Rinnai Technical Bulletin 200
I-Series Plus Boiler Manual Revisions for Termination Clearances and Maintenance Warning
PURPOSE
To communicate two upcoming changes to the I-Series Plus Combi and Heat-Only Installation and Operation Manuals.
PRODUCT INFORMATION
- Applicable Product: Rinnai I-Series Plus Condensing Boilers (Combi and Heat-Only)
- Applicable Models:
- Combi Models: IP060160C, IP090099C, IP090160C, IP090199C, IP120199C, IP150199C, IP175199C, IP199199C
- Heat-Only Models: IP060S, IP090S, IP120S, IP150S, IP175S, IP199S
DETAILS
Update #1:
The first update to the I-Series Plus Boiler Combi and Heat-Only Installation and Operation Manual applies to section "13. Maintenance" (Figure 1). In the second bullet point in the "Warning" section, the terminology "must be" and "must verify" are changing to "is recommended to." For example:
Current Statement:
"The boiler must be inspected annually by a licensed professional. Repairs and maintenance shall be performed by a licensed professional. The licensed professional must verify proper operation after servicing."
Revised Statement:
"The boiler is recommended to be inspected annually by a licensed professional. Repairs and maintenance shall be performed by a licensed professional. The licensed professional is recommended to verify proper operation after servicing."
Owner Maintenance
Licensed Professional Maintenance
Test the Ignition Safety Shutoff Device
WARNING
Maintenance is required to maintain safe operation of the boiler.
The boiler must be inspected annually by a licensed professional. Repairs and maintenance shall be performed by a licensed professional. The licensed professional must verify proper operation after servicing.
Keep the boiler area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
To protect yourself from harm, before performing maintenance:
- Turn off the electrical power supply by unplugging the power cord or by turning off the electricity at the circuit breaker. (The boiler controller does not control the electrical power.)
- Turn off the gas at the manual gas control valve, usually located immediately below the boiler.
- Turn off the incoming water supply. This can be done at the isolation valve immediately below the boiler or by turning off the water supply to the building.
13.1 Owner Maintenance
WARNING
If you encounter a problem that is difficult to solve, stop the operation and immediately contact a licensed professional.
Table 49: MONTHLY
Boiler Area | Piping | Venting | Boiler | |
---|---|---|---|---|
Verify the area is free of combustible materials, gasoline and other flammable vapors and liquids. Verify the area is clean from dust and obstructions. Verify the air intake area is free of any contaminants listed in the boiler Installation and Operation Manual. Any contaminants in the boiler intake air vicinity must be removed. If they cannot be removed, contact a licensed professional. | Inspect all water, gas, and condensation piping for leaks. Look for signs of leaking lines or corrosion. Confirm the condensation line is not blocked. If a condensation drain pump is used, confirm the condensation drain pump operates correctly. | Verify the boiler vent discharge and air intake is clean and free of obstructions. Check for leakage, damage, or deformation of venting. | Verify the boiler is free from any abnormal situations, such as diagnostic error codes, loud noises, leakage or other potential issues. Check that the pressure on the controller display or external pressure gauge indicates 17 to 26 PSI (117 to 180 kPa). |
Update #2:
The second update to the I-Series Plus Boiler Combi and Heat-Only Installation and Operation Manual applies to the two sections below:
- Section in Manual: 5.5.5 Non-Direct Vent (Room Air) Termination Clearances – Table 23, Reference B (Clearance to window or door that may be opened) (Figure 2).
- Section in Manual: 5.5.2 Direct Vent (Concentric and Twin Pipe) Termination Clearances – Table 15, Reference B (Clearance to window or door that may be opened) (Figure 3).
In both sections, Reference B for Canadian installations is being modified to reflect the new clearances as shown in the table below.
Room Air: Termination Clearances
Diagram showing clearances for non-direct vent (room air) termination. Key elements include:
- Clearance above grade, veranda, porch, deck, or balcony (Ref. B)
- Clearance to window or door that may be opened (Ref. B)
- Clearance to permanently closed window
- Vertical clearance to ventilated soffit
- Inside corner detail
- AIR SUPPLY INLET
- VENT TERMINAL
- AREA WHERE TERMINAL IS NOT PERMITTED
Table 23
Ref. A also applies to anticipated snow line | TERMINATION | Clearance in | ||||||
---|---|---|---|---|---|---|---|---|
SNOW | Fixed V | Operable V | B | |||||
Ref | Description | Canadian Installations (CSA B149.1) | U.S. Installations (ANSI Z223.1/NFPA 54) | |||||
Clearance above grade, veranda, porch, deck, or balcony | Other than Direct vent (Room Air) 12 in. (30 cm) | Other than Direct Vent (Room Air) 12 in. (30 cm) | ||||||
B | Clearance to window or door that may be opened | 36 in. (91 cm) | 4 ft (1.2 m) below or to side of oper 1 ft (300 mm) above opening | |||||
C | Clearanento permanently closed window | |||||||
D | Vertical clearance to ventilated soffit, located above the terminal within a horizontal vence of 2 ft (61 cm) from the center line of the terminal |
5.5.2 Direct Vent (Concentric and Twin Pipe): Termination Clearances
The information below applies to Concentric and Twin Pipe.
Diagram showing clearances for direct vent (concentric and twin pipe) termination. Key elements include:
- Clearance above grade, veranda, porch, deck, or balcony (Ref. B)
- Clearance to window or door that may be opened (Ref. B)
- Clearance to permanently closed window
- Clearance to unventilated soffit
- Clearance to outside corner
- Clearance to inside corner
- Clearance to each side of center line extended above meter/regulator assembly
- Clearance to service regulator vent outlet
- Inside corner detail
- AIR SUPPLY INLET
- VENT TERMINAL
- AREA WHERE TERMINAL IS NOT PERMITTED
Table 15
Ref. A also applies to anticipated snow line | TERMINATION | Clearance in | ||||||
---|---|---|---|---|---|---|---|---|
SNOW | Fixed V | Operable V | B | |||||
Ref | Description | Canadian Installations (CSA B149.1) | U.S. Installations (ANSI Z223.1/NFPA 54) | |||||
Clearance above grade, veranda, porch, deck, or balcony | Direct Vent (Indoor Unit) 12 in. (30 cm) | Direct Vent (Indoor Unit) 12 in. (30 cm) | ||||||
B | Clearance to window or door that may be opened | 36 in. (91 cm) | 12 in. (30 cm) | |||||
C | Clearance to permanently closed window | 12 in. (30 cm) | ||||||
D | Clearance to unventilated soffit | |||||||
E | Clearance to outside corner | |||||||
F | Clearance to inside corner | |||||||
G | Clearance to each side of center line extended above meter/regulator assembly | |||||||
H | Clearance to service regulator vent outlet |
Table 23, Reference B
Table 15, Reference B
Ref B (Canadian Installations) REVISED Clearances:
Ref | Description | Canadian Installations (CSA B149.1) |
---|---|---|
B | Clearance to window or door that may be opened |
|
The above clearance adjustments are required to ensure compliance with the CSA B149.1 standard, as well as ensure a safe and proper installation.
NEXT STEPS
The above changes are being announced in this technical bulletin for immediate notification and will appear in the next revision of the boiler Installation and Operation manual.
The Installation and Operation manual is packaged with the boiler, or can be accessed online at www.rinnai.us or www.rinnai.ca.