Description

Interface between phase cut controllers and valves or actuators.

Features

  • Input: 0 to 20 Vdc phase cut
  • Output: 0 to 10 Vdc
  • Two operating ranges, for magnetic valves and damper actuators
  • Inputs and outputs short-circuit-proof and protected against polarity reversal

Product Number

SEZ91.6

Warning/Caution Notations

WARNING: ⚠️Personal injury/loss of life may occur if a procedure is not performed as specified.
CAUTION:Equipment damage may occur if the user does not follow a procedure as specified.

Application

The interface is used when operating 0 to 10 Vdc magnetic valves, Flowrite™ valves or OpenAir™ damper actuators in conjunction with controllers with a 0 to 20 Vdc phase cut output signal.

Function

  • The SEZ91.6 interface is used in retrofit projects.
  • An operating voltage of 24 Vac is required for the interface.
  • All terminal connections are short-circuit-proof and protected against polarity reversal.

Ordering

When ordering, specify the quantity, product number and description.

Mechanical Design

  • The plastic housing accommodates the printed circuit board and the terminal connections.
  • The housing is sealed with a plastic, shrink-wrapped sleeve.
  • The SEZ91.6 has a white label.
  • The two different operating ranges are selected by connection to the relevant input terminal.

Mounting

Provided the interface is mounted in a dry environment, it can be located wherever there is sufficient space and in any orientation:

  • In the control panel on DIN rails or in the trunking
  • Unit-mounted
  • In ceiling voids
  • In remote distributor boxes

Diagram Description (Figures 3 & 4): Visuals show the SEZ91.6 interface mounted on DIN rails within a control panel and also shown as a unit mounted within a distributor box.

Specifications

Value
Supply Voltage (Output Side)Operating voltage24 Vac ±20%, Class 2
Frequency50/60Hz
Power consumption, excluding field devices0.5 VA
InputsFor magnetic valves
Type0 to 20 Vdc phase cut
Load impedance2K ohm
Maximum voltage (phase cut)30 Vdc
Operating range10 to 20 Vdc phase cut
For damper actuators
Type0 to 20 Vdc phase cut
Load impedance2K ohm
Maximum voltage (phase cut)30 Vdc
Operating range2 to 12 Vdc phase cut
OutputsType0 to 10 Vdc
Minimum load impedance5K ohm
Maximum output voltage12 Vdc
ConnectionsScrew terminals for maximum 2 x 14 AWG

Specifications, Continued

Value
Weight/DimensionsWeight (including packaging)0.13 lb. (0.06 kg)
Dimensions (L x W x H)2.24 x 0.87 x 0.71 inches (57 x 22 x 18 mm)
Ambient ConditionsOperation Temperature32 to 122°F (0 to 50°C)
Operation HumidityMaximum 85% rh
Storage Temperature-13 to 149°F (-25 to 65°C)
Storage HumidityMaximum 95% rh
Agency ApprovalsConforms to CE requirements

Connection Terminals

Input Side (Figure 5)

  • G0: System neutral
  • Y: Control signal 0 to 20 Vdc phase cut for damper actuators
  • G+: Control signal "Plus" (for phase cut, 100 Hz half-wave)
  • Y: Control signal 0 to 20 Vdc phase cut for magnetic valves

Output Side (Figure 6)

  • Y: Control signal, 0 to 10 Vdc
  • G0: System neutral
  • G: System voltage 24 Vac
  • G0: System neutral

Wiring Diagrams

Figure 1. KLIMO Controller.

Description: A graph illustrating the KLIMO controller's operating ranges. The Y-axis represents VDC Phase-cut, and the X-axis represents W (Temperature). It shows the magnetic valve operating range between 10 and 15 Vdc phase-cut, and the damper actuator operating range between 2 and 10 Vdc phase-cut. Xp denotes a point on the magnetic valve range.

Figure 2. Effective Range.

Description: A graph depicting the effective operating range of the SEZ91.6 interface. The Y-axis shows VDC (Output signal), and the X-axis shows VDC phase-cut (Input signal). It indicates that input signals above 12 Vdc phase-cut correspond to the damper actuator range, and input signals between 10 and 20 Vdc phase-cut correspond to the magnetic valve range.

Figure 7. SEZ91.6 Interface with Magnetic Valves.

Description: This diagram illustrates the wiring between a controller (N1, e.g., KLIMO RDK99), the SEZ91.6 interface (U1), and a magnetic valve (Y1, e.g., MX...461..., M2H...FY). It shows connections for 24 VAC power, input signals (Y, G+, G0), and output signals (Y, G0). A note indicates G0 – (Ym) is recommended for MX...461...

Figure 8. SEZ91.6 Interface with OpenAir Damper Actuators.

Description: This diagram shows the wiring for connecting the SEZ91.6 interface (U1) to an OpenAir damper actuator (Y1, e.g., GBB161.1E) and a controller (N1, e.g., KLIMO RDK99). It details the 24 VAC power and signal connections (Y, G+, G0 for input; Y, G0 for output). A position feedback (V) is also indicated.

Dimensions (Figure 9)

Description: A diagram showing the physical dimensions of the SEZ91.6 interface. The length is 2.24 inches (57 mm), the width is 0.87 inches (22 mm), and the height is 0.71 inches (18 mm). The diagram labels the input and output sides.

PDF preview unavailable. Download the PDF instead.

3950 Acrobat Distiller 3.01 for Windows

Related Documents

Preview Siemens OpenAir GCA Spring Return Rotary Electronic Damper Actuator Installation Instructions
Installation guide for Siemens OpenAir GCA Series spring return rotary electronic damper actuators, covering mounting, wiring, manual override, and specifications for HVAC applications.
Preview Siemens SKD...U Electronic Valve Actuator Installation Instructions
Comprehensive installation guide for Siemens SKD...U Electronic Valve Actuators, covering product details, mounting procedures, wiring diagrams, and start-up operations for Flowrite 599 Series valves.
Preview Siemens SAX Electronic Valve Actuator Installation Instructions
Comprehensive installation guide for Siemens SAX Electronic Valve Actuators, covering product description, prerequisites, mounting, wiring, and commissioning procedures for both proportional and three-position control models.
Preview Siemens OpenAir GVD/GKD Series Electronic Damper Actuator Installation Instructions
Comprehensive installation guide for Siemens OpenAir GVD/GKD Series electronic damper actuators, designed for UL Listed fire/smoke and smoke control dampers. Covers product details, prerequisites, installation steps, wiring diagrams, EFL installation, maintenance, and dimensions.
Preview Siemens Flowrite 599 Series Valve and Actuator Assembly Selection Guide
This technical bulletin provides a comprehensive guide for selecting Siemens Flowrite 599 Series valve and actuator assemblies. It includes detailed instructions, selection graphs (Figures 1-3), and extensive tables (Tables 1-12) listing specifications, part numbers, and compatible combinations for various valve types, sizes, and applications.
Preview Siemens SSC Series Electronic Valve Actuator Installation Guide
Installation instructions for the Siemens SSC Series Electronic Valve Actuator, covering product description, prerequisites, mounting, wiring, calibration, start-up, troubleshooting, and dimensions. Includes model numbers SSC61U, SSC61.5U, SSC81U, and SSC81.5U.
Preview Siemens OpenAir GRD Series Electronic Damper Actuator Installation Instructions
Installation instructions for the Siemens OpenAir GRD Series Electronic Damper Actuator, designed for UL Listed Fire/Smoke and Smoke Control Dampers. Covers product description, parts, prerequisites, installation, wiring, EFLs, maintenance, and dimensions.
Preview Siemens Desigo PXC4.E16 Automation Station: Features, Specifications, and Technical Data
Comprehensive technical overview of the Siemens Desigo PXC4.E16 automation station, detailing its features, functions, connectivity options (BACnet/IP, KNX PL-Link, Modbus), technical specifications, and installation guidelines for HVAC and building control systems.