3.8kW Single-Phase Switched Automatic Transfer Switch PDU, 10 Outlets, TAA Compliant

Overview

The Tripp Lite PDUMH20HVATNET Switched Automatic Transfer Switch (ATS) PDU provides a redundant power solution for single-corded network devices. It features dual input cords that connect to separate PRIMARY and SECONDARY power sources. The ATS unit maintains continuous output to all connected devices, typically drawing power from the primary input. If the primary power source becomes unstable or fails, the ATS automatically switches to the secondary power source within milliseconds, ensuring uninterrupted operation until the primary input is restored and stable. This PDU also offers individually controllable output receptacles and a built-in network interface for remote management. It supports fault-tolerant hot-swappable UPS protection when used with a single UPS, and fully redundant UPS protection when each cord is connected to a separate UPS system. Advanced configurations are supported, including separate mains circuits, backup generators, and even separate utility power grid feeds. The on-board ATS processor continuously evaluates power quality on both inputs to prevent switching to a secondary source of lower quality. Front panel LEDs indicate primary or secondary power availability. The integrated LX Platform network management interface card enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet, or SSH, supporting 10/100 Mbps auto-sensing Ethernet communication.

Key Features

Specifications

Category Details
INPUT PDU Input Voltage 200-240V DUAL INPUT
Recommended Electrical Service Two single-phase 16/20A 200-240V circuits
Maximum Input Amps 16 (Agency de-rated to 16A continuous ⚠️)
PDU Plug Type (2) IEC-320 C20
Input Phase Single-Phase
Input Cord Details Set of two inputs connect to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 12
Input Cord Length (m) 3.66
OUTPUT Output Capacity Details 3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (8) C13; (2) C19
Output Nominal Voltage 200-240V
Overload Protection n/a
Customized Load Management Receptacles 8 individually switched C13 output receptacles ?
USER INTERFACE, ALERTS & CONTROLS Front Panel LCD Display Digital display reports total PDU output current in amps ?
Front Panel LEDs 8 LEDs display power on-off status for each C13 output receptacle ?, plus 2 additional LEDs to indicate input power status for primary (?) and secondary (?) inputs
Switches Toggle switch ⚙️ near digital display enables the setting of "HI" for 220, 230 or 240V nominal applications or "LO" for 200 or 208V applications
PHYSICAL Form Factors Supported 1U rackmount ?️
Material of Construction Metal ?
Minimum Required Rack Depth (cm) 46.48
Minimum Required Rack Depth (inches) 18.3
PDU Form Factor Horizontal (1U) ?️
Shipping Dimensions (hwd / cm) 13.72 x 52.83 x 59.44
Shipping Dimensions (hwd / in.) 5.40 x 20.80 x 23.40
Shipping Weight (kg) 7.71
Shipping Weight (lbs.) 17.00
Unit Dimensions (hwd / cm) 4.4 x 43.9 x 37.6
Unit Dimensions (hwd / in.) 1.72 x 17.3 x 14.8
Unit Weight (kg) 4.67
Unit Weight (lbs.) 10.30
ENVIRONMENTAL Operating Temperature Range 0°C ~ 40°C (32°F ~ 104°F) ?️
Storage Temperature Range -30°C to +50°C (-22°F to +122°F) ❄️?
Relative Humidity 5-95% (non-condensing) ?❌
COMMUNICATIONS SNMP Compatibility Pre-installed LX platform interface ? provides remote monitoring ? via Java-free HTML5 web interface ?, telnet ?, SSH ?, and SNMP ? management systems
SPECIAL FEATURES High Availability PDU Features Auto Probe Monitoring and Reboot (included) ?
STANDARDS & COMPLIANCE Certifications Tested to UL 60950 (USA, Canada) ✔️, CE (Europe) ✔️, Class A (Emissions) ✔️, NOM (Mexico) ✔️, RoHS Complaint ✔️, TAA Compliant ✔️
WARRANTY Product Warranty Period (Worldwide) 2-year limited warranty ?️

Package Includes

Notes

© 2021 Tripp Lite. All rights reserved. ⚖️ All product and company names are trademarks or registered trademarks of their respective holders. ™® Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. ? Specifications are subject to change without notice. ⚠️ Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. ? See a list of Tripp Lite's testing agencies: tripplite.com/products/product-certification-agencies ?

Models: PDUMH20HVATNET, Single-Phase Switched Automatic Transfer Switch

File Info : application/pdf, 4 Pages, 159.31KB

PDF preview unavailable. Download the PDF instead.

mmo 8180642 1620382594 041 11658

References

iTextSharp™ 5.5.13.2 ©2000-2020 iText Group NV (AGPL-version); modified using iTextSharp™ 5.5.13.2 ©2000-2020 iText Group NV (AGPL-version)

Related Documents

Preview Tripp Lite PDUMH30HVATNET: Single-Phase Switched Rack-Mount ATS PDU
Explore the features and specifications of the Tripp Lite PDUMH30HVATNET, a 5-5.8kW single-phase switched rack-mount Automatic Transfer Switch (ATS) PDU designed for reliable power distribution in IT environments.
Preview Tripp Lite PDU3EVN6G30B 3-Phase Monitored 0U Vertical PDU - Technical Specifications
Detailed technical specifications and features for the Tripp Lite PDU3EVN6G30B, a 3-Phase Monitored 0U Vertical Power Distribution Unit with 48 outlets, 10kW capacity, HTML5 network interface, and rackmount compatibility.
Preview Tripp Lite PDU3MV6L2130: 3-Phase Metered Rackmount PDU - Technical Specifications
Detailed specifications and features for the Tripp Lite PDU3MV6L2130, a 3-phase metered rackmount power distribution unit with 48 outlets, 8.6kW capacity, and digital load metering.
Preview Tripp Lite PDUBHV20B: 220-240V 13A Single-Phase Hot-Swap PDU with Manual Bypass
The Tripp Lite PDUBHV20B is a 220-240V, 13A single-phase hot-swap PDU designed for critical IT equipment requiring 24/7 uptime. It features manual bypass for uninterrupted UPS maintenance, dual C20 inlets, four BS1363 outlets, and an optional ECO power-saving feature. Mountable in 2U rack space or on a wall.
Preview Tripp Lite PDU1215 / PDU121506 Rack PDU Technical Specifications and Dimensions
Detailed technical drawing and specifications for Tripp Lite PDU1215 and PDU121506 rack-mountable power distribution units, including dimensions, outlet configuration, and material tolerances.
Preview Tripp Lite N48S-2L24L-10: 1U Preloaded Fiber Panel with 2x 24F OS2 Singlemode Cables
Detailed specifications and features for the Tripp Lite N48S-2L24L-10, a 1U preloaded fiber panel with two 10-meter OS2 singlemode LC duplex trunk cables, designed for efficient cable management and cost savings in data center and network environments.
Preview Tripp Lite PowerAlert Element Manager Installation Guide
This guide provides comprehensive instructions for installing, maintaining, upgrading, and troubleshooting the Tripp Lite PowerAlert Element Manager (PAEM) software, designed for managing LX Platform devices.
Preview PowerAlert Device Manager (PADM) 20.0.0 User's Guide
User's Guide for Tripp Lite's PowerAlert Device Manager (PADM) version 20.0.0. Learn to configure, monitor, and manage Tripp Lite LX Platform devices, UPS systems, and PDUs. Covers web interface, network settings, security, logging, and more. Essential for IT professionals managing network infrastructure.