Wattstopper Infusion Controller II

Architectural Dimming Controllers

Description

The Infusion Controller II (IC-24-II and IC-36-II) serves as the central control unit for sophisticated building management systems. It is designed to support a wide range of Wattstopper user interfaces, including Equinox touchscreens, and offers advanced capabilities for managing complex systems. The controller provides precise control, real-time feedback, and a scalable architecture, enabling personalized system configurations. It seamlessly integrates various building subsystems such as shades, comfort control, security, and audio/video, enhancing the overall control experience.

Operation

The Infusion Controller II operates with an independent power supply. The IC-24-II utilizes a 24V power supply delivering 35W shared power to two station bus runs, while the IC-36-II uses a 36V power supply delivering 60W to each of two station bus runs. This allows for support of up to 120 WireLink stations or 38 Equinox 40 stations, and up to 120 RadioLink stations. Multiple controllers can be networked to expand system capacity. The system features five RS232 and two RS485 ports for device connectivity, and an Ethernet connection for IP-connected products. The BACnet-IP-IC option enables seamless integration with Building Management Systems (BMS) for control and feedback from the Wattstopper architectural dimming platform.

Highlights

Features

Specifications

Model IC-36-II and IC-24-II
Ambient operating humidity 5-95% non-condensing
Ambient operating temperature 32-104°F (0-40°C)
Cooling Convection
Lithium battery backup Disk battery CR2032, 3V (2.5 yrs. un-powered or 20 yrs. powered)
Max. # WireLink stations (IC-24-II) Up to 50 stations each bus or until the shared 35W supply is used
Max. # WireLink stations (IC-36-II) Up to 60 stations each bus or until the independent 60W supply is used on each bus
Max. distance of each controller to controller bus network 2,000 feet / 609 meters (Wattstopper spec. wire); 1,000 feet / 304 meters (CAT5 wire)
Max. wire from IC to SC 200 feet / 61 meters
Max. wire length Station Bus 2,000 feet of cabling max. on each Station Bus. No station more than 1,000 feet from controller.
Maximum power draw 200W
Minimum power draw 6W
Station Bus power supply, IC-24-II One 35W shared power supply to both Station Buses
Station Bus power supply, IC-36-II One 60W independent power supply to each Station Bus
Station Bus specification 2C 16AWG, non-shield, < 30pF per foot. Station Bus should be separated a minimum of 18" from other parallel communication and/or high voltage runs.
Voltage 120-240V, 50/60Hz
Weight 3.3 lbs / 1.5kg
Station Bus wiring topology Daisy chain, branch, star
Controller-to-controller, IC network wiring topology Daisy chain
Lightning/surge protection Static shock 10; all ports and case; IEC 61000-4-2, low-voltage; ITU-T K.20
UL, CUL, and CE Listed Yes
Warranty 5 years

System Compatibility

The IC-36-II and IC-24-II controllers are compatible with other IC-II class controllers.

Wiring Diagram

The Infusion Controller plugs into the main enclosure terminal board after all connections have been made. CAT5E: RJ-45 termination consistent with local area network pinout wiring.

Terminal Board Part #: VSUB215 (Pre-Installed in Main Enclosures)

Key Terminal Connections:

Important Notes:

Ordering Information

Catalog # Description Voltage Misc.
IC-36-II InFusion Controller II - 36V 120-240V, 50/60Hz Up to 60 stations per bus; Up to 18 Equinox 40 stations per bus
IC-24-II InFusion Controller II - 24V 120-240V, 50/60Hz Up to 50 stations per bus; Up to 11 Equinox 40 stations
BACNET-IP-IC BACnet-enabled IC-36-II and IC-24-II controllers Enables two-way BACnet control of InFusion Controllers

Additional Mounting Accessories

Catalog # Description Catalog # Description
IRME-24 24 Volt InFusion Rack Mount Enclosure IRME-24RF-KIT 24 Volt In Fusion Rack Mount Enclosure Kit
IRME-36 36 Volt InFusion Rack Mount Enclosure IRME-36RF-KIT 36 Volt In Fusion Rack Mount Enclosure Kit
ISME-24 24 Volt InFusion Surface Mount Enclosure ISME-24RF-KIT 24 Volt In Fusion Surface Mount Enclosure with RadioLink Kit
ISME-36 36 Volt InFusion Surface Mount Enclosure ISME-36RF-KIT 36 Volt InFusion Surface Mount Enclosure with RadioLink Kit

PDF preview unavailable. Download the PDF instead.

BACNET-IP-IC Adobe PDF Library 9.9 Adobe InDesign CS5.5 (7.5.2)

Related Documents

Preview WattStopper LMSM Series: Network Segment Manager & Supervisor Datasheet
This document details the WattStopper LMSM Series Network Segment Manager and Network Supervisor, providing comprehensive information on their features, specifications, operation, and applications for digital lighting management systems. It covers network connectivity, scheduling, monitoring, and BACnet integration for efficient building control.
Preview Wattstopper PW-311 Occupancy Sensor: Installation, Features, and Troubleshooting
Comprehensive guide to installing and configuring the Wattstopper PW-311 Passive Infrared 0-10 Volt Wall Switch Occupancy Sensor. Covers specifications, wiring, multi-way setup, emergency lighting integration, button functions, coverage patterns, advanced programming, troubleshooting, and warranty information.
Preview Wattstopper LMPS-6000 DLM Skylight Photocell Installation Guide
Installation guide for the Wattstopper LMPS-6000 DLM Skylight Photocell, detailing its integration with Legrand's DLM system for automated daylight harvesting and lighting control. Includes specifications, wiring, and maintenance.
Preview Wattstopper FSP-301B PIR Fixture Integrated Outdoor Sensor Installation Guide
Comprehensive installation, configuration, and troubleshooting guide for the Wattstopper FSP-301B series of low voltage, continuous dimming PIR fixture integrated outdoor sensors with Bluetooth low energy technology.
Preview Wattstopper HS-150 Line Voltage Card Key Switch Installation Guide
Comprehensive installation and operation guide for the Wattstopper HS-150 Line Voltage Card Key Switch. Includes detailed specifications, wiring diagrams (textual descriptions), troubleshooting tips, and ordering information for hotel room lighting and power control.
Preview Wattstopper LMDC-100 Dual Technology Ceiling Mount Occupancy Sensor
Detailed specifications and features of the Wattstopper LMDC-100, a dual-technology ceiling mount occupancy sensor for energy-efficient lighting and plug load control. Includes operation, applications, mounting, wiring, and ordering information.
Preview Wattstopper DSW Series Dual Technology Wall Switch Occupancy Sensor Installation Guide
Comprehensive installation instructions, specifications, operating modes, and troubleshooting for the Wattstopper DSW Series Dual Technology Multi-Way Wall Switch Occupancy Sensors (DSW-301, DSW-302). Covers features like PIR and ultrasonic detection, manual/auto ON modes, time delays, and multi-way wiring.
Preview Wattstopper Power Pack Installation Instructions
Installation instructions for Wattstopper Power Packs, including wiring diagrams and warranty information. Covers models A120C-P and A277C-P.