Qoltec Hybrid Solar Inverter Off-Grid

Models: 53863, 53864

Introduction

Thank you for choosing the Qoltec solar inverter. This manual will guide you through the setup, operation, and troubleshooting of your device. Please read it carefully before installation and operation.

About This Manual

This manual provides instructions for assembly, installation, operation, and troubleshooting. Keep it for future reference. It includes safety guidelines, installation information, and details on tools and wiring.

Product Overview

This is a multifunctional inverter combining inverter, solar charger, and battery charger functions for uninterrupted power supply. The LCD display offers user-friendly controls for battery charging current, AC/solar charging priority, and input voltage settings.

Figure 1: Unit Components

Installation

I. Preparation

Inspect the unit for any damage before installation. Ensure all components are present: solar inverter and user manual.

Remove the bottom cover by unscrewing the three screws before connecting wires.

II. Unit Installation

Consider the following when selecting an installation location:

NOTE: Suitable for mounting ONLY on concrete or other non-combustible surfaces.

Mount the unit using M4 or M5 screws.

III. Battery Connection

NOTE: A separate DC disconnect device is required for safe operation and regulatory compliance. Refer to the table for appropriate fuse or breaker sizing.

Insulation Length:

WARNING: All wiring must be performed by qualified personnel.

Use the correct cable for battery connection to ensure system safety and efficiency. Follow recommended stripping lengths (L1, L2).

Figure 5: Recommended Cable Stripping Lengths

Model Max. Amperage Battery Capacity Cable Size Cable Cross-section (mm²) L1 (mm) L2 (mm) Nominal Torque
1500W-24 70A 100AH 6AWG 13.3 3 18 2~3 Nm
2500W-24 100A 100AH 4AWG 21.15 3 18 2~3 Nm
Other models 140A 100AH 2AWG 38 3 18 2~3 Nm

Battery Connection Steps:

  1. Strip 18mm of insulation from positive and negative wires.
  2. Connect battery packs according to unit requirements. Use recommended battery capacity.
  3. Slide the battery cable into the inverter's battery connector and tighten screws to 2-3 Nm. Ensure correct polarity (+ to + and - to -) for both battery and inverter/charger.

WARNING: Risk of electric shock. Installation requires caution due to high battery voltage.

ATTENTION: Do not place anything between the inverter terminal's flat part. Do not apply antioxidant to terminals before connection.

NOTE: Ensure correct polarity (+ to + and - to -) before final DC connection.

IV. AC Input/Output Connection

NOTE: Install a separate AC switch between the inverter and the AC power source for safe disconnection during maintenance and overcurrent protection. A 50A breaker is recommended.

NOTE: Terminal blocks are marked "IN" and "OUT". Do not confuse them.

WARNING: All wiring must be performed by qualified personnel.

Use the correct cable size for AC connection.

Model Cross-sectional Area Torque Value
1.5KVA 12AWG 1.4~1.6Nm
2.5KVA/3.5KVA 10AWG 1.4~1.6Nm
5.5KVA 8 AWG 1.4~1.6Nm

AC Input/Output Connection Steps:

  1. Ensure the DC breaker is open before making AC connections.
  2. Strip 10mm of insulation from six wires. Shorten the phase (L) and neutral (N) wires by 3mm.
  3. Insert AC input wires according to terminal block polarity. Connect the PE (ground) wire first (yellow-green), then L (brown), then N (blue).
  4. Connect AC output wires similarly, ensuring PE is connected first.
  5. Verify all wires are correctly connected.

V. PV Connection

NOTE: Install a DC breaker between the inverter and PV modules before connecting.

WARNING: All wiring must be performed by qualified personnel.

Use the correct cable size for PV connection.

Model Typical Amperage Cable Size Torque
1.5KVA 15A 12 AWG 1.4~1.6 Nm
2.5KVA 15A 12 AWG 1.4~1.6 Nm
3.5KVA 15A 12 AWG 1.4~1.6 Nm
5.5KVA 18A 12 AWG 1.4~1.6 Nm
6.2KVA 27A 12 AWG 1.4~1.6 Nm

PV Module Selection: Consider the following parameters:

  1. PV module open-circuit voltage (Voc) must not exceed the inverter's maximum open-circuit voltage.
  2. PV module open-circuit voltage (Voc) must be higher than the minimum battery voltage.

Solar Charging Mode

MODEL INVERTER 1.5KW-3.5KW 5.5KVA
Max. PV Array Open Circuit Voltage 500VDC 500VDC
PV Array MPPT Voltage Range 30VDC~500VDC 60VDC~500VDC
Max. PV INPUT CURRENT 15A 18A

Example configurations for 450 Wp and 550 Wp PV modules:

Solar Input Specifications (450Wp reference) Number of Panels Total Input Power Model
1 in series 1 450W 1.5KW-5.5KW
2 units in series 2 900 W
3 units in series 3 1,350 W
4 units in series 4 1,800 W
5 units in series 5 2,250 W
6 units in series 6 2,700 W
7 units in series 7 3,150 W 2.5KW-5.5KW
8 units in series 8 3,600 W
9 units in series 9 4,050 W
- Vmp: 34.67Vdc 3.5KW-5.5KW
- Imp: 13.82A
- Voc: 41.25Vdc
Solar Input Specifications (550Wp reference) Number of Panels Total Input Power Model
- Isc: 12.98A 10 units in series 10 4,500 W 5.5KVA
11 units in series 11 4,950 W
12 units in series 12 5,400 W
6 units in series and 2 units in parallel 12 5,400 W 1.5KW-5.5KW
SOLAR INPUT Number of panels Total input power Model
1 in series 1 550W 1.5KW-5.5KW
2 units in series 2 900 W 1.5KVA-5.5KW
3 units in series 3 1,650 W 2.5KVA-5.5KW
- Vmp: 42.48Vdc 4 units in series 4 2,200 W 3.5KW-5.5KW
- Imp: 12.95A 5 units in series 5 2,750 W 5.5KW
- Voc: 50.32Vdc 6 units in series 6 3,300 W
- Isc: 13.70A 7 units in series 7 3,850 W
8 units in series 8 4,400 W
9 units in series 9 4,950 W
4 sets in series and 2 sets in parallel 8 4,400 W
5 sets in series and 2 sets in parallel 10 5,500 W

PV Module Connection: Follow these steps:

  1. Strip 10mm insulation from positive and negative cables.
  2. Verify correct polarity of connection cables and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).

VI. Final Assembly

Once all wires are connected, replace the bottom cover and secure it with the screws.

Operation

I. Power On/Off

After correct installation and battery connection, press the On/Off switch to power on the unit.

II. Operation Panel and Display

The operation panel is located on the front of the inverter and includes indicators, function buttons, and an LCD display showing operating status, input/output information, and power source details.

Figure 13: LED Indicators and Messages

Indicator LED Color Status Message
AC/INV Green Solid Output is powered directly from the grid (Line Mode).
Blinking Output is powered by the battery or PV in battery mode.
CHG Green Solid Battery is fully charged.
Blinking Battery is charging.
DEFECT Red Solid An error has occurred in the inverter.
Blinking A warning exists in the inverter.

III. LCD Display Settings

Press and hold the ENTER button for 3 seconds to enter setting mode. Use UP/DOWN buttons to select programs and ENTER to confirm or ESC to exit.

Program Settings

Program Description Selection Options
01 Output Source Priority: Configure charging source priority.
  • Grid Priority: Power is supplied primarily to consumers. Solar and battery power are used only when grid power is unavailable.
  • Solar Priority: Solar energy supplies consumers first. If solar energy is insufficient, battery energy supplements. Grid power is used only when solar energy is unavailable or battery voltage is low.
  • SBU Priority: Solar energy supplies consumers first. Battery energy supplements if solar is insufficient. Grid power is used when battery voltage drops to a warning level.
  • SUB Priority: Solar energy is charged first, then consumers are supplied. If solar is insufficient, grid power supplements consumers.
  • SUF Priority: Solar energy supplies consumers and charges the battery if sufficient. If insufficient, grid power supplements consumers.
02 Maximum Charging Current: Configure total charging current for solar and grid chargers. 60A (default). The charging current range is from the AC source current up to the specified maximum charging current.
03 Input Voltage Range:
  • Devices (default): 90-280 VAC
  • UPS: 170-280 VAC
  • Generator: 170-280 VAC (may be unstable due to generator fluctuations)
05 Battery Type:
  • AGM (default)
  • Flooded
  • User Defined: Allows setting battery charging voltage and low DC cutoff voltage (Programs 26, 27, 29).
  • Lithium battery without communication: Use "LIB" setting. Default values are suitable. Charging and low voltage cutoff can be set (Programs 26, 27, 29).
06 Automatic Restart after Overload: Disable Automatic Restart (default) / Enable Automatic Restart.
07 Automatic Restart after Over-temperature: Disable Automatic Restart / Enable Automatic Restart (default).
08 Output Voltage: 220V / 230V (default) / 240V.
09 Output Frequency: 50Hz (default) / 60Hz.
10 Bypass: Manual (default) / Auto. In Auto mode, the system switches to bypass if the grid supply is correct, even if the switch is off.
11 Current: 30A (default).
12 Grid Source Voltage Setting: Used for "SBU" or "Solar first" priority (Program 01). Settings depend on the model (12V, 24V, 48V). Max setting must be lower than Program 13 value.
13 Battery Full Charge Voltage Setting: Used for "SBU" or "Solar first" priority (Program 01). Settings depend on the model (12V, 24V, 48V). Max setting must be higher than Program 12 value.
16 Charging Source Priority: For configuring charging source priority.
  • Solar Energy (default): Solar priority for battery charging. Grid charges only if solar is unavailable.
  • Solar and Grid Simultaneously: Both solar and grid charge the battery.
  • Solar Only: Solar is the sole charging source, regardless of grid availability. For battery mode, solar is the only source.
18 Buzzer Mode:
  • Mode 1: Buzzer activates on power source change, warning, or specific fault.
  • Mode 2: Buzzer activates on warning or specific fault.
  • Mode 3: Buzzer activates on fault.
  • Mode 4 (default): Buzzer is off.
19 Return to Default Display: Return to Default Display (default) / Stay on Last Screen.
20 Backlight Control: Backlight On (default) / Backlight Off.
23 Overload Bypass: When activated, the unit switches to grid power if overloaded in battery mode. Bypass Disabled / Bypass Enabled (default).
25 Modbus ID Setting: Modbus ID: 001 (default) ~ 247.
26 Charging Buffer Voltage (CV): User Defined setting. Value must be >= Program 27. Increments of 0.1V. Settings vary by model (12V, 24V, 48V).
27 Float Charging Voltage: User Defined setting. Settings vary by model (12V, 24V, 48V).
29 Low DC Disconnect Voltage: User Defined setting. Value must be < Program 12. Increments of 0.1V. Settings vary by model (12V, 24V, 48V).
32 Charging Time (CV stage): Automatic (default) / 5 min / 900 min. If "USE" selected in Program 05, this can be set.
33 Battery Equalization: Battery Equalization / Battery Equalization Disabled (default).
34 Battery Voltage Equalization: Settings depend on model (12V, 24V, 48V).
35 Battery Equalization Time: 60 min (default) / 0 to 900 minutes.
36 Battery Equalization Time: 120 min (default) / 0 to 900 minutes.
37 Equalization Interval: 30 days (default) / 1 to 90 days.
39 Immediate Equalization: Enabled / Disabled (default). If enabled, "E9" appears on LCD. If disabled, equalization is cancelled until next scheduled interval.
41 Automatic Activation for Lithium Battery: If "LIx" is selected (Program 05) and battery is not detected, unit activates lithium battery at specified time. Requires unit restart. Disabled Automatic Activation (default).
42 Manual Activation for Lithium Battery: If "LIx" is selected (Program 05) and battery is not detected, manual activation is possible. This function is only available on models supporting lithium battery activation. Implicit: Manual Activation Disabled.
46 Maximum Discharge Current: Reserved setting (not available for use). Implicit OFF / Current Discharge Disabled / Protection Function. Available in single model. Network power enables grid mode, stopping discharge if set current is exceeded. If network power is unavailable, warning appears, and discharge continues. Setting range: 20A to 500A.

Battery Equalization

The charge controller includes a battery equalization function to eliminate negative chemical effects like stratification and sulfate crystal buildup, which can reduce battery capacity. Periodic equalization is recommended.

How to Apply Equalization:

  1. Activate equalization in LCD settings (Program 33).
  2. Apply via:
    • Set equalization interval in Program 37.
    • Activate immediate equalization in Program 39.

When to Perform Equalization:

The controller enters equalization mode when the set time interval is reached or immediate equalization is activated.

Equalization Charging Time and Limit:

During equalization, the controller provides maximum power until the battery reaches the set equalization voltage. A constant voltage charge maintains this voltage. The battery remains in equalization until the set time is reached. If the set time passes and the voltage is still below the equalization voltage, the equalization time is extended. If the voltage remains low after the extended time, equalization ends, and the unit returns to maintenance mode.

Lithium Battery Settings

Settings for Lithium Battery without Communication

To avoid BMS protection triggers when there's no communication between the BMS and the unit:

  1. Obtain BMS specifications (Max Charge Voltage, Max Charge Current, Discharge Protection Voltage).
  2. Set Battery Type to "LIB".
  3. Set CV (Charge Voltage) to BMS Max Charge Voltage minus 0.5V.

Troubleshooting

Problem: Unit shuts down during startup.

Possible Cause: Battery voltage too low.

Solution: Charge the battery. Replace the battery.

Problem: No response after startup.

Possible Cause: Battery voltage too low, incorrect battery polarity.

Solution: Charge the battery. Check battery and cable connections. Replace battery pack.

Problem: Power is available, but the unit operates in battery mode.

Possible Cause: Input voltage displayed as 0 on LCD, green LED blinking (indicating poor AC quality or activated protection).

Solution: Check if the AC breaker is off and AC wiring is correct. Check AC cable thickness and length. Verify generator operation and input voltage settings.

Problem: Unit powers on, internal relay repeatedly starts and stops.

Possible Cause: Battery is disconnected.

Solution: Set "Solar First" as output source priority. Check battery cable connections.

Problem: Buzzer sounds continuously, red LED is on.

Possible Cause: Error code 07 (Overload), 05 (Short circuit), 02 (Internal temperature >100°C), 03 (Battery overcharged), 06/22 (Invalid output voltage), 08/09/15 (Component failure), 13 (Overcurrent/overvoltage), 14 (Low bus voltage).

Solution: Reduce load. Check wiring and remove abnormal loads. Ensure ventilation. Contact service center.

Specifications

Table 1: Line Mode Specifications

Model 1.5KV A 1.5KV A 2.5KV A 3.5KV A 5.5KVA
Input Voltage Waveform Sinusoidal (grid or generator)
Nominal Input Voltage 230V AC
Reduced Loss Voltage 170V AC ±7V (UPS)
90V AC ±7V (appliances)
Reduced Loss Voltage 180V AC ±7V (UPS)
100V AC ±7V (appliances)
High Loss Voltage 280V AC ±7V
High Loss Return Voltage 270V AC ±7V
Max. AC Input Voltage 300V C.A.
Nominal Input Frequency 50Hz / 60Hz (auto-detect)
Reduced Loss Frequency 40 ±1Hz
High Loss Return Frequency 42 ±1Hz
High Loss Frequency 65 ±1Hz
High Loss Return Frequency 63 ±1Hz
Output Short Circuit Protection Battery Mode: Electronic circuits
Efficiency (Linear Mode) >95% (nominal R load, fully charged battery)
Switching Time 10 ms typical (UPS)
20 ms typical (appliances)
Output Power Limitation: When AC input voltage drops to 95V or 170V, output power will be limited.

Table 2: Inverter Mode Specifications

Model Inverter 1.5KVA/1.5KW 1.5KVA 2.5KVA/2.5KW 3.5KVA/3.5KW 5.5KVA/5.5KW
Rated Output Power 1.5KVA 1.5KVA 2.5KVA 3.5KVA 5.5KVA
Input Voltage Waveform Sine
Output Voltage Regulation 230Vac±5%
Output Frequency 50Hz or 60Hz
Max. Efficiency 94%
Peak Capacity 2* rated power for 5 seconds
Nominal DC Input Voltage 12Vdc 24Vdc 48Vdc
Cold Start Voltage 11.0Vdc 23.0Vdc 46.0Vdc
Low Voltage Warning (CC) 11.0Vdc
10.7Vdc
10.1Vdc
22.0Vdc
21.4 Vcc
20.2Vdc
40.4Vdc
42.8Vdc
44.0Vdc
Low Voltage Recovery (Continuous Current) 11.5Vdc
11.2Vdc
10.6Vdc
23.0Vdc
22,4 Vcc
21.2Vdc
42.4Vdc
44.8Vdc
46.0Vdc
Low Voltage Disconnect 10.5Vdc
10.2Vdc
9.6Vdc
21.0Vdc
20.4Vdc
19.2Vdc
42.0Vdc
40.8Vdc
38,4Vdc

Table 3: Charger Mode Specifications

Model 1.5KVA 1.5KVA 2.5KVA 3.5KVA 5.5KVA
Utility Charging Current (PV+AC) (@ VI/P=230Vac) 100Amp 60Amp 100Amp 100Amp 100Amp
AC Charging Current (@ VI/P=230Vac) 60Amp
Charging Voltage (Bulk) 14.6 Vcc (Flooded)
14.1Vdc (AGM/GEL)
29,2 VCC
28.2VDC
58.4VDC
56.4VDC
Continuous Charging Voltage 13.5Vdc 27VDC 54VDC
Overcharge Protection 16.5Vdc 32VDC 63VDC
Charging Algorithm 3 stages
Charging Curve Figure 89
Solar Input
Model 1.5KVA 1.5KVA 2.5KVA 3.5KVA 5.5KVA
Rated Power 2000W 2000W 3000W 4000W 5500W
Max PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 30Vdc~500Vdc 60Vdc~500Vdc
Max Input Current 15A 15A 15A 15A 18A
Charging Current (PV) 100A 60A 100A 100A 100A

Table 4: General Specifications

Model 1.5KV A 2.5KV A 3.5KV A 5.5KVA
Operating Temperature Range -10°C to 55°C
Storage Temperature -15°C~60°C
Humidity 5% to 95% (non-condensing)

Maintenance

  1. Keep the VALVATOR clean with a soft, dry cloth. Do not use chemicals.
  2. Regularly inspect power cables and connectors for damage (abrasions, cracks, loose connections).
  3. Ensure ventilation openings are clean and unobstructed for proper cooling.
  4. Avoid contact with water or other liquids to prevent electrical damage.

Disposal

This product is subject to WEEE regulations. Dispose of it at an authorized electrical waste collection point for safe recycling. Contact the manufacturer or an authorized service center for disposal inquiries.

Warranty and Service Information

The product is covered by a 24-month manufacturer's warranty from the date of purchase, covering defects in materials and workmanship. Contact the service department for assistance. The warranty does not cover damage from improper use, drops, mechanical damage, unauthorized repairs, or disassembly attempts.

PDF preview unavailable. Download the PDF instead.

ro-53863-53864-instrukcja-obslugi-pl pypdf

Related Documents

Preview Qoltec Hybrid Solar Inverter User Manual
Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, troubleshooting, and technical specifications. Includes model numbers 53863 and 53864.
Preview Qoltec Off-Grid Hybrid Solar Inverter User Manual
Comprehensive user manual for the Qoltec Off-Grid Hybrid Solar Inverter, covering installation, operation, technical specifications, troubleshooting, and maintenance for models 53863 and 53864.
Preview Руководство по эксплуатации гибридного солнечного инвертора Qoltec Off-Grid
Подробное руководство по установке, эксплуатации и устранению неполадок гибридного солнечного инвертора Qoltec Off-Grid. Включает информацию о подключении батарей, входов/выходов переменного тока и фотоэлектрических модулей.
Preview Qoltec Hybrid Off-Grid Solar Inverter User Manual
Comprehensive user manual for the Qoltec Hybrid Off-Grid Solar Inverter (models 53863, 53864), covering installation, operation, troubleshooting, and specifications.
Preview Qoltec Hybrid Solar Inverter Off-Grid User Manual
Comprehensive user manual for the Qoltec Hybrid Solar Inverter Off-Grid, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864.
Preview Qoltec Hybrid Solar Inverter User Manual
Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, maintenance, and troubleshooting for models 53863 and 53864.
Preview Qoltec Hybrid Solar Inverter Off-Grid User Manual
User manual for the Qoltec Hybrid Solar Inverter Off-Grid, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864.
Preview Qoltec Hybrid Solar Inverter User Manual
Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864.