Qoltec Hybrid Solar Inverter Off-Grid
Models: 53863, 53864
Introduction
Thank you for choosing the Qoltec solar inverter. This manual will guide you through the setup, operation, and troubleshooting of your device. Please read it carefully before installation and operation.
About This Manual
This manual provides instructions for assembly, installation, operation, and troubleshooting. Keep it for future reference. It includes safety guidelines, installation information, and details on tools and wiring.
Product Overview
This is a multifunctional inverter combining inverter, solar charger, and battery charger functions for uninterrupted power supply. The LCD display offers user-friendly controls for battery charging current, AC/solar charging priority, and input voltage settings.
Figure 1: Unit Components
- 1. LCD Display
- 2. Status Indicator
- 3. Charging Indicator
- 4. Error Indicator
- 5. Function Button
- 6. Grounding Terminal
- 7. AC Input
- 8. AC Output
- 9. Battery Input
- 10. PV Input
- 11. Wi-Fi Communication Port
- 12. On/Off Switch
Installation
I. Preparation
Inspect the unit for any damage before installation. Ensure all components are present: solar inverter and user manual.
Remove the bottom cover by unscrewing the three screws before connecting wires.
II. Unit Installation
Consider the following when selecting an installation location:
- Do not mount on flammable materials.
- Mount on a solid surface.
- Install at eye level for optimal LCD visibility.
- Optimal ambient temperature: 0°C to 55°C.
- Recommended mounting position: Vertical, against a wall.
- Ensure adequate space around the unit for heat dissipation and cable removal.
NOTE: Suitable for mounting ONLY on concrete or other non-combustible surfaces.
Mount the unit using M4 or M5 screws.
III. Battery Connection
NOTE: A separate DC disconnect device is required for safe operation and regulatory compliance. Refer to the table for appropriate fuse or breaker sizing.
Insulation Length:
WARNING: All wiring must be performed by qualified personnel.
Use the correct cable for battery connection to ensure system safety and efficiency. Follow recommended stripping lengths (L1, L2).
Figure 5: Recommended Cable Stripping Lengths
Model | Max. Amperage | Battery Capacity | Cable Size | Cable Cross-section (mm²) | L1 (mm) | L2 (mm) | Nominal Torque |
---|---|---|---|---|---|---|---|
1500W-24 | 70A | 100AH | 6AWG | 13.3 | 3 | 18 | 2~3 Nm |
2500W-24 | 100A | 100AH | 4AWG | 21.15 | 3 | 18 | 2~3 Nm |
Other models | 140A | 100AH | 2AWG | 38 | 3 | 18 | 2~3 Nm |
Battery Connection Steps:
- Strip 18mm of insulation from positive and negative wires.
- Connect battery packs according to unit requirements. Use recommended battery capacity.
- Slide the battery cable into the inverter's battery connector and tighten screws to 2-3 Nm. Ensure correct polarity (+ to + and - to -) for both battery and inverter/charger.
WARNING: Risk of electric shock. Installation requires caution due to high battery voltage.
ATTENTION: Do not place anything between the inverter terminal's flat part. Do not apply antioxidant to terminals before connection.
NOTE: Ensure correct polarity (+ to + and - to -) before final DC connection.
IV. AC Input/Output Connection
NOTE: Install a separate AC switch between the inverter and the AC power source for safe disconnection during maintenance and overcurrent protection. A 50A breaker is recommended.
NOTE: Terminal blocks are marked "IN" and "OUT". Do not confuse them.
WARNING: All wiring must be performed by qualified personnel.
Use the correct cable size for AC connection.
Model | Cross-sectional Area | Torque Value |
---|---|---|
1.5KVA | 12AWG | 1.4~1.6Nm |
2.5KVA/3.5KVA | 10AWG | 1.4~1.6Nm |
5.5KVA | 8 AWG | 1.4~1.6Nm |
AC Input/Output Connection Steps:
- Ensure the DC breaker is open before making AC connections.
- Strip 10mm of insulation from six wires. Shorten the phase (L) and neutral (N) wires by 3mm.
- Insert AC input wires according to terminal block polarity. Connect the PE (ground) wire first (yellow-green), then L (brown), then N (blue).
- Connect AC output wires similarly, ensuring PE is connected first.
- Verify all wires are correctly connected.
V. PV Connection
NOTE: Install a DC breaker between the inverter and PV modules before connecting.
WARNING: All wiring must be performed by qualified personnel.
Use the correct cable size for PV connection.
Model | Typical Amperage | Cable Size | Torque |
---|---|---|---|
1.5KVA | 15A | 12 AWG | 1.4~1.6 Nm |
2.5KVA | 15A | 12 AWG | 1.4~1.6 Nm |
3.5KVA | 15A | 12 AWG | 1.4~1.6 Nm |
5.5KVA | 18A | 12 AWG | 1.4~1.6 Nm |
6.2KVA | 27A | 12 AWG | 1.4~1.6 Nm |
PV Module Selection: Consider the following parameters:
- PV module open-circuit voltage (Voc) must not exceed the inverter's maximum open-circuit voltage.
- PV module open-circuit voltage (Voc) must be higher than the minimum battery voltage.
Solar Charging Mode
MODEL INVERTER | 1.5KW-3.5KW | 5.5KVA |
---|---|---|
Max. PV Array Open Circuit Voltage | 500VDC | 500VDC |
PV Array MPPT Voltage Range | 30VDC~500VDC | 60VDC~500VDC |
Max. PV INPUT CURRENT | 15A | 18A |
Example configurations for 450 Wp and 550 Wp PV modules:
Solar Input Specifications (450Wp reference) | Number of Panels | Total Input Power | Model |
---|---|---|---|
1 in series | 1 | 450W | 1.5KW-5.5KW |
2 units in series | 2 | 900 W | |
3 units in series | 3 | 1,350 W | |
4 units in series | 4 | 1,800 W | |
5 units in series | 5 | 2,250 W | |
6 units in series | 6 | 2,700 W | |
7 units in series | 7 | 3,150 W | 2.5KW-5.5KW |
8 units in series | 8 | 3,600 W | |
9 units in series | 9 | 4,050 W | |
- Vmp: 34.67Vdc | 3.5KW-5.5KW | ||
- Imp: 13.82A | |||
- Voc: 41.25Vdc |
Solar Input Specifications (550Wp reference) | Number of Panels | Total Input Power | Model | |
---|---|---|---|---|
- Isc: 12.98A | 10 units in series | 10 | 4,500 W | 5.5KVA |
11 units in series | 11 | 4,950 W | ||
12 units in series | 12 | 5,400 W | ||
6 units in series and 2 units in parallel | 12 | 5,400 W | 1.5KW-5.5KW | |
SOLAR INPUT | Number of panels | Total input power | Model | |
1 in series | 1 | 550W | 1.5KW-5.5KW | |
2 units in series | 2 | 900 W | 1.5KVA-5.5KW | |
3 units in series | 3 | 1,650 W | 2.5KVA-5.5KW | |
- Vmp: 42.48Vdc | 4 units in series | 4 | 2,200 W | 3.5KW-5.5KW |
- Imp: 12.95A | 5 units in series | 5 | 2,750 W | 5.5KW |
- Voc: 50.32Vdc | 6 units in series | 6 | 3,300 W | |
- Isc: 13.70A | 7 units in series | 7 | 3,850 W | |
8 units in series | 8 | 4,400 W | ||
9 units in series | 9 | 4,950 W | ||
4 sets in series and 2 sets in parallel | 8 | 4,400 W | ||
5 sets in series and 2 sets in parallel | 10 | 5,500 W |
PV Module Connection: Follow these steps:
- Strip 10mm insulation from positive and negative cables.
- Verify correct polarity of connection cables and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
VI. Final Assembly
Once all wires are connected, replace the bottom cover and secure it with the screws.
Operation
I. Power On/Off
After correct installation and battery connection, press the On/Off switch to power on the unit.
II. Operation Panel and Display
The operation panel is located on the front of the inverter and includes indicators, function buttons, and an LCD display showing operating status, input/output information, and power source details.
Figure 13: LED Indicators and Messages
Indicator LED | Color | Status | Message |
---|---|---|---|
AC/INV | Green | Solid | Output is powered directly from the grid (Line Mode). |
Blinking | Output is powered by the battery or PV in battery mode. | ||
CHG | Green | Solid | Battery is fully charged. |
Blinking | Battery is charging. | ||
DEFECT | Red | Solid | An error has occurred in the inverter. |
Blinking | A warning exists in the inverter. |
III. LCD Display Settings
Press and hold the ENTER button for 3 seconds to enter setting mode. Use UP/DOWN buttons to select programs and ENTER to confirm or ESC to exit.
Program Settings
Program | Description | Selection Options |
---|---|---|
01 | Output Source Priority: Configure charging source priority. |
|
02 | Maximum Charging Current: Configure total charging current for solar and grid chargers. | 60A (default). The charging current range is from the AC source current up to the specified maximum charging current. |
03 | Input Voltage Range: |
|
05 | Battery Type: |
|
06 | Automatic Restart after Overload: | Disable Automatic Restart (default) / Enable Automatic Restart. |
07 | Automatic Restart after Over-temperature: | Disable Automatic Restart / Enable Automatic Restart (default). |
08 | Output Voltage: | 220V / 230V (default) / 240V. |
09 | Output Frequency: | 50Hz (default) / 60Hz. |
10 | Bypass: | Manual (default) / Auto. In Auto mode, the system switches to bypass if the grid supply is correct, even if the switch is off. |
11 | Current: | 30A (default). |
12 | Grid Source Voltage Setting: Used for "SBU" or "Solar first" priority (Program 01). Settings depend on the model (12V, 24V, 48V). Max setting must be lower than Program 13 value. | |
13 | Battery Full Charge Voltage Setting: Used for "SBU" or "Solar first" priority (Program 01). Settings depend on the model (12V, 24V, 48V). Max setting must be higher than Program 12 value. | |
16 | Charging Source Priority: For configuring charging source priority. |
|
18 | Buzzer Mode: |
|
19 | Return to Default Display: | Return to Default Display (default) / Stay on Last Screen. |
20 | Backlight Control: | Backlight On (default) / Backlight Off. |
23 | Overload Bypass: When activated, the unit switches to grid power if overloaded in battery mode. | Bypass Disabled / Bypass Enabled (default). |
25 | Modbus ID Setting: | Modbus ID: 001 (default) ~ 247. |
26 | Charging Buffer Voltage (CV): User Defined setting. Value must be >= Program 27. Increments of 0.1V. Settings vary by model (12V, 24V, 48V). | |
27 | Float Charging Voltage: User Defined setting. Settings vary by model (12V, 24V, 48V). | |
29 | Low DC Disconnect Voltage: User Defined setting. Value must be < Program 12. Increments of 0.1V. Settings vary by model (12V, 24V, 48V). | |
32 | Charging Time (CV stage): | Automatic (default) / 5 min / 900 min. If "USE" selected in Program 05, this can be set. |
33 | Battery Equalization: | Battery Equalization / Battery Equalization Disabled (default). |
34 | Battery Voltage Equalization: Settings depend on model (12V, 24V, 48V). | |
35 | Battery Equalization Time: | 60 min (default) / 0 to 900 minutes. |
36 | Battery Equalization Time: | 120 min (default) / 0 to 900 minutes. |
37 | Equalization Interval: | 30 days (default) / 1 to 90 days. |
39 | Immediate Equalization: | Enabled / Disabled (default). If enabled, "E9" appears on LCD. If disabled, equalization is cancelled until next scheduled interval. |
41 | Automatic Activation for Lithium Battery: If "LIx" is selected (Program 05) and battery is not detected, unit activates lithium battery at specified time. Requires unit restart. | Disabled Automatic Activation (default). |
42 | Manual Activation for Lithium Battery: If "LIx" is selected (Program 05) and battery is not detected, manual activation is possible. This function is only available on models supporting lithium battery activation. | Implicit: Manual Activation Disabled. |
46 | Maximum Discharge Current: Reserved setting (not available for use). | Implicit OFF / Current Discharge Disabled / Protection Function. Available in single model. Network power enables grid mode, stopping discharge if set current is exceeded. If network power is unavailable, warning appears, and discharge continues. Setting range: 20A to 500A. |
Battery Equalization
The charge controller includes a battery equalization function to eliminate negative chemical effects like stratification and sulfate crystal buildup, which can reduce battery capacity. Periodic equalization is recommended.
How to Apply Equalization:
- Activate equalization in LCD settings (Program 33).
- Apply via:
- Set equalization interval in Program 37.
- Activate immediate equalization in Program 39.
When to Perform Equalization:
The controller enters equalization mode when the set time interval is reached or immediate equalization is activated.
Equalization Charging Time and Limit:
During equalization, the controller provides maximum power until the battery reaches the set equalization voltage. A constant voltage charge maintains this voltage. The battery remains in equalization until the set time is reached. If the set time passes and the voltage is still below the equalization voltage, the equalization time is extended. If the voltage remains low after the extended time, equalization ends, and the unit returns to maintenance mode.
Lithium Battery Settings
Settings for Lithium Battery without Communication
To avoid BMS protection triggers when there's no communication between the BMS and the unit:
- Obtain BMS specifications (Max Charge Voltage, Max Charge Current, Discharge Protection Voltage).
- Set Battery Type to "LIB".
- Set CV (Charge Voltage) to BMS Max Charge Voltage minus 0.5V.
Troubleshooting
Problem: Unit shuts down during startup.
Possible Cause: Battery voltage too low.
Solution: Charge the battery. Replace the battery.
Problem: No response after startup.
Possible Cause: Battery voltage too low, incorrect battery polarity.
Solution: Charge the battery. Check battery and cable connections. Replace battery pack.
Problem: Power is available, but the unit operates in battery mode.
Possible Cause: Input voltage displayed as 0 on LCD, green LED blinking (indicating poor AC quality or activated protection).
Solution: Check if the AC breaker is off and AC wiring is correct. Check AC cable thickness and length. Verify generator operation and input voltage settings.
Problem: Unit powers on, internal relay repeatedly starts and stops.
Possible Cause: Battery is disconnected.
Solution: Set "Solar First" as output source priority. Check battery cable connections.
Problem: Buzzer sounds continuously, red LED is on.
Possible Cause: Error code 07 (Overload), 05 (Short circuit), 02 (Internal temperature >100°C), 03 (Battery overcharged), 06/22 (Invalid output voltage), 08/09/15 (Component failure), 13 (Overcurrent/overvoltage), 14 (Low bus voltage).
Solution: Reduce load. Check wiring and remove abnormal loads. Ensure ventilation. Contact service center.
Specifications
Table 1: Line Mode Specifications
Model | 1.5KV A | 1.5KV A | 2.5KV A | 3.5KV A | 5.5KVA |
---|---|---|---|---|---|
Input Voltage Waveform | Sinusoidal (grid or generator) | ||||
Nominal Input Voltage | 230V AC | ||||
Reduced Loss Voltage | 170V AC ±7V (UPS) 90V AC ±7V (appliances) |
||||
Reduced Loss Voltage | 180V AC ±7V (UPS) 100V AC ±7V (appliances) |
||||
High Loss Voltage | 280V AC ±7V | ||||
High Loss Return Voltage | 270V AC ±7V | ||||
Max. AC Input Voltage | 300V C.A. | ||||
Nominal Input Frequency | 50Hz / 60Hz (auto-detect) | ||||
Reduced Loss Frequency | 40 ±1Hz | ||||
High Loss Return Frequency | 42 ±1Hz | ||||
High Loss Frequency | 65 ±1Hz | ||||
High Loss Return Frequency | 63 ±1Hz | ||||
Output Short Circuit Protection | Battery Mode: Electronic circuits | ||||
Efficiency (Linear Mode) | >95% (nominal R load, fully charged battery) | ||||
Switching Time | 10 ms typical (UPS) 20 ms typical (appliances) |
||||
Output Power Limitation: When AC input voltage drops to 95V or 170V, output power will be limited. |
Table 2: Inverter Mode Specifications
Model Inverter | 1.5KVA/1.5KW | 1.5KVA | 2.5KVA/2.5KW | 3.5KVA/3.5KW | 5.5KVA/5.5KW |
---|---|---|---|---|---|
Rated Output Power | 1.5KVA | 1.5KVA | 2.5KVA | 3.5KVA | 5.5KVA |
Input Voltage Waveform | Sine | ||||
Output Voltage Regulation | 230Vac±5% | ||||
Output Frequency | 50Hz or 60Hz | ||||
Max. Efficiency | 94% | ||||
Peak Capacity | 2* rated power for 5 seconds | ||||
Nominal DC Input Voltage | 12Vdc | 24Vdc | 48Vdc | ||
Cold Start Voltage | 11.0Vdc | 23.0Vdc | 46.0Vdc | ||
Low Voltage Warning (CC) | 11.0Vdc 10.7Vdc 10.1Vdc |
22.0Vdc 21.4 Vcc 20.2Vdc |
40.4Vdc 42.8Vdc 44.0Vdc |
||
Low Voltage Recovery (Continuous Current) | 11.5Vdc 11.2Vdc 10.6Vdc |
23.0Vdc 22,4 Vcc 21.2Vdc |
42.4Vdc 44.8Vdc 46.0Vdc |
||
Low Voltage Disconnect | 10.5Vdc 10.2Vdc 9.6Vdc |
21.0Vdc 20.4Vdc 19.2Vdc |
42.0Vdc 40.8Vdc 38,4Vdc |
Table 3: Charger Mode Specifications
Model | 1.5KVA | 1.5KVA | 2.5KVA | 3.5KVA | 5.5KVA |
---|---|---|---|---|---|
Utility Charging Current (PV+AC) (@ VI/P=230Vac) | 100Amp | 60Amp | 100Amp | 100Amp | 100Amp |
AC Charging Current (@ VI/P=230Vac) | 60Amp | ||||
Charging Voltage (Bulk) | 14.6 Vcc (Flooded) 14.1Vdc (AGM/GEL) |
29,2 VCC 28.2VDC |
58.4VDC 56.4VDC |
||
Continuous Charging Voltage | 13.5Vdc | 27VDC | 54VDC | ||
Overcharge Protection | 16.5Vdc | 32VDC | 63VDC | ||
Charging Algorithm | 3 stages | ||||
Charging Curve | Figure 89 | ||||
Solar Input | |||||
Model | 1.5KVA | 1.5KVA | 2.5KVA | 3.5KVA | 5.5KVA |
Rated Power | 2000W | 2000W | 3000W | 4000W | 5500W |
Max PV Array Open Circuit Voltage | 500Vdc | ||||
PV Array MPPT Voltage Range | 30Vdc~500Vdc | 60Vdc~500Vdc | |||
Max Input Current | 15A | 15A | 15A | 15A | 18A |
Charging Current (PV) | 100A | 60A | 100A | 100A | 100A |
Table 4: General Specifications
Model | 1.5KV A | 2.5KV A | 3.5KV A | 5.5KVA |
---|---|---|---|---|
Operating Temperature Range | -10°C to 55°C | |||
Storage Temperature | -15°C~60°C | |||
Humidity | 5% to 95% (non-condensing) |
Maintenance
- Keep the VALVATOR clean with a soft, dry cloth. Do not use chemicals.
- Regularly inspect power cables and connectors for damage (abrasions, cracks, loose connections).
- Ensure ventilation openings are clean and unobstructed for proper cooling.
- Avoid contact with water or other liquids to prevent electrical damage.
Disposal
This product is subject to WEEE regulations. Dispose of it at an authorized electrical waste collection point for safe recycling. Contact the manufacturer or an authorized service center for disposal inquiries.
Warranty and Service Information
The product is covered by a 24-month manufacturer's warranty from the date of purchase, covering defects in materials and workmanship. Contact the service department for assistance. The warranty does not cover damage from improper use, drops, mechanical damage, unauthorized repairs, or disassembly attempts.
Related Documents
![]() |
Qoltec Hybrid Solar Inverter User Manual Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, troubleshooting, and technical specifications. Includes model numbers 53863 and 53864. |
![]() |
Qoltec Off-Grid Hybrid Solar Inverter User Manual Comprehensive user manual for the Qoltec Off-Grid Hybrid Solar Inverter, covering installation, operation, technical specifications, troubleshooting, and maintenance for models 53863 and 53864. |
![]() |
Руководство по эксплуатации гибридного солнечного инвертора Qoltec Off-Grid Подробное руководство по установке, эксплуатации и устранению неполадок гибридного солнечного инвертора Qoltec Off-Grid. Включает информацию о подключении батарей, входов/выходов переменного тока и фотоэлектрических модулей. |
![]() |
Qoltec Hybrid Off-Grid Solar Inverter User Manual Comprehensive user manual for the Qoltec Hybrid Off-Grid Solar Inverter (models 53863, 53864), covering installation, operation, troubleshooting, and specifications. |
![]() |
Qoltec Hybrid Solar Inverter Off-Grid User Manual Comprehensive user manual for the Qoltec Hybrid Solar Inverter Off-Grid, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864. |
![]() |
Qoltec Hybrid Solar Inverter User Manual Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, maintenance, and troubleshooting for models 53863 and 53864. |
![]() |
Qoltec Hybrid Solar Inverter Off-Grid User Manual User manual for the Qoltec Hybrid Solar Inverter Off-Grid, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864. |
![]() |
Qoltec Hybrid Solar Inverter User Manual Comprehensive user manual for the Qoltec Hybrid Solar Inverter, covering installation, operation, troubleshooting, and specifications for models 53863 and 53864. |