NAPCO GEMC-EZM8 Zone Expansion Module Installation Instructions

For GEMINI C-Series Control Panels

Model: GEMC-EZM8

Document Revision: WI1683 08/10

Manufacturer: NAPCO SECURITY SYSTEMS, INC.

Address: 333 Bayview Avenue, Amityville, New York 11701

Sales/Repairs: (800) 645-9445 | Technical Service: (800) 645-9440

Publicly traded on NASDAQ Symbol: NSSC

UL LISTED: BURGLARY AND FIRE WARNING SYSTEM CONTROL UNIT ACCESSORY

Description

The GEMC-EZM8 Zone Expansion Module expands the capacity of NAPCO's GEMC-Series control panels. Each module provides up to 8 additional zones, configurable as either 4 or 8 zones per module. Multiple GEMC-EZM8 modules can be combined to meet the required number of zones for the GEMC-Series control panel. Refer to the GEMC-Series control panel installation instructions (WI1653) for specific wiring requirements.

Specifications

Wiring

Wire the expansion zones to the module and the module to the control panel using 12-22AWG wire. Install end-of-line resistors (EOLR) on all zones, even if a zone is not used. Note: Adding Zone Expansion Modules reduces the current available from the control panel's Auxiliary Power Output terminals by 60mA.

Diagram Descriptions

GEM-EZM8 Wiring Diagram

This diagram illustrates the connections for the GEMC-EZM8 module. It shows:

  • Power Connections: Input power from the GEMC Panel (Positive [+] and Negative [negative-terminal]) and Power Out (Positive [+] and Negative [negative-terminal]).
  • Zone Connections: Terminals for Zones 1 through 16 (or more, depending on configuration), each requiring a Positive [+] and Negative [negative-terminal] connection.
  • EOLR Connections: Placement of 2.2K UL Commercial Fire Listed EOLR resistors across contacts and at the end of loops.
  • PGM Output: A PGM output terminal.
  • Optional Connections: Terminals for an Optional Thermostat and a 4-Wire Smoke Detector, with specific wiring requirements including EOL resistors for fire zones.
  • Supervision: Zones are rated for 10.5-6VDC, 4.7-5.5mA. PGM is rated 12VDC @ 5mA. All zones are Class B, Style B and Supervised.
  • Location: For indoor/dry location use only.

4 Zone Configuration (1 EZM - 4 ZONES)

This configuration uses one GEMC-EZM8 module to provide 4 zones. Loop supervision is achieved with one contact per zone, using a 2.2K resistor across the contact and a 2.2K EOL resistor at the end of the line. All zones are Class B, Style B and Supervised. The configuration is set by placing jumper J1 on position #7.

Typical devices include: Magnetic contacts, PIRs (Passive Infrared sensors), pull stations, heat detectors, waterflow tamper switches, 4-wire smokes, carbon monoxide detectors, etc.

8 Zone Configuration (2 EZM - 8 ZONES)

This configuration uses one GEMC-EZM8 module to provide 8 zones. Loop supervision is achieved similarly to the 4-zone configuration, using 2.2K resistors across contacts and at the end of lines for each zone. All zones are Class B, Style B and Supervised. The default setting is 8 zones, achieved by removing jumper J1.

Typical devices include: Magnetic contacts, PIRs, pull stations, heat detectors, waterflow tamper switches, 4-wire smokes, carbon monoxide detectors, etc.

Configuration and Programming

Zone Assignment

Each GEMC-EZM8 module can be configured for either 4 or 8 zones. This is controlled by jumper J1. Place jumper J1 on position #7 for a 4-zone configuration. Remove jumper J1 for the default 8-zone configuration.

Base Address Assignment

Every module must be assigned a unique "base address". This address determines which zones the module will contain. The base address depends on the number of zones used by preceding modules or the control panel. Zones are divided into consecutively numbered groups of four. Missing numbers are not permitted. No two modules may have the same base address, even if on separate buses.

The base address is set using the Address Jumpers (located to the right of the LED). The following tables detail the jumper settings for configuring the module's base address and zone response.

Base Address and Configuration Tables

These tables map jumper settings (J1-J8, J7) to specific configurations, including loop response time (50ms or 750ms) and zone count (4Z or 8Z), and determine the resulting base address and the range of zone numbers assigned (First Zone # to Last Zone #).

Table 1: Base Address 1-10

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
1OFFOFFOFFOFFOFFOFFOFFOFFOFFOFF916912
2OFFONOFFOFFOFFOFFOFFONOFFOFF912912
3OFFOFFOFFOFFOFFOFFONOFFOFFOFF13201316
4OFFONOFFOFFOFFOFFONONOFFOFF17241720
5OFFOFFOFFOFFOFFONOFFOFFOFFOFF21282124
6OFFONOFFOFFOFFONOFFONOFFOFF25322528
7OFFOFFOFFOFFONOFFOFFOFFOFFOFF29362932
8OFFONOFFOFFONOFFOFFONOFFOFF33403336
9OFFOFFOFFONOFFOFFOFFOFFOFFOFF37443740
10OFFONOFFONOFFOFFOFFONOFFOFF41484144

Table 2: Base Address 11-20

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
11OFFOFFOFFONOFFOFFONOFFOFFOFF45524548
12OFFONOFFONOFFOFFONONOFFOFF53605356
13OFFOFFOFFONOFFONOFFOFFOFFOFF61686164
14OFFONOFFONOFFONOFFONOFFOFF69766972
15OFFOFFOFFONONOFFOFFOFFOFFOFF77847780
16OFFONOFFONONOFFOFFONOFFOFF81888184
17OFFOFFOFFONONOFFONOFFOFFOFF85928588
18OFFONOFFONONOFFONONOFFOFF89968992
19OFFOFFOFFONONONOFFOFFOFFOFF9710497100
20OFFONOFFONONONOFFONOFFOFF101108101104

Table 3: Base Address 21-30

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
21OFFOFFOFFONONOFFOFFOFFOFFOFF109116109112
22OFFONOFFONONOFFOFFONOFFOFF113120113116
23OFFOFFOFFONONOFFONOFFOFFOFF117124117120
24OFFONOFFONONOFFONONOFFOFF121128121124
25OFFOFFONOFFOFFOFFOFFOFFOFFOFF129136129132
26OFFONONOFFOFFOFFOFFONOFFOFF137144137140
27OFFOFFONOFFOFFOFFONOFFOFFOFF141148141144
28OFFONONOFFOFFOFFONONOFFOFF145152145148
29OFFOFFONOFFOFFONOFFOFFOFFOFF149156149152
30OFFONONOFFOFFONOFFONOFFOFF153160153156

Table 4: Base Address 31-40

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
31OFFOFFONOFFONOFFOFFOFFOFFOFF157164157160
32OFFONONOFFONOFFOFFONOFFOFF161168161164
33OFFOFFONOFFONOFFONOFFOFFOFF165172165168
34OFFONONOFFONOFFONONOFFOFF169176169172
35OFFOFFONONOFFOFFOFFOFFOFFOFF173180173176
36OFFONONONOFFOFFOFFONOFFOFF177184177180
37OFFOFFONONOFFOFFONOFFOFFOFF181188181184
38OFFONONONOFFOFFONONOFFOFF185192185188
39OFFOFFONONOFFONOFFOFFOFFOFF189196189192
40OFFONONONOFFONOFFONOFFOFF193200193196

Table 5: Base Address 41-50

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
41OFFOFFONONONOFFOFFOFFOFFOFF197204197200
42OFFONONONONOFFOFFONOFFOFF201208201204
43OFFOFFONONONOFFONOFFOFFOFF205212205208
44OFFONONONONOFFONONOFFOFF209216209212
45OFFOFFONONONONOFFOFFOFFOFF213220213216
46OFFONONONONONOFFONOFFOFF217224217220
47OFFOFFONONONONONOFFOFFOFF221228221224
48OFFONONONONONONONOFFOFF225232225228
49OFFOFFONONONONONONOFFOFF229236229232
50OFFONONONONONONONONOFF233240233236

Table 6: Base Address 51-63

Base Address Config First 4 Zone Loop Response 4 or 8 Zone EZM Base Address Jumpers (J7-J1) First Zone # Last Zone # First Zone # (with J7) Last Zone # (with J7)
OFF=750mS ON=50mSOFF=8Z ON=4Z87654321
51OFFOFFONONONONONONOFFOFF237244237240
52OFFONONONONONONONONOFF241248241244
53OFFOFFONONONONONONONOFF245252245248
54OFFONONONONONONONONON249256249252
55OFFOFFONONONONONONONON253260253256
56OFFONONONONONONONONONXXXX
57OFFOFFONONONONONONONONXXXX
58OFFONONONONONONONONONXXXX
59OFFOFFONONONONONONONONXXXX
60OFFONONONONONONONONONXXXX
61OFFOFFONONONONONONONONXXXX
62OFFONONONONONONONONONXXXX
63OFFOFFONONONONONONONONXXXX

Note: 'X' indicates values not specified or applicable for these configurations.

Tamper Functionality

If the module cover is removed or the module is detached from its mounting, the keypad sounder will pulse, and the display will indicate a zone/module tamper condition along with the module number. Pressing RESET silences the sounder. Note: The EZM tamper function does not operate when the module is used in a GEMC-Series control panel Fire system or Combination Fire/Burglary system if the GEMC-EZM8 is programmed as a 4 Zone Fire type or 8 Zone Fire type.

Loop Response

Loop response times for Zones 1 through 8 are programmed in the control panel. The default response time for all expansion zones is 750mS. To reduce the response time of zones 1 through 4 of the EZM Module to 50mS, install the Loop Response Jumper (Jumper #8: ON = 50mS; OFF = 750mS). To revert to the normal 750mS response time, remove the jumper. Refer to the Wiring Diagram for placement. DO NOT ENABLE THIS FEATURE IN UL INSTALLATIONS.

Status LED

The Status LED indicates the condition of the zone module:

NAPCO Limited Warranty

NAPCO warrants its products against manufacturing defects in materials and workmanship for thirty-six (36) months from the date of manufacture. NAPCO will, at its option, repair or replace any defective product free of charge to the original purchaser or user.

This warranty does not cover equipment that has been repaired by others, improperly installed, misused, altered, damaged, subjected to acts of God, or had serial numbers altered or removed. NAPCO is not responsible for dismantling or reinstallation charges.

There are no warranties, express or implied, beyond the description on the face of this document, including implied warranties of merchantability or fitness for a particular purpose. This warranty is in lieu of all other obligations or liabilities of NAPCO.

Any claim for breach of warranty must be brought within six months following the end of the warranty period. NAPCO shall not be liable for any consequential or incidental damages for breach of this or any other warranty, even if caused by NAPCO's negligence.

For warranty service, contact the security professional who installed the system. The product must be returned by the professional, with shipping costs prepaid and insured, to NAPCO. NAPCO covers the cost of returning repaired/replaced products.

NAPCO recommends weekly testing of the entire system. The product may not prevent all personal injury or property loss and is not an insurer. NAPCO's liability is limited to the original selling price of the product.

Some states may have different rules regarding implied warranties or incidental/consequential damages.

Important Wiring Methods

Proper wiring techniques are crucial for reliable operation. The following methods are recommended for terminal blocks:

Single-Conductor Terminal Blocks

Correct Method: For terminating more than one conductor to a terminal, use a single incoming conductor and/or a pigtail connector (wire nut or crimp connector) to connect multiple wires. This ensures a secure connection for each wire.

Incorrect Method: Simply twisting wires together or forcing multiple bare wires into a single terminal without proper connectors.

"Barrier" Type Terminal Blocks

Correct Method: For terminating two conductors to a terminal, ensure separate incoming and outgoing conductors are properly seated. For more than two conductors or different wire sizes, use the "pigtail" method with an appropriate wire nut or crimp connector.

Incorrect Method: Overloading terminals or using improper connections.

Use insulated wire for pigtails and secure conductors firmly with appropriate connectors for the number and gauge of wires used.

PDF preview unavailable. Download the PDF instead.

GEMC-EZM8 Acrobat Distiller 5.0.5 (Windows)

Related Documents

Preview NAPCO GEM-P1632 Installation Instructions
Comprehensive installation guide for the NAPCO GEM-P1632 Control Panel/Communicator, detailing wiring, features, specifications, and testing procedures for burglary and fire alarm systems.
Preview NAPCO GEM-P1632 Control Panel Programming Instructions
Comprehensive programming manual for the NAPCO GEM-P1632 Control Panel/Communicator, detailing setup and configuration with various NAPCO keypads including Classic and K Series models. Covers Easy Menu-Driven and Direct Address programming modes.
Preview Napco FireLink FACP Programming and Installation Guide
A comprehensive guide to programming and installing the Napco FireLink Fire Alarm Control Panel (FACP) and communicator, covering both easy default and advanced programming methods, along with warranty information.
Preview Napco GEM-RP3DGTL Keypad Operating Guide
Comprehensive operating guide for the Napco GEM-RP3DGTL keypad, detailing its features, functions, arming/disarming procedures, fire protection, troubleshooting, and system error codes. Includes instructions for installation, programming, and system testing.
Preview NAPCO GEM-RP1CAe2 Keypad Operating Guide
This comprehensive operating guide provides detailed instructions for the NAPCO GEM-RP1CAe2 keypad, a smart, user-friendly, interactive menu-driven keypad for Napco control panels. It covers system arming and disarming, fire protection, keypad functions, programming, troubleshooting, error codes, and warranty information.
Preview NAPCO Freedom F-64TPBR Touchpad Home Security System Operating Guide
Comprehensive operating guide for the NAPCO Freedom F-64TPBR Bedroom Touchpad Home Security System, covering system introduction, controls, arming and disarming procedures, emergency functions, fire protection, menu modes, user programming, error codes, FCC statements, system limitations, and warranty information.
Preview NAPCO GEM-P816 Control Panel/Communicator Programming Instructions
Comprehensive programming instructions for the NAPCO GEM-P816 Control Panel/Communicator, covering both classic and K Series keypads. Details easy menu-driven and direct address programming modes, system options, keypad configuration, and more.
Preview NAPCO GEM-P1664 Control Panel Programming Instructions
This document provides programming instructions for the NAPCO GEM-P1664 Control Panel and Communicator, detailing operations for both 'Classic' GEM-RP series and 'K Series' GEM-K series keypads. It covers various programming modes including Easy Menu-Driven Program Mode and Direct Address Program Mode, along with system options, keypad configuration, and user code management.