Wattstopper HS-150 Line Voltage Card Key Switch Installation Instructions

Document Number: No: 24776-06/24 rev. 2

Installation Instructions • Instructions d'Installation • Instrucciones de Instalación

Catalog Number: HS-150

Country of Origin: Made in China • Fabriqué en Chine • Hecho en China

Specifications

Voltage120/277VAC, 50/60Hz
Power ConsumptionMaximum 2.1 Watts
Load Rating@120 VAC: 0-1800W tungsten or ballast, 15A receptacle; 1/2 hp
@277 VAC: 0-1200W ballast
Egress Time Delay30 seconds
EnvironmentIndoor use only
Operating Temperature32° to 104°F (0° to 40°C)
Humidity95% RH, non-condensing
Card Slot Dimensions2.125"W x 3.375"H x 0.034"D (53.975mm x 85.725mm x 0.8636mm)
Tools NeededInsulated Screwdriver, Wire Strippers

Description and Operation

The HS-150 is a line voltage card key switch that operates as a master switch to enable or disable power to single-pole electric branch circuits and loads in a hotel guest room or similar site. When a hotel door entry card key (or the key fob HS-FOB) is inserted in the HS-150 card slot, the controlled circuits are energized. When the hotel door entry card key (or HS-FOB) is removed, the controlled circuits will remain energized for 30 seconds more to allow safe egress from the hotel room. After this time delay elapses, they will be de-energized. To restore power to the room, the occupant will need to reinsert the hotel door entry card key into the HS-150 card slot.

Lighted Card Slot

To help locate the HS-150 in a dark room, two green LEDs illuminate the card slot. When the card or HS-FOB is in the slot, the green LEDs are OFF.

Installation and Wiring

⚠ WARNING: TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING.

  1. Make sure that the power has been turned off at the circuit breaker.
  2. Strip insulation off the wires to expose their copper cores to the length indicated by the "Strip Gauge" shown in Figure 1. Approximately 1/2".
  3. Connect wires to the HS-150 flying leads as shown in the wiring diagram (Figure 2).
    • Connect the green or non-insulated (copper) GROUND wire from the circuit to the green terminal on the HS-150.
    • Connect the NEUTRAL wire from the circuit to the white wire on the HS-150.
    • Connect the power wire from the circuit box (HOT/LINE) to the black wire on the HS-150.
    • Connect the power wire to the loads to the red wire on the HS-150.
  4. Put the HS-150 in the wall box and secure it to the wall box with the screws provided.
  5. Attach the cover plate.
  6. Restore power to the circuit.

Figure 1: Strip Gauge. This diagram shows the recommended wire stripping length, approximately 1/2 inch (12.7mm).

Figure 2: Line voltage wiring. This diagram illustrates the connections for the HS-150. It shows a ground wire connecting to the green terminal, a neutral wire to the white wire, the hot/line wire from the circuit box to the black wire, and the power wire to the loads connected to the red wire. It also indicates the placement of local OFF switches, lighting loads, and controlled receptacles within the room. A warning states: 'To prevent risk of damage to the unit - Do not exceed the HS-150's maximum 15 A load rating.'

Troubleshooting

Lighted card slot is OFF; no response from controlled loads in the guest room when card is inserted in slot.

  • Make sure the circuit breaker that feeds the HS-150 and hence the controlled guest room loads is on and functioning.
  • If the guest room loads are still not energized, turn power off and verify that the HS-150 is wired correctly and that all wire leads are tightly connected.
  • If loads still do not respond properly after following troubleshooting, turn OFF power to the circuit and call Technical Support at 800.879.8585.

Lighted card slot is ON; no response from controlled loads in the guest room when card is inserted in slot or removed from it.

  • Turn power off and verify that the HS-150 is wired correctly and that all wire leads are tightly connected. Turn power back ON.
  • If there is still no response from the controlled loads in the guest room, call Technical Support.

When controlling multiple circuits in a room, call Technical Support at 800.879.8585 for diagrams.

Ordering Information

Catalog NumberDescription
HS-150-WLine Voltage Card Key Switch; 120/277VAC, 50/60Hz
HS-100-WLow Voltage Card Key Switch; 24VDC/VAC
HS-FOB-W*Key Fob accessory for use when room access uses a standard key entry or other system without standard size hotel card key
HS-WP-W**Cover plate for single-gang box
HS-WPR-WCover plate for triple-gang box with decorator switch option (card slot on the right)
HS-WPL-WCover plate for triple-gang box with decorator switch option (card slot on the left)

Hotel Card Key Switches, Key Fobs and Cover Plates are available in White

* Not needed when hotel uses card key entry system.

** One HS-WP-W included with each switch.

Warranty Information

Wattstopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of Wattstopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.

INFORMATIONS RELATIVES À LA GARANTIE

Wattstopper garantit que ses produits sont exempts de défauts de matériaux et de fabrication pour une période de cinq (5) ans. Wattstopper ne peut être tenu responsable de tout dommage consécutif causé par ou lié à l'utilisation ou à la performance de ce produit ou tout autre dommage indirect lié à la perte de propriété, de revenus, ou de profits, ou aux coûts d'enlèvement, d'installation ou de réinstallation.

INFORMACIÓN DE LA GARANTÍA

Wattstopper garantiza que sus productos están libres de defectos en materiales y mano de obra por un período de cinco (5) años. No existen obligaciones ni responsabilidades por parte de Wattstopper por daños consecuentes que se deriven o estén relacionados con el uso o el rendimiento de este producto u otros daños indirectos con respecto a la pérdida de propiedad, renta o ganancias, o al costo de extracción, instalación o reinstalación.

Models: HS-150 Line Voltage Card Key Switch, HS-150, Line Voltage Card Key Switch, Voltage Card Key Switch, Card Key Switch, Key Switch

File Info : application/pdf, 2 Pages, 325.15KB

PDF preview unavailable. Download the PDF instead.

24776r2 HS-150 ii WEB (1)

References

Adobe PDF Library 17.0 Adobe InDesign 19.4 (Windows)

Related Documents

PreviewWattstopper LMDM-101 Digital Lighting Management Dimming Wall Switch Installation Guide
This guide provides installation, operation, and troubleshooting details for the Wattstopper LMDM-101 Digital Lighting Management Low Voltage Dimming Wall Switch by Legrand. Learn about its features, specifications, and connectivity.
PreviewWattstopper WS-250 Passive Infrared Wall Switch Occupancy Sensor
The Wattstopper WS-250 is a passive infrared wall switch occupancy sensor that turns lighting on and off based on occupancy and ambient light level. It replaces existing wall switches and offers features like adjustable time delay, sensitivity, and light level settings.
PreviewWattstopper Lighting Integrator Panel Installation Instructions
Comprehensive installation and setup guide for the Wattstopper Lighting Integrator Panel (LI8, LI24, LI48) by Legrand, covering component identification, wiring, low-voltage connections, smartwiring, testing, and troubleshooting.
PreviewWattstopper WS-250 Passive Infrared Wall Switch Occupancy Sensor Installation and Operation Guide
Comprehensive guide for installing, operating, and troubleshooting the Wattstopper WS-250 Passive Infrared Wall Switch Occupancy Sensor. Covers specifications, wiring, adjustments, and coverage patterns for efficient lighting control.
PreviewWattstopper LMSW Series Digital Lighting Management Low Voltage Switches Quick Start Guide
This guide provides quick start instructions, specifications, connectivity details, and troubleshooting for Wattstopper LMSW series digital lighting management low voltage switches from Legrand. Learn about Plug n' Go operation and Push n' Learn adjustments.
PreviewWattstopper DSW Series Dual Technology Wall Switch Occupancy Sensor Installation Guide
Comprehensive installation instructions, specifications, operating modes, and troubleshooting for the Wattstopper DSW Series Dual Technology Multi-Way Wall Switch Occupancy Sensors (DSW-301, DSW-302). Covers features like PIR and ultrasonic detection, manual/auto ON modes, time delays, and multi-way wiring.
PreviewWattstopper PW-311 Occupancy Sensor: Installation, Features, and Troubleshooting
Comprehensive guide to installing and configuring the Wattstopper PW-311 Passive Infrared 0-10 Volt Wall Switch Occupancy Sensor. Covers specifications, wiring, multi-way setup, emergency lighting integration, button functions, coverage patterns, advanced programming, troubleshooting, and warranty information.
PreviewWattstopper LMPS-6000 DLM Skylight Photocell Installation Guide
Installation guide for the Wattstopper LMPS-6000 DLM Skylight Photocell, detailing its integration with Legrand's DLM system for automated daylight harvesting and lighting control. Includes specifications, wiring, and maintenance.