Engineering Specification
Model: ES-TR2
LEAD FREE Series TR2 Transition Risers
Customizable
Sizes: 2" – 3"
Series TR2 Transition Risers are used to connect the main potable water supply to the building drinking water system or fire supply to the building overhead fire system. The fitting passes under the foundation without joints and extends up through the floor. Provided with either an MNPT or FNPT (ASME B1.20.1), Flanged [ANSI B16.5 150], or industry standard grooved-end connection (AWWA C606) for easy connection to either the underground supply (PVC, Ductile Iron, or Copper Pipe) or drinking water supply/ overhead fire sprinkler system. Note that FNPT or Flanged connections require separate adapter. The TR2 features Lead Free Pipe construction to comply with Lead Free installation requirements.
Watts Transition Risers are precision engineered and manufactured to provide exceptional reliability and reduce installation time & labor costs associated with field assembly. In accordance with NFPA 24 and numerous regional plumbing codes, the UL/FM approved Transition Risers replace numerous fittings, elbows & spools and reduce the possibility of leaks or failure in comparison to traditional installation methods and materials. Factory tested integrity ensures the highest quality installation. The use of stainless steel significantly increases the reliability and life of the riser.
Features
- Cost savings
- Corrosion resistant stainless steel construction, type 304
- Ease of installation and lightweight allow one person to position and handle the riser
- Minimal site preparation; joint restraint one-piece construction reduces time and labor; no missing parts, no leaks; easily identifiable for approvals
- UL/FM and NSF Approved
- Sizes: available 2", 21⁄2", and 3"
- ASME B1.20.1 MNPT/FNPT Thread Options
- ANSI B16.5 for Class 150 Flange Option
- AWWA C606 Outlet
Specification
Transition Riser shall be installed as indicated on the plans. Riser shall be composed of a single extended 90 degree fitting of fabricated 304 stainless steel pipe, maximum working pressure 200psi (14 bar). The fitting shall either have a grooved end, flanged, or MNPT or FNPT connection on the outlet (building) or inlet (underground) side. The Transition Riser shall be a Watts Series TR2.
Diagram shows a 90-degree pipe fitting representing the riser. Text indicates custom lengths are available from 3' to 16', with the sum of leg lengths not exceeding 19'.
Diagram illustrates the riser installed under a building floor, connecting to a water supply and passing through the floor into a building. Arrows indicate water flow.
NOTICE: Inquire with governing authorities for local installation requirements. The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Standards
NFPA: Designed to allow the contractor to conform to NFPA 24.
Where a riser is close to building foundations, underground fittings of proper design and type shall be used to avoid pipe joints being located under the foundations.
Approvals
Fittings: FM class 1920, UL HKQA (2", 21⁄2", 3").
Certifications: UL Certified, FM Certified, NSF Certified to NSF/ANSI 61-G and NSF/ANSI 372.
Pipe
Meets AWWA C220.
End Connections
Vertical and Horizontal End:
- Meets AWWA C-606 dimensions for roll grooved pipe
- Meets ASME B1.20.1 for MNPT / FNPT Thread
- Meets ANSI B16.5 for Class 150 Flange
End Connections Options
Standard Configuration: GRVXMNPT - Groove x Male NPT
Optional Configurations - see your local agent:
- GRVXGRV - Groove x Groove
- MNPTxMNPT - Male NPT x Male NPT
The following adapters are also available for connection to the MNPT portion of the riser:
- ASME B1.20.1 MNPT to FNPT converter
- 150 RF 304/L Threaded Flange
Note: Adapters add between 1" and 21⁄2" to riser leg length when installed - depending on riser diameter.
Dimensions – Weights
Schematic shows a 90-degree pipe fitting with dimensions labeled A, B, and C. Connection types are indicated for different options: 'Grooved or MNPT Options' for dimension A, and 'Grooved, MNPT, FNPT or Flanged Options' for the end connection.
DESIGN PROOF PRESSURE
SIZE (in.) | DESIGN PROOF PRESSURE (psi) | (bar) |
---|---|---|
2 | 200 | 13.7 |
21⁄2 | 200 | 13.7 |
3 | 200 | 13.7 |
DIMENSIONS AND WEIGHTS
SIZE | A (OD) | B (Rise) | C (Run) | WEIGHT | ||||
---|---|---|---|---|---|---|---|---|
in. | mm | ft. | cm | ft. | cm | lbs | kg | |
2 | 23⁄8 | 60 | 4 | 122 | 4 | 122 | 29 | 13 |
5 | 152 | 6 | 183 | 37 | 17 | |||
6 | 183 | 6 | 183 | 40 | 18 | |||
44 | 20 | |||||||
21⁄2 | 27⁄8 | 73 | 4 | 122 | 4 | 122 | 46 | 21 |
4 | 122 | 6 | 183 | 58 | 26 | |||
5 | 152 | 6 | 183 | 64 | 29 | |||
6 | 183 | 6 | 183 | 69 | 32 | |||
3 | 31⁄2 | 89 | 4 | 122 | 4 | 122 | 60 | 27 |
4 | 122 | 6 | 183 | 76 | 34 | |||
5 | 152 | 6 | 183 | 83 | 38 | |||
6 | 183 | 6 | 183 | 91 | 41 |
NOTICE
Inquire with governing authorities for local installation requirements.
The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.