81/75.5 Ω
Indoor fan motor Capacitor 3 uF 1,5 uF 3 uF 3 uF
Indoor fan motor Speed (Hi/Mi/Lo) 1200 / 1050 / 800 rpm 1250 / 1100 / 800 rpm 1200 / 1100 / 900 rpm 1260 / 1090 / 950 rpm
Indoor air flow (Hi/Mi/Lo) 350/310/240 cfm 480/420/310 cfm 680/620/510 cfm 940/810/710 cfm
Indoor noise level (Hi/Mi/Lo) 40/36/29 dB(A) 44/41/31 dB(A) 48/45/37 dB(A) 50/46/44 dB(A)
Indoor unit Dimension (W*D*H) 30.31x7.40x10.04 in 35.63x7.80x10.83 in 40.55x8.58x12.40 in 56.89x10.91x13.39 in
Indoor unit Packing (W*D*H) 32.87x10.43x12.99 in 38.19x10.63x13.58 in 43.90x15.55x11.81 in 60.24x16.54x14.37 in
Indoor unit Net / Gross weight 16.53/20.94 lb 19.84/25.35 lb 26.46/33.07 lb 52.91/70.55 lb
Outdoor unit Input 64/47 W 119/96 W 136/130 W 299/223 W
Outdoor unit RLA 0,7 A 0,55 A 0,6 A 1,36 A
Outdoor fan motor LRA 0,81 A 0,8 A 0,9 A 2 A
Outdoor fan motor Capacitor 3 uF 2,5 uF 2,5 uF 10 uF
Outdoor fan motor Speed 860 / -- / 660 rpm 860 / -- / 680 rpm 930 / -- / 830 rpm 750 / -- / 615 rpm
Outdoor air flow 820 cfm 1290 cfm 1590 cfm 2240 cfm
Outdoor noise level 55 dB(A) 59 dB(A) 61 dB(A) 61 dB(A)
Outdoor unit Dimension (W*D*H) 26.0x10.4x21.3 in 29.9x11.2x23.2 in 33.3x12.6x27.6 in 39.0x13.6x38.0 in
Outdoor unit Packing (W*D*H) 31.1x14.0x24.4 in 34.9x14.0x25.4 in 38.0x15.6x29.7 in 44.1x17.1x43.3 in
Outdoor unit Net/Gross weight 66.1/70.6 lb 82.7/88.2 lb 103.6/111.3 lb 167.6/191.8 lb
Refrigerant type / charge R410A / 33.6 oz R410A / 42.3 oz R410A / 56.5 oz R410A / 107.8 oz
Refrigerant precharge 16 ft 16 ft 16 ft 16 ft
Design pressure 550 / 340 psig 550 / 340 psig 550 / 340 psig 550 / 340 psig
Pre-Charged Refrigerant Line Set 16 ft Quick Connect 16 ft Quick Connect 16 ft Quick Connect 16 ft Quick Connect
Connection wiring 16AWG*4 Stranded, unshielded 16AWG*4 Stranded, unshielded 16AWG*4 Stranded, unshielded 16AWG*4 Stranded, unshielded
Thermostat type Remote Control Remote Control Remote Control Remote Control
Operation Indoor (cooling/ heating) 62 ~ 90°F / 32 ~ 86°F 62 ~ 90°F / 32 ~ 86°F 62 ~ 90°F / 32 ~ 86°F 62 ~ 90°F / 32 ~ 86°F
Temperature Outdoor (cooling/heating) 32 ~ 122°F / 5 ~ 86°F 32 ~ 122°F / 5 ~ 86°F 32 ~ 122°F / 5 ~ 86°F 32 ~ 122°F / 5 ~ 86°F
Application area 425-550 sq ft 575-800 sq ft 827-1200 sq ft 1300-1600 sq ft

Continued product improvement is our goal at Klimaire Products, Inc. Hence, specifications and data listed herein are subject to change without notice and without obligation on our part. Allways comply with local, state, and national electrical codes.

A diagram shows an indoor air conditioning unit, a rectangular unit with a front panel, indicating dimensions for Width (W), Depth (D), and Height (H).
A diagram shows an outdoor air conditioning unit, a rectangular unit with a fan grille on top, indicating dimensions for Width (W), Depth (D), and Height (H).

PDF preview unavailable. Download the PDF instead.

ksidspecs 1 Corel PDF Engine Version 15.2.0.686 CorelDRAW X5

Related Documents

Preview Klimaire KSIV Series Ductless Mini-Split Systems: High Efficiency, Comfort & Savings
Discover the Klimaire KSIV Series ductless mini-split air conditioners and heat pumps. Featuring up to 19 SEER efficiency, DC inverter technology, quiet operation, and advanced comfort features for residential and commercial applications. Learn about energy savings, installation, and control options.
Preview Klimaire KIWU/KOIU Series Split-Type Room Air Conditioner User Manual
User manual for the Klimaire KIWU/KOIU Series split-type room air conditioner. Contains safety guidelines, remote control operation, and usage instructions for optimal performance.
Preview Klimaire KIWU/KOIU Series Split-Type Room Air Conditioner User's Manual
This user manual provides comprehensive instructions for the Klimaire KIWU/KOIU Series Split-Type Room Air Conditioner, covering safety precautions, remote control operation, various modes, and essential operating procedures.
Preview Klimaire KSIV Series Ductless Mini-Split Comfort Systems
Explore the Klimaire KSIV Series of ductless mini-split comfort systems, offering high SEER efficiency, advanced DC inverter technology, and personalized climate control for residential use. Learn about features like quiet operation, energy savings, air filtration, and smart control options.
Preview Klimaire KIWQ/KOIQ Series Split-Type Room Air Conditioner Installation Manual
Comprehensive installation manual for Klimaire KIWQ/KOIQ series split-type room air conditioners, covering safety precautions, refrigerant handling, installation procedures, and testing.
Preview Klimaire KIWQ KOIQ Series WiFi Function User's Manual
Comprehensive user manual for the Klimaire KIWQ KOIQ Series Split-Type Room Air Conditioner, detailing WiFi function setup, app control, device management, and troubleshooting.
Preview KIWU/KOIU Series Split-Type Room Air Conditioner Wi-Fi Function User's Manual
This user's manual provides instructions for using the Wi-Fi function of the KIWU/KOIU Series Split-Type Room Air Conditioner. It covers app download and installation, account registration, device setup, and control operations.
Preview KLIMAIRE KSIE Series Split-Type Room Air Conditioner: Owner's Manual & Installation Guide
Comprehensive guide for KLIMAIRE KSIE Series Split-Type Room Air Conditioners, covering safety precautions, operation, installation, maintenance, troubleshooting, and specifications.