Rinnai I-Series Plus Condensing Boiler

Technical Specifications, Diagnostics, and Parts Guide

Performance Data

To View Performance Data:

  1. Press and hold the [Down] button for two seconds (Fig 1).
  2. While holding the [Down] button, press and hold the "Domestic Hot Water" (DHW) button (hold both buttons at the same time) (Fig 1).
  3. Use the [Up] and [Down] buttons (Fig 2) to scroll to the desired information described in Table 1(A). Performance Data.
  4. The data for the performance number automatically appears in the display (Fig 3).
  5. To exit performance data, repeat step 2 above.

Fig 1. "Down" and "DHW" Buttons

Fig 2. "Up" and "Down" Buttons

Fig 3. Data Appearing in Display

Table 1(A). Performance Data

# Data Unit
01Water PressurePSI/bar¹
03Supply Temperature°F/°C¹
04Return Temperature°F/°C¹
05Freeze Protection Temperature°F/°C¹
06Exhaust Temperature°F/°C¹
11Fan FrequencyHz
17Venturi Position0=Closed, 1=Open
18Venturi Cyclesx100
20Pump Cyclesx100
21Pump Hoursx10
22Pump for Boiler0=OFF, 1=ON
23Pump for System (Pumps 1-3)0=OFF, 1=ON

¹ See "Units of Measurement" section to right.

Table 1(B). Pump for System (1-3)

Pump for System (1-3) System Pump ON OFF
Pump 1_ _ _1_ _ _0
Pump 2_ _1_ __ _0_ _
Pump 3_1_ _ __0_ _

Electrical Diagnostics

Important Safety Notes: There are a number of (live) tests required when performing electrical diagnostics on this product. Proceed with caution at all times to avoid contact with energized components inside the boiler. Only trained and qualified service technicians should attempt to repair this product. Before checking for resistance readings, disconnect the power source to the unit and isolate the item from the circuit (unplug it).

Electrical Diagram: Refer to the Wiring Diagram attached to the back of the boiler front cover.

Flame Rod: Place one lead of your meter to the flame rod and the other to the ground. When the unit is attempting to ignite, you should read more than 2 VAC.

Amp Fuses: This unit has two (2) amp glass fuses located on the PC Board. Remove the fuses and check continuity through it. If you have continuity through each fuse, then it is functioning. Otherwise, the fuse is blown and must be replaced.

Table 3. Diagnostic Points

COMPONENT WIRE COLOR VOLTAGE RESISTANCE PCB CONNECTOR PCB PIN
Power SupplyBlack-WhiteAC108~132VN/ACN2001-3
Flame RodYellow-BodyMore than 0.5VACN/ACN820
Spark ElectrodeBlack-BodyMore than 0.5VACN/ACN71
Combustion FanWhite-Black11~14VDC*N/ACN82-3
Red-Black7~48VDC*N/ACN718-19
White-Black2~14VDC*N/ACN716-18
Yellow-Black11~14VDC*N/ACN717-18
Venturi Control DeviceBlue-BlackN/A350~550ΩCN111-9, 2-9, 3-9, & 4-9
Red-BlackN/ACN118-11, 8-12, 8-13, & 8-14
Black-Black4~6VDC*N/ACN118-16 & 6-7
Gas Solenoid ValveYellow-Black11~14VDC²15~25ΩCN811-12
Exhaust ThermistorWhite-WhiteN/A59°F: 11.4-14kΩ
86°F: 6.4-7.8kΩ
113°F: 3.6-4.5kΩ
140°F: 2.2-2.7kΩ
221°F: 0.6-0.8kΩ
Disconnect the connector and measure at thermistor side.
CN73-6
Heat Exchanger ThermistorWhite-WhiteN/ACN711-14
Supply ThermistorWhite-WhiteN/ACN75-6
Return ThermistorWhite-WhiteN/ACN78-10
Freeze Protection ThermistorBlack-BlackN/A32°F: 38k-43k
50°F: 22k-26k
68°F: 14k-17k
Disconnect the connector and measure at thermistor side.
CN77-10
TransformerWhite-GreyAC108~132VN/ACN2021-2
Red-RedAC20~30V
(Possible to measure at Output terminal as substitute position)
N/ACN2023-4
Overheat SwitchBlack-BlackLess than 1VDCLess than 2ΩCN84-15
Water Pressure SensorRed-Black11~14VDCN/ACN85-9
Yellow-Black0 kPa: 655-745 mV;
200 kPa: 2,155-2,245 mV;
400 kPa: 3,655-3,745 mV
N/ACN81-9
Water Level ElectrodeWhite-White11~14VDCN/ACN813-14
Integrated PumpWhite-BlackAC108~132VN/ACN1011-2
Control PanelBlack-Black11~14VDCN/ACN61-2

¹ See "Units of Measurement" section to right.

² When the unit is operating.

Table 4. PC Board Buttons

Item # PC Board Switch # Primary Function Notes
1Button 1Parameter Setting ModeRefer to section "12.4 Parameter Settings" in Boiler Installation and Operation Manual.
2Button 2Deaeration ModeRefer to section "10. Commissioning" in Boiler Installation and Operation Manual.
3Button 3Data Transfer Mode/ Test Combustion Mode/ Flushing ModeThis is for transferring PCB data when replacing the PCB. Refer to the instructions included in the replacement parts. Also, this is used for setting the boiler into forced combustion mode and flushing mode.

Fig 4. PC Board Buttons

Parameter Settings

To access the parameter settings:

  1. Press and hold the SW 1 Button on the PC Board for five seconds (Fig 5). "00-A" appears on the display (Fig 6).
  2. Press the [Up] or [Down] arrows to select a parameter setting. Then, press the "Select" button (Fig 7).
  3. Press the [Up] or [Down] arrows to change the selection for the setting number (such as 11-A or 11-b). Then, press the "Select" button (Fig 8).
  4. To exit parameter settings and enter normal operation mode, press and hold the SW1 Button on the PC Board.

Fig 5. SW 1 Button on PC Board

Fig 6. "00-A" shown in display

Fig 7. "Up," "Down" and "Select" Buttons

Fig 8. "Up," "Down" and "Select" Buttons

For more information on parameter settings, refer to the "I-Series Plus Condensing Boiler Installation and Operation Manual."

Table 5. Parameter Settings

Parameter # Setting Description A (Default) b C d E F H
00Outdoor Temperature Sensor: Enables or disables the outdoor temperature sensor.In UseNot In Use
01Outdoor Reset Curve: (*) This parameter shows up only when selecting Outdoor Temperature Sensor "In Use" as selecting parameter number 00. For selecting outdoor reset curve, see below: Curve 1: Standard baseboard, high efficiency air handler, cast iron or panel radiators, Curve 2: Staple up radiant., Curve 3: High temperature air handler or undersized baseboard. Curve 4: Low Mass Radiant, Curve 5: High Mass Radiant, Curve 6: Radiators, Curve 7: Custom curve based on customer input.1234567
02Boost: Available when parameter 00 is selected as "A." Boost Mode increases the CH set temperature above the outdoor reset curve target when the boiler has been running on an unusually long call for heat.30 Minutes60 Minutes
03Maximum Outdoor Temperature: Available when parameter 00 is set to as "A." Sets maximum outdoor temperature the boiler will fire in CH mode and can prevent boiler from firing in warm outdoor temperatures.No Maximum77°F (25°C)
04Service Soon: SS is a time-based service indicator set during installation.Disabled0.5 Year1 Year2 Years
05Pressure Indication on Controller Panel: The current pressure will cycle on the controller display. If an external pressure gauge is present, it is permissible to change the setting to "No."YesNo
06De-Rate: This parameter is to limit maximum input when it is necessary.NoSetting 1Setting 2
28Indirect Tank: Enables the Indirect Tank Function for Pump 4.OnOff
29Indirect Tank Thermistor/Thermostat Selection: Selects the method of controlling the indirect tank.ThermostatThermistor
30Indirect Tank Supply Temperature with Thermistor Control: This parameter is available when parameter number 28 is selected as "A" and parameter number 29 is selected as "b." This selects the supply temperature for the indirect tank when using a thermostat. 180°F (Default) is the maximum supply temperature. The higher the supply temperature to the tank, the quicker the tank will heat up. If this temperature is too high, select other settings as appropriate. Ensure the indirect tank supply temperature is 18°F (10°C) higher than the set point temperature of the tank thermostat.180°F (82°C)Tank Setting Temperature +18°F (10°C)
31Indirect Tank Supply Temperature with Thermostat Control: This parameter is available when parameter number 28 is selected as "A" and parameter number 29 is selected as "A." This selects the supply temperature for the indirect tank when using a thermostat. 180°F (Default) is the maximum supply temperature. The higher the supply temperature to the tank, the quicker the tank will heat up. If this temperature is too high, select other settings as appropriate.180°F (82°C)160°F (71°C)140°F (60°C)
32Allowed indirect tank temperature drop before firing (with thermistor) This parameter is available when parameter number 28 is selected as "A" and parameter number 29 is selected as "b." This selects the differential temperature between the indirect tank setpoint temperature and thermistor reading. The smaller the value, the more frequently the indirect tank will call for heat.5.4°F (3°C)10.8°F (6°C)16.2°F (9°C)21.6°F (12°C)
33Indirect Tank Operation Option This parameter is available when parameter number 28 is selected as "A." When a 3-Way Valve and the boiler pump are to be used for recovering the indirect tank, select "b". Only 120 VAC 3-Way Valves may be used in this application.Use PumpUse 3-Way Valve
34Indirect Tank Simultaneous Heating-Up This parameter is available when parameter number 28 is selected as "A" and parameter number 32 is selected as "A." This selects the operation of the indirect tank heating by priority or simultaneously with CH. When "Indirect Tank Priority" is selected, other pumps except for the indirect tank pump will not operate while the tank is being heated. When "Simultaneous Heating with Indirect Tank and CH", all pumps may operate simultaneously. When in Simultaneous mode, if the tank does not achieve the Indirect Tank Setpoint Temperature within 60 minutes, it will transition to Indirect Tank Priority.Indirect Tank PrioritySimultaneous Heating with Indirect Tank and CH
35Indirect Tank Priority Time This parameter is available when parameter number 28 is selected as "A." This selects the time that the indirect tank will maintain priority. After this period of time passes, the indirect tank will cease to be heated and central heating will have priority. If there is still an indirect tank demand after 60 minutes passes of CH priority, indirect tank priority will begin again.60 Minutes40 Minutes90 Minutes
40CH Temperature Limitation to Allow Simultaneous Operation with Indirect Tank This parameter is available when parameter number 28 is selected as "A," parameter number 32 is selected as "A" and parameter number 33 is selected as "b." This enables CH setting limitation during simultaneous heating. This can prevent unintentionally supplying high temperature supply water to low water heating temperature applications such as floor heating. During simultaneous operation, the heating supply temperature is based on the indirect tank supply temperature. When "NO" is selected, make sure that the CH system and heating application is designed to allow for the high supply temperature.YesNo
41Linked Operation Among Each CH Pumps This parameter enables linked operation among each CH pumps. For example, when parameter b is selected and T/T 1 is active, both pump 1 and 2 are ON. The T/T wire must be connected to the T/T1 connection. This setting is primarily for an application that requires two pumps or more for one zone, such as in use with an injection loop or similar system.NoLinked Together CH Pump 1 and Pump 2Linked Together CH pump 1, pump 2 and pump 3Linked Together CH pump 1, pump 2, pump 3 and pump 4
42Linked Operation Between Main Boiler Pump and CH Pump 1: This enables the linked operation between the main boiler pump and CH pump 1. Example: when the main pump is on, pump 1 is also on.NoYes (Linked together)
43Main Pump Runs When the Target Temperature is Reached: This selects the mode of the main pump running when the target setpoint is achieved. This setting is for whether running on intervals to reduce pump operation or continuously running to reduce wait time to re-fire. Intervals are 10 minutes ON and 30 minutes OFF.ContinuouslyIntervals
44External Pump Runs When the Temperature is Reached: For selecting the mode of external pump running when the temperature is reached to setting. This is setting for whether stopping external pump running to reduce pump operation timing or operating as same as main pump operation to enable to deliver remained heat in heat exchangerSame as Main PumpDoes Not Run
45External Pump Running at Freeze Protection Operation: Selects the mode of external pump running when freeze protection operation. This is setting for whether stopping external pump running to reduce pump operation timing or operating as same as main pump operation to enable to deliver remained heat to the system for keeping system piping from freezing. But it could reduce the temperature inside heat exchanger.Does Not RunSame as Main PumpFor Warm Room Temp
46Freeze Protection Level: This selects the freeze protection level. Selecting "b" will prevent the boiler from operating in freeze protection mode more than believed necessary.Normal
47The Differential Temperature From Extinguishing Fire to Fire Again: How much temperature drop is permitted by the supply water thermistor before the boiler will fire again. When selecting "Quick", the boiler will fire more frequently and achieve more temperature controlCH Setting Temperature
Normal
168°F -182°F (75-82°C)
104°F -166°F (40-74°C)
Temperature Drop
Quick
27°F (15°C)
15°F (8°C)
Temperature Drop
Quick
15°F (8°C)
9°F (5°C)
48The Time Which Not Allow to Fire Again for CH: For selecting time which not allow to fire again for CH after shutdown burner. This is setting for whether preventing from frequently operating unit or allowing frequent operation for quick heating up again.Normal (3 Minutes)Quick (10 Seconds)
50Heating Eco Mode On Time This setting changes the on time of the heating Eco mode. This mode enables greater energy savings by reducing the length of time the boiler is operating. The output temperature of the boiler is slower in this mode.30 Minutes15 Minutes
51Air Handler Connection: The setting changes to enable to AH output with linking pump 3.NoYes
52Air Handler Post Pump Extension Setting: Extending the post Pump timing of pump 3.15 Seconds40 Seconds
60N/A: Manufacture Use OnlyManufacture Use OnlyManufacture Use OnlyManufacture Use Only
61Thermostat Usage: Changes the mode between Thermostat Usage and Central Heating Button.Thermostat UsedCH ON button used. Boiler fires based on return water temperature.
A0Gas Type: For selecting gas type when conducting gas conversion.Natural GasLiquid Propane
A1Model: Manufacture Use OnlyManufacture use onlyManufacture use only
A2Vent Material Used: This selects the venting material used. The boiler is set from the factory to be installed in a PVC venting system. If CPVC, PP, or other approved venting is used, this may be adjusted. See the section on PVC Safety Switch for more information.PVCMaterial other than PVC: CPVC, PP, or Other.
A3Altitude Setting: Sets the elevation of the boiler installation.Level 0: 0-2,000 ft (0-610m)Level 1: 2,001-5,400 (610-1646m)Level 2: 5,401-7,700 ft (1,646-2,347m)Level 3: 7,701-10,200 ft (2,347-3,109m)

Table 2. Units of Measurement

Units of Measurement Temp. Water Flow Pressure
1: English°Fgal/minpsi
2: Metric°CL/minbar

Diagnostic Codes

To Display Diagnostic Codes:

  1. Press and hold the "DHW" button for two seconds and then the [Up] button simultaneously (Fig 9).
  2. The last nine maintenance codes display and flash one after the other.
  3. To exit diagnostic codes and return the boiler to normal operation, press and hold the "DHW" button for two seconds, and then the [Up] button simultaneously.

Fig 9. "Up" and "DHW" Buttons

Table 7. Diagnostic Codes

Code Description Troubleshooting Steps
100Air Supply or Exhaust Blockage/Condensate Trap is Full• Fan current initial check error.
• Ensure condensate line and trap is not blocked.
• Ensure internal air filter is clean with no obstructions.
• Ensure high altitude setting is set properly (See High Altitude Setting).
• Ensure combustion air and exhaust vents are not blocked and the approved venting materials are being used.
• Ensure either the exhaust ring or intake cap is removed properly.
• Ensure vent length is within limits.
• Check fan for debris and ensure wheel turns freely.
• Verify fan check valve is not stuck between fan casing and burner body.
110No Ignition (Unit Not Turning On)• Ignition Error.
• Check that the gas is turned on at the boiler, gas meter, and/or propane cylinder.
• If the unit is installed in a propane system, ensure that gas is in the tank.
• Bleed all air from the gas lines.
• Check the ground wire for the PC Board.
• Ensure the flame rod wire is connected.
• Ensure the igniter is operational.*
• Ensure the venting is installed in accordance to this manual.
• Check that the surface of the electrode and flame rod are clean.
• Check gas solenoid valves for open or short circuits.*
• Verify gas orifice installed is correct for the gas system the unit is installed in.
• Check flame rod voltage to ground during ignition.
120Flame Failure• Boiler has flame failure.
• Check that the gas is turned on at the boiler, gas meter, and/or propane cylinder.
• If the unit is installed in a propane system, ensure that gas is in the tank.
• Ensure the venting is installed in accordance to this manual.
• Ensure the flame rod wire is connected.
• Ensure the gas type and inlet gas pressure are correct.
• Bleed all air from the gas lines.
• Check the ground wire to the PC Board.
• Check flame rod voltage to ground during ignition.
140Heat Exchanger Overheat• Overheat switch is tripped.
• Measure the resistance of the Overheat Switch.*
• Check the heat exchanger surface for hot spots which may indicate blockage due to scale buildup.
• Ensure the boiler pump is not locked up.
• Ensure that all of the valves in the CH circuit are open.
• Ensure the boiler and CH circuit does not have a freezing condition.
• The surface of the heat exchanger may turn to a black color as stainless steel is tempered even in normal conditions. This does not indicate an abnormal condition.
• Check for damage on the exhaust, seal, and venting.
150Venturi Control• Venturi operation error.
• Ensure the venturi motor is operating correctly.*
• Replace the gas valve assembly.
161High Outgoing Temperature• Safety shutdown because DHW outgoing temperature is too hot.
• Check sensor wiring for damage of outgoing thermistor.
• Measure resistance of outgoing thermistor.*
• Ensure the gas valve has no damage and the orifice is installed correctly.
• Replace the gas valve assembly.
170Venturi Blockage• Check the venturi and silencer for blockage.
• Before resetting this error, check if the condensate drain is block and if the venting is connected properly.
180Gas Valve Adjustment Limit• Ensure gas type is correct.
• Ensure the ground from PCB is correct.
• Ensure gas type parameter is correct.
• Please call Rinnai Technical Support.
190Electrical Grounding• Secondary circuit ground fault.
• Check all electrical components for electrical short.
210Data Transfer Error• If the PCB has been replaced, ensure the data transfer process is complete.
220Gas Valve Adjustment• Ensure a Reed switch is located properly.
• Ensure the gas valve adjustment is operating correctly.*
250Condensate Pump (Accessory)• Boiler will operate for 60 seconds.
• Confirm wire connections and harnesses are good.
• Ensure the condensate reservoir is empty and condensate pump is operational.
310Freeze Protection Thermistor• Check sensor wiring for damage.
• Measure the resistance of the sensor.
• Replace if necessary.
353Supply Thermistor• Check sensor wiring for damage.
• Clean the surface of the sensor.
• Measure the resistance of the sensor.
• Check the return thermistor.
• Replace if necessary.
363Return Thermistor• Check sensor wiring for damage.
• Measure the resistance of the sensor.
• Replace if necessary.
371Indirect Thermistor• Check if the indirect thermostat is not used at the setting for thermistor usage.
• Check sensor wiring for damage.
• Measure resistance of sensor and replace sensor, if necessary.
• Replace if necessary.
380Exhaust Thermistor• Check sensor wiring for damage.
• Clean the surface of the sensor.
• Measure the resistance of the sensor.
• Check the return thermistor.
• Replace if necessary.
393Outdoor Thermistor• Ensure that parameter number 00 is set to the appropriate position.
• Check sensor wiring for damage.
• Measure the resistance of the sensor.
• Replace if necessary.
400Pressure Sensor• Check sensor wiring for damage.
• Measure the voltage of the sensor.
• Replace if necessary.
430High/Low Water Pressure• If the water pressure is too low, add water into the system until at least 13 PSI is observed.
• Ensure there are no leaking components in the CH system.
• If the pressure is too high, adjust the pressure to a maximum of 30 PSI.
• Ensure the pressure relief valve and water fill are working correctly.
443Low Water Cut-Off (LWCO)• Ensure the LWCO device is working correctly.
• Ensure the LWCO jumper is connected properly when LWCO is not in use.
• Ensure the output is 24 V AC. If it is not, a transformer is needed.
520Solenoid Valve Circuit• Check the flame rod and wire for damage.
• Close the gas shut off valve installed near the boiler.
• Ensure the flame rod and wire are not wet.
• Check the output from the PC Board to the solenoid gas valve.
• If the output from the PC Board is abnormal, replace the PC Board.
• If the output from the PC Board is normal, replace the gas control.
540High Exhaust Temperature• Make sure boiler pump activates during operation.
• Check the exhaust thermistor wiring for damage.
• Clean the surface of the thermistor.
• Measure the resistance of the exhaust thermistor.*
• If the sensor has been replaced and the error still appears, check the return thermistor.
• If boiler is used in a hard water area, flush the DHW plate heat exchanger.
• Check the exhaust duct, seal, and venting for damage.
610Combustion Fan• Check the motor wire harness for loose or damaged connections.
• Measure resistance and voltage of motor wire harness.*
• Ensure the combustion fan spins freely.
700PC Board• PC Board circuit error.
• Replace PC Board.
710Solenoid Valve Circuit• Ensure Dip switch 5 on the PC Board is in the OFF position (default).
• Ensure the gas control wire is not loose or damaged.
• Ensure the heater circuit is not grounded.
• Replace the PC Board.
720Flame Rod• Check the flame rod and wire for damage.
• Ensure the flame rod and wire are not wet.
• If there is no issue with the flame rod or wiring, replace the PC Board.
831Indirect Tank Temperature• Indirect tank runs for more than twelve hours without cycling off.
• Check if the tank size is adequate.
• Check the thermistor location.
• Confirm that primary-secondary piping is utilized (such as low loss header, closely spaced tees, etc.)
• Check if the supply temperature for the tank is higher than the tank setting temperature (see parameter 30 in "Parameter Settings" section).
• Check sensor wiring for damage.
• Measure resistance of sensor.*
• If something is wrong on the sensor, replace the sensor.
890Freeze Issue• The boiler checks the heat exchanger temperature at the time of operation. If the temperature is too low, an error will occur.
• Check if there is freezing in the boiler or CH system.
FFFMaintenance Indicator• This code is a placeholder in diagnostic code history indicating a service provider performed maintenance or service.
• Enter this code after performing service by pressing the following buttons at the same time: [Up], [Down], and [DHW]. FFF appears on the monitor (right image).
SSService Soon (SS)• Service Soon (SS) is a time-based service indicator set during installation. See parameter 04 in the "Parameter Settings" section for more information.
• To reset the SS code, press the Central Heating (CH) button 5 times until SS disappears.
NO CODEBoiler Does Not Start Heating With a Heating Demand Present• Supply temperature or return temperature inside the boiler may be too hot.
• Ensure the pump operates properly.
• If there is a demand immediately after using DHW, wait at least three minutes for operation.
NO CODESupply Temperature is Different From the Setting Temperature on the Controller• During outdoor sensor control, the supply temperature will vary dependent on the outdoor temperature.
NO CODECH Capacity is Insufficient• Ensure the parameters are properly set for the installation.
NO CODEFan Even With No Demand• The boiler may start or operate the pump for freeze protection operation.

Table 6. Error Reset

Reset Type Description
Power ResetVenturi Control (150), Gas Valve Adjustment Limit (180), Gas Valve Adjustment(220), High Exhaust Temperature (540), and Freeze Issue (890) can be reset by shutting down power to the boiler.
Interlock ResetVenturi (170) and Solenoid Valve (520) allow only interlock rest. Please call Rinnai Technical Support.
Other ResetOther error can be reset by Indirect Tank "On/Off" button or "Central Heating" (CH) button.

Parts List and Gas Conversion Kits

The document includes exploded view diagrams illustrating the assembly of various Rinnai boiler components, such as the burner assembly, heat exchanger, fan assembly, and control panel, aiding in component identification.

This section provides a detailed parts list for Rinnai I-Series Plus models (IP060S, IP090S, IP120S, IP150S). It includes item descriptions, part numbers, and quantities for each model.

Parts List

ITEM DESCRIPTION PART NUMBER IP090S IP060S IP120S IP150S
001Front Cover Panel Assembly FF8090003061111
003Wall Mount Bracket1090005942222
007Connection Reinforcement Plate8090003071111
008Rubber BushingCF79-41020-A4444
010Residential Screw and Washer1060006451111
011Ground Screw1090000761111
012Combustion Chamber Support Plate1090005972222
015Latch1090013932222
100Burner Assembly-Large80600008211
101Burner Gasket-Large10900060911
102Burner Plate Assembly-L80600005011
103Combustion Check Valve Assembly1080001351111
105Burner Assembly-medium80600008311
106Burner Gasket-medium10900061011
107Burner Plate Assembly-M80600005211
110Combustion Fan Assembly1080001301111
111Fan Mounting Packing1090013961111
112O-ring1090006121111
113Hexagon Head ScrewZQAA0514UK3333
114Gas Valve Assembly8060000841111
115O-ring1090002522222
116Gas Connection Pipe8060000851111
117Gas Tube Bracket1090006351111
118Inlet Gas Supply Connection1060001191111
119Inlet Gas Test Port Screw1060001382222
120O-ringM10B-13-42222
121Noise Filter1060002711111
130Heat Exchanger Assembly-Large80700023411
131Heat Exchanger Assembly-Middle80700023511
136OHS Bracket1090006141111
145Condensate Trap8070002361111
147Condensation Drain Tube8070002371111
148Drain Tube at Air Intake8070002381111
150Electrode/Flame Rod Assembly8050001501111
151Electrode8050001511111
152Flame Rod8050001521111
153Electrode Gasket8050001531111
154Electrode Plate1090014011111
156Electrode Sleeve1090006201111
200Exhaust Duct Assembly8080000441111
201Exhaust Gasket1090014032222
202Intake Gasket1090014041111
203Air Supply Seal Ring1090014051111
204Exhaust Thermistor1050020241111
205O-ring1070003231111
206Exhaust Duct Gasket8080000511111
207Thermistor Screw1090006221111
210Rubber Cap1090014071111
212Exhaust Adapter Ring1080001321111
213Air Inlet Seal Ring - 2 inch1090014081111
214Air Inlet Gasket1090014091111
220Duct Assembly1080001331111
221Air Inlet Filter1080000861111
222Air Inlet Cap1080001341111
410CH Connection8070001822222
413Water Pressure Sensor Assembly8070001851111
416Plate HEX-CH Heating Connection-28070002091111
422CH Heating Return Pipe Assembly8070002081111
423CH Heating Connection Assembly8070002101111
431Heat Exchanger Pipe Connection80700019311
435Trap Drain Plug Assembly8070001951111
440HEX-CH Heating Connection Pipe8070001961111
441Heat Exchanger Pipe Connection-medium80700019711
442Air Vent8080000521111
443Secondary Heat Exchanger Outlet Fitting8070001981111
444Secondary Heat Exchanger Inlet Fitting8070001991111
445Primary-Secondary Pipe Assembly-Large80700020011
446Primary-Secondary Pipe Assembly-Medium80700020111
447Primary-Secondary Connecting Fitting8070002021111
451Pipe Bracket8090001682222
452Retention Clip8090001692222
453Pipe Bracket8090001701111
460Thermistor Sensor8050001541111
461Thermistor Sensor8050001551111
470O-ring8070002152222
472O-ring80700020411111111
473O-ring8070002052222
480O-ring8070002071111
502Clip8090001732222
504Clip80900017411
506Clip1090006385555
702PC Board - CH8050001671111
704PCB Cover8090003121111
705Power Transformer8050001581111
707Controller Unit8050001591111
708Controller Unit Harness1050020421111
710Power Cord8050001601111
712Sensor Harness-28050001681111
714Heater Ground Harness8050001621111
716Over Heat Switch8050001641111
717Water Pressure Connection Harness8050000901111
718Thermistor Sensor8050001651111
719Igniter Ground Harness1050002431111
720Guide Seal8090001761111
730Igniter Assembly (Module)8050001831111
731Igniter Plate8050001661111
800Screw1090007464444
801ScrewCP-305834444
802ScrewZBA0408UK3333
803ScrewCP-3058025252525
804Screw1090006482222
807ScrewU217-4496666
808Screw1090014175555
809ScrewCP-804521111
810Screw1090001793333
811Screw1090014163333
812Screw1090006494444
819Thermistor screwZFAB0406UK2222
821Truss Screw10900059814141414
822Screw8090001782222
824Screw8090001791111
825Screw1090007932222
828Ground Screw80900018210101010
829Screw8090003102222
840Cable Clip1090012971111
841Cable Clip8090003111111
842Cable ClipCP-90124-31111
860Mount Bracket1090006281111
861Vent Screen Set1080001041111
863Pressure Relief Valve8070002111111
864Outdoor Thermistor Kit8030000811111
888User Manual - EN8000001931111
889Installation Manual - EN8000001911111
890Tech Sheet8000001961111
891User Manual - FR8000002061111
892Installation Manual - FR8000002071111
992Gas Conversion Kit8040001241111

Gas Conversion Kits

Models Gas Type Kit Number
IP150S, IP120S, IP090S, IP060SNG/LPG804000124

PDF preview unavailable. Download the PDF instead.

d8sytbjr2xnsp8kknrzk Microsoft Publisher for Microsoft 365

Related Documents

Preview Rinnai I-Series Plus Boiler Manual Revisions: Termination Clearances and Maintenance
Technical bulletin detailing revisions to the Rinnai I-Series Plus Combi and Heat-Only Boiler Installation and Operation Manuals, specifically concerning termination clearances and maintenance warnings.
Preview Rinnai I-Series Plus Condensing Heat-Only Boiler Installation and Operation Manual
Comprehensive installation and operation manual for the Rinnai I-Series Plus Condensing Heat-Only Boiler (models IP175S, IP199S). Covers safety, installation, specifications, venting, gas supply, electrical, operation, maintenance, and troubleshooting for efficient home heating.
Preview Rinnai I-Series Plus Condensing Combi Boiler: Installation and Operation Manual
Comprehensive guide for installing and operating the Rinnai I-Series Plus Condensing Combi Boiler, covering safety, specifications, installation procedures, and maintenance.
Preview Rinnai Zen Series Gas-Fired Condensing Boilers: User and Installation Manual
Comprehensive guide for Rinnai Zen series gas-fired, condensing, wall-hung boilers (models Zen I24, I29, I34). Covers user instructions, installation guidelines, safety information, and maintenance for efficient home heating and hot water.
Preview Manuale d'Uso e Installazione Caldaie a Condensazione Rinnai Zen
Guida completa per l'uso e l'installazione delle caldaie a condensazione Rinnai Zen (modelli I24, I29, I34). Include informazioni su caratteristiche, sicurezza, funzionamento, installazione, manutenzione e risoluzione problemi.
Preview Rinnai Water Heater Energy Labels: REU-DD300VCM28 Series
Official EU energy efficiency labels for Rinnai REU-DD300VCM28 series water heaters, detailing energy class, sound levels, and annual consumption.
Preview Rinnai IP090199C Boiler Energy Efficiency Guide
EnergyGuide label for the Rinnai IP090199C boiler, detailing its Annual Fuel Utilization Efficiency (AFUE) rating of 96.0% and comparison to similar models. Information sourced from productinfo.energy.gov.
Preview Rinnai REB-KAI Series Heating Generator Product Fiche
Product specifications and energy efficiency data for Rinnai REB-KAI series heating generators, including models REB-KAI2024FF, REB-KAI2529FF, and REB-KAI3135FF, and the WF-100W_EU temperature control device.