NAPCO GEMC-EZM8 Zone Expansion Module Installation Instructions
For GEMINI C-Series Control Panels
Model: GEMC-EZM8
Document Revision: WI1683 08/10
Manufacturer: NAPCO SECURITY SYSTEMS, INC.
Address: 333 Bayview Avenue, Amityville, New York 11701
Sales/Repairs: (800) 645-9445 | Technical Service: (800) 645-9440
Publicly traded on NASDAQ Symbol: NSSC
UL LISTED: BURGLARY AND FIRE WARNING SYSTEM CONTROL UNIT ACCESSORY
Description
The GEMC-EZM8 Zone Expansion Module expands the capacity of NAPCO's GEMC-Series control panels. Each module provides up to 8 additional zones, configurable as either 4 or 8 zones per module. Multiple GEMC-EZM8 modules can be combined to meet the required number of zones for the GEMC-Series control panel. Refer to the GEMC-Series control panel installation instructions (WI1653) for specific wiring requirements.
Specifications
- Input Power: 12.5 - 7.5VDC, 60mA
- Zone Loop Current: 4.7mA nominal, 5.5mA when shorted
- Maximum Zone Loop Resistance: 300 ohms
- End of Line Resistor (EOLR): 2.2K (UL Listed part number EOL2.2K required for Fire applications)
- PGM Output: 5mA, 12V (Active low). For power-limited circuits less than 14VDC. Use only in Burglary applications.
- Ground Faults Detected: 1.25K to ground or less.
Wiring
Wire the expansion zones to the module and the module to the control panel using 12-22AWG wire. Install end-of-line resistors (EOLR) on all zones, even if a zone is not used. Note: Adding Zone Expansion Modules reduces the current available from the control panel's Auxiliary Power Output terminals by 60mA.
Diagram Descriptions
GEM-EZM8 Wiring Diagram
This diagram illustrates the connections for the GEMC-EZM8 module. It shows:
- Power Connections: Input power from the GEMC Panel (Positive [+] and Negative [negative-terminal]) and Power Out (Positive [+] and Negative [negative-terminal]).
- Zone Connections: Terminals for Zones 1 through 16 (or more, depending on configuration), each requiring a Positive [+] and Negative [negative-terminal] connection.
- EOLR Connections: Placement of 2.2K UL Commercial Fire Listed EOLR resistors across contacts and at the end of loops.
- PGM Output: A PGM output terminal.
- Optional Connections: Terminals for an Optional Thermostat and a 4-Wire Smoke Detector, with specific wiring requirements including EOL resistors for fire zones.
- Supervision: Zones are rated for 10.5-6VDC, 4.7-5.5mA. PGM is rated 12VDC @ 5mA. All zones are Class B, Style B and Supervised.
- Location: For indoor/dry location use only.
4 Zone Configuration (1 EZM - 4 ZONES)
This configuration uses one GEMC-EZM8 module to provide 4 zones. Loop supervision is achieved with one contact per zone, using a 2.2K resistor across the contact and a 2.2K EOL resistor at the end of the line. All zones are Class B, Style B and Supervised. The configuration is set by placing jumper J1 on position #7.
Typical devices include: Magnetic contacts, PIRs (Passive Infrared sensors), pull stations, heat detectors, waterflow tamper switches, 4-wire smokes, carbon monoxide detectors, etc.
8 Zone Configuration (2 EZM - 8 ZONES)
This configuration uses one GEMC-EZM8 module to provide 8 zones. Loop supervision is achieved similarly to the 4-zone configuration, using 2.2K resistors across contacts and at the end of lines for each zone. All zones are Class B, Style B and Supervised. The default setting is 8 zones, achieved by removing jumper J1.
Typical devices include: Magnetic contacts, PIRs, pull stations, heat detectors, waterflow tamper switches, 4-wire smokes, carbon monoxide detectors, etc.
Configuration and Programming
Zone Assignment
Each GEMC-EZM8 module can be configured for either 4 or 8 zones. This is controlled by jumper J1. Place jumper J1 on position #7 for a 4-zone configuration. Remove jumper J1 for the default 8-zone configuration.
Base Address Assignment
Every module must be assigned a unique "base address". This address determines which zones the module will contain. The base address depends on the number of zones used by preceding modules or the control panel. Zones are divided into consecutively numbered groups of four. Missing numbers are not permitted. No two modules may have the same base address, even if on separate buses.
The base address is set using the Address Jumpers (located to the right of the LED). The following tables detail the jumper settings for configuring the module's base address and zone response.
Base Address and Configuration Tables
These tables map jumper settings (J1-J8, J7) to specific configurations, including loop response time (50ms or 750ms) and zone count (4Z or 8Z), and determine the resulting base address and the range of zone numbers assigned (First Zone # to Last Zone #).
Table 1: Base Address 1-10
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
1 | OFF | OFF | OFF | OFF | OFF | OFF | OFF | OFF | OFF | OFF | 9 | 16 | 9 | 12 | |
2 | OFF | ON | OFF | OFF | OFF | OFF | OFF | ON | OFF | OFF | 9 | 12 | 9 | 12 | |
3 | OFF | OFF | OFF | OFF | OFF | OFF | ON | OFF | OFF | OFF | 13 | 20 | 13 | 16 | |
4 | OFF | ON | OFF | OFF | OFF | OFF | ON | ON | OFF | OFF | 17 | 24 | 17 | 20 | |
5 | OFF | OFF | OFF | OFF | OFF | ON | OFF | OFF | OFF | OFF | 21 | 28 | 21 | 24 | |
6 | OFF | ON | OFF | OFF | OFF | ON | OFF | ON | OFF | OFF | 25 | 32 | 25 | 28 | |
7 | OFF | OFF | OFF | OFF | ON | OFF | OFF | OFF | OFF | OFF | 29 | 36 | 29 | 32 | |
8 | OFF | ON | OFF | OFF | ON | OFF | OFF | ON | OFF | OFF | 33 | 40 | 33 | 36 | |
9 | OFF | OFF | OFF | ON | OFF | OFF | OFF | OFF | OFF | OFF | 37 | 44 | 37 | 40 | |
10 | OFF | ON | OFF | ON | OFF | OFF | OFF | ON | OFF | OFF | 41 | 48 | 41 | 44 |
Table 2: Base Address 11-20
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
11 | OFF | OFF | OFF | ON | OFF | OFF | ON | OFF | OFF | OFF | 45 | 52 | 45 | 48 | |
12 | OFF | ON | OFF | ON | OFF | OFF | ON | ON | OFF | OFF | 53 | 60 | 53 | 56 | |
13 | OFF | OFF | OFF | ON | OFF | ON | OFF | OFF | OFF | OFF | 61 | 68 | 61 | 64 | |
14 | OFF | ON | OFF | ON | OFF | ON | OFF | ON | OFF | OFF | 69 | 76 | 69 | 72 | |
15 | OFF | OFF | OFF | ON | ON | OFF | OFF | OFF | OFF | OFF | 77 | 84 | 77 | 80 | |
16 | OFF | ON | OFF | ON | ON | OFF | OFF | ON | OFF | OFF | 81 | 88 | 81 | 84 | |
17 | OFF | OFF | OFF | ON | ON | OFF | ON | OFF | OFF | OFF | 85 | 92 | 85 | 88 | |
18 | OFF | ON | OFF | ON | ON | OFF | ON | ON | OFF | OFF | 89 | 96 | 89 | 92 | |
19 | OFF | OFF | OFF | ON | ON | ON | OFF | OFF | OFF | OFF | 97 | 104 | 97 | 100 | |
20 | OFF | ON | OFF | ON | ON | ON | OFF | ON | OFF | OFF | 101 | 108 | 101 | 104 |
Table 3: Base Address 21-30
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
21 | OFF | OFF | OFF | ON | ON | OFF | OFF | OFF | OFF | OFF | 109 | 116 | 109 | 112 | |
22 | OFF | ON | OFF | ON | ON | OFF | OFF | ON | OFF | OFF | 113 | 120 | 113 | 116 | |
23 | OFF | OFF | OFF | ON | ON | OFF | ON | OFF | OFF | OFF | 117 | 124 | 117 | 120 | |
24 | OFF | ON | OFF | ON | ON | OFF | ON | ON | OFF | OFF | 121 | 128 | 121 | 124 | |
25 | OFF | OFF | ON | OFF | OFF | OFF | OFF | OFF | OFF | OFF | 129 | 136 | 129 | 132 | |
26 | OFF | ON | ON | OFF | OFF | OFF | OFF | ON | OFF | OFF | 137 | 144 | 137 | 140 | |
27 | OFF | OFF | ON | OFF | OFF | OFF | ON | OFF | OFF | OFF | 141 | 148 | 141 | 144 | |
28 | OFF | ON | ON | OFF | OFF | OFF | ON | ON | OFF | OFF | 145 | 152 | 145 | 148 | |
29 | OFF | OFF | ON | OFF | OFF | ON | OFF | OFF | OFF | OFF | 149 | 156 | 149 | 152 | |
30 | OFF | ON | ON | OFF | OFF | ON | OFF | ON | OFF | OFF | 153 | 160 | 153 | 156 |
Table 4: Base Address 31-40
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
31 | OFF | OFF | ON | OFF | ON | OFF | OFF | OFF | OFF | OFF | 157 | 164 | 157 | 160 | |
32 | OFF | ON | ON | OFF | ON | OFF | OFF | ON | OFF | OFF | 161 | 168 | 161 | 164 | |
33 | OFF | OFF | ON | OFF | ON | OFF | ON | OFF | OFF | OFF | 165 | 172 | 165 | 168 | |
34 | OFF | ON | ON | OFF | ON | OFF | ON | ON | OFF | OFF | 169 | 176 | 169 | 172 | |
35 | OFF | OFF | ON | ON | OFF | OFF | OFF | OFF | OFF | OFF | 173 | 180 | 173 | 176 | |
36 | OFF | ON | ON | ON | OFF | OFF | OFF | ON | OFF | OFF | 177 | 184 | 177 | 180 | |
37 | OFF | OFF | ON | ON | OFF | OFF | ON | OFF | OFF | OFF | 181 | 188 | 181 | 184 | |
38 | OFF | ON | ON | ON | OFF | OFF | ON | ON | OFF | OFF | 185 | 192 | 185 | 188 | |
39 | OFF | OFF | ON | ON | OFF | ON | OFF | OFF | OFF | OFF | 189 | 196 | 189 | 192 | |
40 | OFF | ON | ON | ON | OFF | ON | OFF | ON | OFF | OFF | 193 | 200 | 193 | 196 |
Table 5: Base Address 41-50
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
41 | OFF | OFF | ON | ON | ON | OFF | OFF | OFF | OFF | OFF | 197 | 204 | 197 | 200 | |
42 | OFF | ON | ON | ON | ON | OFF | OFF | ON | OFF | OFF | 201 | 208 | 201 | 204 | |
43 | OFF | OFF | ON | ON | ON | OFF | ON | OFF | OFF | OFF | 205 | 212 | 205 | 208 | |
44 | OFF | ON | ON | ON | ON | OFF | ON | ON | OFF | OFF | 209 | 216 | 209 | 212 | |
45 | OFF | OFF | ON | ON | ON | ON | OFF | OFF | OFF | OFF | 213 | 220 | 213 | 216 | |
46 | OFF | ON | ON | ON | ON | ON | OFF | ON | OFF | OFF | 217 | 224 | 217 | 220 | |
47 | OFF | OFF | ON | ON | ON | ON | ON | OFF | OFF | OFF | 221 | 228 | 221 | 224 | |
48 | OFF | ON | ON | ON | ON | ON | ON | ON | OFF | OFF | 225 | 232 | 225 | 228 | |
49 | OFF | OFF | ON | ON | ON | ON | ON | ON | OFF | OFF | 229 | 236 | 229 | 232 | |
50 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | OFF | 233 | 240 | 233 | 236 |
Table 6: Base Address 51-63
Base Address | Config | First 4 Zone Loop Response | 4 or 8 Zone EZM | Base Address Jumpers (J7-J1) | First Zone # | Last Zone # | First Zone # (with J7) | Last Zone # (with J7) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
OFF=750mS ON=50mS | OFF=8Z ON=4Z | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | ||||||
51 | OFF | OFF | ON | ON | ON | ON | ON | ON | OFF | OFF | 237 | 244 | 237 | 240 | |
52 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | OFF | 241 | 248 | 241 | 244 | |
53 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | OFF | 245 | 252 | 245 | 248 | |
54 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | ON | 249 | 256 | 249 | 252 | |
55 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | ON | 253 | 260 | 253 | 256 | |
56 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
57 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
58 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
59 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
60 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
61 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
62 | OFF | ON | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X | |
63 | OFF | OFF | ON | ON | ON | ON | ON | ON | ON | ON | X | X | X | X |
Note: 'X' indicates values not specified or applicable for these configurations.
Tamper Functionality
If the module cover is removed or the module is detached from its mounting, the keypad sounder will pulse, and the display will indicate a zone/module tamper condition along with the module number. Pressing RESET silences the sounder. Note: The EZM tamper function does not operate when the module is used in a GEMC-Series control panel Fire system or Combination Fire/Burglary system if the GEMC-EZM8 is programmed as a 4 Zone Fire type or 8 Zone Fire type.
Loop Response
Loop response times for Zones 1 through 8 are programmed in the control panel. The default response time for all expansion zones is 750mS. To reduce the response time of zones 1 through 4 of the EZM Module to 50mS, install the Loop Response Jumper (Jumper #8: ON = 50mS; OFF = 750mS). To revert to the normal 750mS response time, remove the jumper. Refer to the Wiring Diagram for placement. DO NOT ENABLE THIS FEATURE IN UL INSTALLATIONS.
Status LED
The Status LED indicates the condition of the zone module:
- OFF: Control Panel has no power applied.
- ON Steady: Control Panel has power applied, but the panel is not polling the module. This can occur if: the panel is in "CONFIG" mode, the panel is not programmed to poll the module's address, or the green wire (GRN) is not connected correctly.
- PULSES: Indicates the EZM groups being polled.
- Once slowly: The first EZM group (base address) is polled.
- Once then twice sequentially: The first and second EZM groups are polled.
- 1, 2, 3, 4 sequentially: The first, second, third, and fourth groups are polled.
NAPCO Limited Warranty
NAPCO warrants its products against manufacturing defects in materials and workmanship for thirty-six (36) months from the date of manufacture. NAPCO will, at its option, repair or replace any defective product free of charge to the original purchaser or user.
This warranty does not cover equipment that has been repaired by others, improperly installed, misused, altered, damaged, subjected to acts of God, or had serial numbers altered or removed. NAPCO is not responsible for dismantling or reinstallation charges.
There are no warranties, express or implied, beyond the description on the face of this document, including implied warranties of merchantability or fitness for a particular purpose. This warranty is in lieu of all other obligations or liabilities of NAPCO.
Any claim for breach of warranty must be brought within six months following the end of the warranty period. NAPCO shall not be liable for any consequential or incidental damages for breach of this or any other warranty, even if caused by NAPCO's negligence.
For warranty service, contact the security professional who installed the system. The product must be returned by the professional, with shipping costs prepaid and insured, to NAPCO. NAPCO covers the cost of returning repaired/replaced products.
NAPCO recommends weekly testing of the entire system. The product may not prevent all personal injury or property loss and is not an insurer. NAPCO's liability is limited to the original selling price of the product.
Some states may have different rules regarding implied warranties or incidental/consequential damages.
Important Wiring Methods
Proper wiring techniques are crucial for reliable operation. The following methods are recommended for terminal blocks:
Single-Conductor Terminal Blocks
Correct Method: For terminating more than one conductor to a terminal, use a single incoming conductor and/or a pigtail connector (wire nut or crimp connector) to connect multiple wires. This ensures a secure connection for each wire.
Incorrect Method: Simply twisting wires together or forcing multiple bare wires into a single terminal without proper connectors.
"Barrier" Type Terminal Blocks
Correct Method: For terminating two conductors to a terminal, ensure separate incoming and outgoing conductors are properly seated. For more than two conductors or different wire sizes, use the "pigtail" method with an appropriate wire nut or crimp connector.
Incorrect Method: Overloading terminals or using improper connections.
Use insulated wire for pigtails and secure conductors firmly with appropriate connectors for the number and gauge of wires used.