M9203-AGB-2Z JCI 24Vac, 24Vdc, Floating Control or Two Position, 27 lb-in Torque, 90 second Power On run time, 48" Appliance Cable with 1/2" Conduit Connectors Spring Return Direct Coupled Actuator with 1 SPDT Auxiliary Switch
File Info : application/pdf, 10 Pages, 452.14KB
DocumentDocument*3417918G* M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions M9203-AGA-2, M9203-AGB-2, M9203-AGA-2Z, M9203-AGB-2Z Part No. 34-1791-8, Rev. G Issued May 2021 Applications The M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators are direct-mount actuators that operate on AC/DC 24 V power. These bidirectional actuators do not require a damper linkage, and are easily installed on round shafts from 1/4 to 1/2 in. (6 to 12 mm) or square shafts from 1/4 to 5/16 in. (6 to 8 mm) using the standard shaft clamp included with the actuator. A single M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuator provides 27 lb·in. (3 N·m) running and spring return torque. An integral line voltage auxiliary switch, available only on the M9203-xxB-2(Z) models, indicates end-stop position, or performs switching functions within the selected rotation range. M9203-AGA-2(Z) actuators include plenum-rated cables and are specially configured for installation in spaces used for environmental air-handling purposes other than ducts and plenums as specified in National Fire Protection Association (NFPA) 70: National Electrical Code section 300.22(C), Other Space Used for Environmental Air. The space over a hung ceiling used for environmental air handling purposes is an example of the type of space for which these actuators are configured. IMPORTANT: Use this M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuator only to control equipment under normal operating conditions. Where failure or malfunction of the actuator could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the actuator. IMPORTANT : Utiliser ce M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuator uniquement pour commander des équipements dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du actuator risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du actuator. Installation The M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators mount directly to the surface in any convenient orientation using two No. M3.5 x 9.5 mm self-drilling sheet metal screws and the anti-rotation bracket (parts included with the actuator). No additional linkages or couplers are required. Electrical connections are color-coded and identified with numbers permanently marked on the actuator cable. A tag on the actuator cable identifies the electrical connections and wiring details are included on the actuator housing. M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators 1 Installation Instructions IMPORTANT: Do not install or use this M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuator in or near environments where corrosive substances or vapors could be present. Exposure of the electric actuator to corrosive environments may damage the internal components of the device, and will void the warranty. Dimensions 3-15/16 (82) Parts Included · M9203-AGx-2(Z) actuator · M9203-603 adjustable stop kit · M9000-604 anti-rotation bracket with two No. M3.5 x 9.5 mm, pan-head, cross-recessed (Phillips), self-drilling and self-tapping screws Special Tools Needed · 10 mm wrench/socket · drill with Phillips bit, driver size 1 45/64 (18) 2-1/4 (57.5) 15/64 (6) 10 30 50 70 90 25/32 (20) 6-3/8 (162) 4-55/64 (123.6) 4-15/64 (107.5) DA RA 5/16 (8) Slot Length 1/4 (6.5) Slot Width 47/64 (18.7) FIG:M9203_AGx_dim 1-35/64 (39.2) 1-1/8 (28.7) Figure 1: M9203-AGx-2 Series On/Off and Floating Point Electric Spring Return Actuator Dimensions, in. (mm) 2 M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions Accessories Table 1: Accessories and Replacement Parts (Order Separately) Code Number Description DMPR-KC003 7 in. (178 mm) Blade Pin Extension (without bracket) for Johnson Controls® Direct-Mount Damper Applications (quantity 1) Note: Available with damper and may be ordered separately M9000-322 Weathershield Kit for Damper Application of VA9104, VA9203, VA9208, and VA9308/9310 Series Electric Actuators (quantity 1) M9000-400 Jackshaft Linkage Adapter Kit (quantity 1) M9000-560 Ball Valve Linkage Kit for applying M9104, M9203, and M9208 Series Electric Actuators to VG1000 Series Valves (quantity 1) M9000-561 Thermal Barrier Kit for M9000-560 Ball Valve Linkage. Extends M(VA)9104, M(VA)9203, M(VA)9208, and M(VA)9308/9310 Series Electric Actuators applications to include low pressure steam (quantity 1) M9000-604 Replacement Anti-Rotation Bracket Kit for M9203, M9208, M9220, and M9300 Series Electric Actuators (quantity 1) M9000-606 Position Indicator for Damper Applications (quantity 5) M9000-607 Position Indicator for VG1000 Series Ball Valve Applications (quantity 5) M9203-100 Remote Mounting Kit with Crankarm Kit (quantity 1) M9203-110 Universal Mounting Kit without Crankarm Kit (quantity 1) M9203-115 Universal Mounting Kit with Crankarm Kit (quantity 1) M9203-150 Crankarm Kit (quantity 1) M9203-250 Remote Mounting Kit with Crankarm Kit and Damper Linkage for D1300 Dampers (quantity 1) M9203-601 Replacement Standard Coupler Kit (with Retainer) for Mounting M9203 Series Electric Spring Return Actuators (quantity 1) M9203-602 Replacement Retainer for M9203 Series Electric Spring Return Actuators (quantity 5) M9203-603 Adjustable Stop Kit for M9203 Series Electric Spring Return Actuators (quantity 1) M9000-700 Universal Ball Valve Linkage Kit (Quantity 1) Mounting The M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators can be easily installed on dampers with round shafts from 1/4 to 1/2 in. (6 to 12 mm) or square shafts from 1/4 to 5/16 in. (6 to 8 mm) using the standard shaft coupler included with the actuator. If the damper shaft extends less than 3.31 in. (84 mm), see the Removable Coupler section for further instructions. If the damper shaft extends less than 0.79 in. (20 mm), install a shaft extension recommended by the damper manufacturer. M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions 3 Counterclockwise (CCW) Spring Return Direction Clockwise (CW) Powered Operation For CCW spring return direction, mount the actuator to the damper shaft so that Side A of the actuator is away from the damper as illustrated in Figure 2. With power applied, the actuator drives CW from the 0° position and spring returns CCW. Removable Coupler If the damper shaft extends less than 3.31 in. (84 mm), mount the coupler on the face of the actuator closest to the damper. If the damper shaft extends less than 0.79 in. (20 mm), a shaft extension is required to mount the actuator. 10 30 50 70 90 FIG:exp_cplr DA RA FIG:M9203_AGx_A Figure 2: Actuator Side A Clockwise (CW) Spring Return Direction Counterclockwise (CCW) Powered Operation For CW spring return direction, mount the actuator to the damper shaft so that Side B of the actuator is away from the damper as illustrated in Figure 3. With power applied, the actuator drives CCW from the 0° position and spring returns CW. 50 30 10 70 90 Figure 4: Changing the Coupler Position To change the coupler's position, see Figure 4 and proceed as follows: 1. Mount the coupler on either Side A or Side B of the actuator as determined by the shaft length. 2. Snap the locking clip securely into the coupler retention groove to retain the coupler. Mounting the Actuator To mount the actuator, proceed as follows: 1. See the dimensions in Figure 5 and Table 2 to ensure the correct positioning of the anti-rotation bracket. 10 30 50 70 90 10 30 50 70 90 DIM. A DA RA DA RA DIM. B RA DA Figure 5: Positioning the Anti-Rotation Bracket Table 2: Dimensions from Anti-Rotation Bracket to Shaft Center Shaft Diameter, Dimension A, Dimension B, in. (mm) in. (mm) in. (mm) 1/4 to 1/2 (6 to 12) 4-27/32 (123) 3-5/8 (92) FIG:M9203_AGx_B Figure 3: Actuator Side B 4 M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions FIG:M9203_AGx_brkt IMPORTANT: The tab on the anti-rotation bracket must fit midpoint in the actuator slot. Positioning the tab midpoint in the slot prevents actuator binding and premature wear, and makes actuator removal easier. 2-1/4 (57.5) 3-1/4 (82.5) Self-Drilling Sheet Metal Screws (2) Anti-Rotation Bracket 7. Hold the actuator perpendicular to the damper shaft. Evenly hand-tighten each nut on the coupler U-bolt, then torque the coupler U-bolt nuts to 100 to 125 lb·in. (11 to 14 N·m). 8. Apply power long enough for the actuator to travel a full stroke. Verify that the actuator rotates freely throughout the range. Limiting Rotation Range Using M9203-603 Adjustable Stop Kit The actuator is factory set for 95° rotation, and its range is limited in 5° increments to a minimum of 35°. A stroke-limiting stop can be attached in the field to the shaft coupler side of the actuator to reduce the rotation range. Attaching the stroke-limiting stop in the furthest mounting position reduces the rotation range of the actuator by 5°. Each progressive mounting position reduces the rotation range an additional 5°. 1. Check that the damper blade is visible or its position is permanently marked on the end of the damper shaft, as illustrated in Figure 7. FIG:M9203_ Anti-Rotn_Mntg_Brkt_Posn FIG:FIdaG:dmapemrpsos Damper Frame Figure 6: Anti-Rotation Mounting Bracket 2. Bend or cut the anti-rotation bracket to fit the damper frame or duct as illustrated in Figure 6. Note: The anti-rotation bracket can be bent to fit a round damper. 3. Mark or drill mounting holes in the damper frame or duct using the anti-rotation bracket as a guide (based on the measurements obtained in Table 2 and Figure 5). 4. Secure the anti-rotation bracket to the damper frame or duct using the two No. M3.5 x 9.5 mm self-drilling sheet metal screws provided. IMPORTANT: Do not overtighten the mounting screws to avoid stripping the threads. Be certain that the tab on the anti-rotation bracket remains properly positioned in the slot on the actuator, and that the actuator remains parallel to the mounting surface. 5. Slide the actuator onto the damper shaft, and position the anti-rotation bracket tab into the slot at the bottom of the actuator as illustrated in Figure 6. 6. Rotate the damper blade(s) to the desired position if the power is lost. Figure 7: Damper Position 2. Position the stroke-limiting stop in the serrated slot with its leading edge at the scale position matching the desired stroke. 3. The product label marks hole positions for the M3-0.5 x 8 mm self-tapping screw provided with the adjustable stop kit. Drive the screw through the slot in the adjustable stop and into the actuator face over a marked hole position. (See Figure 8.) Note: The minimum rotation range is 35°. Figure 8: Limiting Rotation Range FIG:strk_limit M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions 5 Wiring See Figure 9 and Figure 10 to wire the applicable M9203-AGx-2(Z) Series model. Floating Control, Four Wire RA RA DA DA BLK RED GRY ORN 12 34 ~ -+ 24 VAC 24 VDC Open/Close, Single Wire Control RA RA DA DA BLK RED GRY ORN 12 34 ~ -+ 24 VAC 24 VDC On/Off Control, Two Wire RA RA DA DA BLK RED GRY ORN 1 2 34 ~ 24 VAC - + 24 VDC Floating Control, Multiple Actuators with One Transformer RA RA DA DA BLK RED GRY ORN 12 34 RA RA DA DA BLK RED GRY ORN 12 34 FIG:M92xx-AGx_cntrlwir ~ -+ 24 VAC 24 VDC Figure 9: Control Wiring S1 21 22 23 21 BLK/ BLK/ BLK/ RED BLU GRY 21 22 23 COM NC NO Figure 10: Auxiliary Switch Wiring Diagram FIG:aux_wring WARNING: Risk of Electric Shock. ! Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. AVERTISSEMENT : Risque de décharge électrique. Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles. CAUTION: Risk of Property Damage. ! Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. MISE EN GARDE : Risque de dégâts matériels. Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement. 6 M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions CAUTION: Risk of Property Damage. ! Insulate and secure each unused wire lead before applying power to the actuator. Failure to insulate and secure each unused wire lead may result in property damage. MISE EN GARDE : Risque de dégâts matériels. Isoler et protéger chaque fil non utilisé avant de mettre l'actuator sous tension. Le non-respect de cette obligation d'isolation et de protection de chaque fil non utilisé risque d'entraîner des dégâts matériels. IMPORTANT: Make all wiring connections in accordance with the National Electrical Code and local regulations. Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid damaging the actuator's electronic circuits. Using Conduit All M9203-xxx-2(Z) Series Actuators accept 1/2 in. threaded electrician's fittings. Figure 11: Adding Flexible Metal Conduit 1. Feed the actuator cables through the field supplied electrician's fitting and conduit. 2. Thread the electrician's fitting into the actuator and secure the conduit to the fitting in accordance with local building code requirements. Setup and Adjustments Mode Selection Switch Actuators have an external mode selection switch to reverse control logic. The switch is accessible from both A and B sides of the actuator as illustrated in Figure 12. Actuators are delivered in Direct Acting (DA) mode and can be switched by the user to Reverse Acting (RA) mode. FIG:add_cndt FIG:AGx_modsel DA RA RA DA Side A of Actuator Side B of Actuator Figure 12: Mode Selection M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions 7 Control Response The installation side of the actuator and the position of the mode selection switch combine to determine control response from the actuator. See Figure 13. Installation Side 10 30 50 70 90 50 30 10 70 90 Control Inputs GRY 3 ORN 4 Mode Selection Switch The switch point is continuously adjustable throughout the actuator's rotation range. For the most accurate switch positioning, see Figure 14 and use the method in the following example. To change the switch point, proceed as follows: 1. Position the actuator in the full spring return position. Note: The switch is factory set to trip when the actuator reaches the 11° position. 2. Rotate the switch adjuster until it points to the desired switch point. Switch Adjuster 10 30 50 70 90 FIG:M92xxAGx_CtrlRspns FIG:swtch_sttng Figure 13: Control Response Auxiliary Switch (M9203-xxB-2(Z) Models) The M9203-xxB-2(Z) models include one integral auxiliary switch with a switch adjuster accessible on either face of the actuator (see Figure 2 and Figure 3). The factory setting for the Auxiliary Switch is 11° closing (relative to the 0 to 90° rotation range as printed on the product label). See the Technical Specifications table for the auxiliary switch ratings. WARNING: Risk of Electric Shock and ! Property Damage. Insulate and secure each unused wire lead before applying power to the actuator. Failure to insulate and secure each unused wire lead may result in property damage, electric shock, and severe personal injury or death. AVERTISSEMENT : Risque de décharge électrique et dégâts matériels. Isoler et protéger chaque fil non utilisé avant de mettre l'actuator sous tension. Le non-respect de cette obligation d'isolation et de protection de chaque fil non utilisé risque d'entraîner des dégâts matériels, des décharges électriques et des blessures graves, voire mortelles. Figure 14: Switch Trip Point Settings 3. Connect the Auxiliary Switch to a power source or an ohmmeter and apply power to the actuator. The actuator moves to the fully open position and holds while power is applied. 4. Observe the switch point. If required, repeat Step 1 through Step 3. Repair Information A number of replacement parts are available; see Table 1 for more details. If an M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring Return Actuator fails to operate within its specifications, replace the unit. For a replacement electric actuator, contact the nearest Johnson Controls representative. 8 M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions Technical Specifications M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring Return Actuator (Part 1 of 2 ) Power Requirements -AGx-2 Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe), 4.7 VA Running, 2.7 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.8 W Running, 1 W Holding Position Minimum Transformer Size: 6 VA per Actuator -AGx-2Z Models AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe), 5.1 VA Running, 2.8 VA Holding Position DC 24 V (DC 19.2 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.9 W Running, 1.1 W Holding Position Minimum Transformer Size: 6 VA per Actuator Input Signal -AGx-2(Z) Models AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10% Class 2 (North America) or SELV (Europe) Minimum Pulse Width: 500 msec Control Input Impedance -AGx-2(Z) Models 4,700 ohm Auxiliary Switch Rating -xxB Models One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts: AC 24 V, 50 VA Pilot Duty AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty Spring Return Direction Is Selectable with Mounting Position of Actuator: Actuator Face Labeled A Is Away from Damper or Valve: CCW Spring Return Actuator Face Labeled B Is Away from Damper or Valve: CW Spring Return Rated Torque Power On (Running) 27 lb·in. (3 N·m) All Operating Temperatures Power Off (Spring Returning) 27 lb·in. (3 N·m) All Operating Temperatures Rotation Range Maximum Full Stroke: 95° Adjustable Stop: 35 to 95° Maximum Position Rotation Time for 90 Degrees of Travel Power On (Running) -AGx-2 Models 150 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at All Operating Conditions Power On (Running) -AGx-2Z Models 90 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at All Operating Conditions Power Off (Spring Returning) 12 to 17 Seconds for 0 to 27 lb·in. (3 N·m) Load, at Room Temperature 16 Seconds Nominal at Full Rated Load 22 Seconds Maximum with 27 lb·in. (3 N·m) Load at -22°F (-30°C) Life Cycles 60,000 Full Stroke Cycles with 27 lb·in. (3 N·m) Load 1,500,000 Repositions with 27 lb·in. (3 N·m) Load M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions 9 M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring Return Actuator (Part 2 of 2 ) Audible Noise Rating Power On (Running) -AGx-2 Models <28 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m) Power On (Running) -AGx-2Z Models <37 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m) Power On (Holding) <20 dBA at a Distance of 39-13/32 in. (1 m) Power Off (Spring Returning) <56 dBA at 27 lb·in. (3 N·m) Load, at a Distance of 39-13/32 in. (1 m) Electrical Connections -AGA-2(Z) Models 120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm²) Conductors and 0.25 in. (6 mm) Ferrule Ends Auxiliary Switch 48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG (0.85 mm²) (-xxB Models) Conductors and 0.25 in. (6 mm) Ferrule Ends Conduit Connections Integral 1/2 in. (13 mm) Threaded Conduit Connector(s) Mechanical Connections Round Shafts Square Shafts Range of Sizes: 1/4 to 1/2 in. (6 to 12 mm) Range of Sizes: 1/4 to 5/16 in. (6 to 8 mm) Enclosure Rating NEMA 2 (IP54) for all Mounting Orientations Ambient Conditions Standard Operating -22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing Storage -40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing Dimensions 6.38 x 3.23 x 2.26 in. (162 x 82 x 57.5 mm) Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators. (Models: All) Plenum Rated (UL 2043). Suitable for use in other environmental air space (plenums) in accordance with Section 300.22 (C) of the National Electric Code Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment (Models: All) Europe CE Mark Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive. Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant (Models: All) Shipping Weight -AGA Models: 2.0 lb (0.9 kg) -AGB Models: 2.4 lb (1.1 kg) European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact: JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Product warranty This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty. Patents Patents: http://jcipat.com Metasys® and Johnson Controls® are registered trademarks of Johnson Controls. All other marks herein are the marks of their respective owners. © 2021 Johnson Controls. 10 M9203-AGx-2(Z) Series On/Off and Floating Point Electric Spring Return Actuators Installation Instructions Published in U.S.A. www.johnsoncontrols.com