User Manual for Comfort Flex models including: Comfort Flex, Two-pipe, S Panel, Wall Mounted, Fan Coil Unit

Two-pipe S Panel Wall Mounted Fan Coil Unit

CLIFCW-PD - CP | Climaproyectos S.A. de C.V.


File Info : application/pdf, 44 Pages, 10.72MB

PDF preview unavailable. Download the PDF instead.

CLIFCW-PD-CP
Two-pipe S Panel Wall Mounted Fan Coil Unit
Users Manual
We are leaders in the creation of innovative air conditioning solutions using state of the art technology and world class product design

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)
Two-pipe S Panel Wall Mounted Fan Coil Unit

1. Introduction ............................................................................................................. 2 2. Nomenclature .......................................................................................................... 2 3. Product Schedule ................................................................................................... 2 4. External Appearance .............................................................................................. 3 5. Features................................................................................................................... 3 6. Specifications ......................................................................................................... 4 7. Dimension ............................................................................................................... 6 8. Wiring Diagrams ..................................................................................................... 7 9. Capacity Tables....................................................................................................... 8 10. Sound Levels ........................................................................................................ 14 11. Exploded View ...................................................................................................... 15 12. Installation............................................................................................................. 16 13. Controller............................................................................................................... 28

1

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

1. Introduction
Fan coil unit is a kind of compound device which assemble fan and heat-exchang coil together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an important component of AC devices. Fan coil unit has concealed type and exposed type. A cooling (heating) supply system usually consists of fan coil terminals and chilled water system (heated water system).

Clima Flex® commercial AC fan coil is designed and manufactured on the base of advanced technology, and utilize qualified galvanized iron as material. Due to its supper-thin design, it has such advantages: beautiful outlook, space saving, easy installation, etc. And the most obvious advantage is that it can decrease the outlet air Temp-difference as low as possible to make room more comfortable, as well as don't decrease cooling capacity output. For the large air flow volume design, it can increase room ventilation frequency, supply more flesh air, and balance room temperature distribution. Benefiting from adoption of advanced material and technology, it can effectively decrease the running noise and keep running smoothly. With the advantages above, it can be widely applied in market, hospital, office building, hotel, airport, etc.
2. Nomenclature

3. Product Schedule
Model
CLIFC-W-250 CLIFC-W-300 CLIFC-W-400 CLIFC-W-500 CLIFC-W-600

Type Wall mounted

Air volume (CFM) 250 300 400 500 600

Power supply 208~230V-1Ph-60Hz

2

CLIFC-W 2015-05
4. External Appearance

Clima Flex Wall Mounted FCU (S type panel)

5. Features
 New panel supplies more choice for customs.  Multi-connection outlet pipe method: left/right/rear, more flexible for installation.

Left piping Left back piping

Right back piping

Right piping

 Wind direction adjustment can be in horizontal and vertical way for auto swing louver

Horizontal air deflector

Vertical air deflector

 Built-in 3-way electromagnetic valve.  Easy maintenance has been realized as the front panel can be removed for easy access.

 Remote controller with LCD display is standard, wired controller and central controller is optional.  Four-speed motor with super high speed reserved for more choice.  Eurovent certified performance.
3

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

6. Specifications

Model

CLIFC-W-250

CLIFC-W-300

CLIFC-W-400

Power supply Air flow (H/M/L)

V/Ph/Hz m3/h CFM

425/390/350 250/230/205

208-230/1/60 510/470/390 300/275/230

680/550/460 400/325/270

Capacity (H/M/L)

kW

2.63/2.41/2.16

2.97/2.47/2.12

3.28/2.83/2.41

Cooling

Water flow rate

L/h

452

511

564

Water pressure drop

kPa

29.4

35.6

43.5

Heating

Capacity (H/M/L) Water pressure drop

kW

3.36/3.1/2.79

3.91/3.26/2.77

kPa

27.3

32.9

4.37/3.73/3.17 40.8

Power input

W

24

37

40

Sound pressure level

dB(A)

30/24/20

35/29/24

37/31/26

Fan motor

Type Quantity

Low noise 4-speed fan motor 1

Type Fan
Quantity

Tangential fan 1

Row

2

Diameter

mm

7

Tube pitch(a)xrow pitch(b)

mm

21×13.37

Dimension (W×H×D)

mm

Coil

Fin spacing

mm

635×315×26.74 1.5

Fin type

Hydrophilic aluminium

Circuit

5

Max. working pressure

MPa

1.6

Net dimensions (W×H×D)

mm

915×290×230

Packing size (W×H×D)

mm

Body

Net weight

kg

13

1020×390×315

13

13.3

Gross weight

kg

16.3

16.3

16.7

Pipe

Water inlet/outlet pipe

inch

G3/4

connections Drain pipe

mm

OD20

Note:

1. H: high speed; M: medium speed; L: low speed

2. Cooling Conditions: entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°C WB.

Heating Conditions: entering water 50°C, Entering air temperature 20°C, the same water flow as the cooling conditions.

3. Noise is tested in semi-anechoic test room.

4

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Model

CLIFC-W-500

CLIFC-W-600

Power supply Air flow (H/M/L)

V/Ph/Hz m3/h CFM

850/745/620 500/440/365

220-240/1/60 1020/915/780 600/540/460

Capacity (H/M/L)

kW

4.25/3.85/3.32

5/4.47/3.97

Cooling

Water flow rate

L/h

731

860

Water pressure drop

kPa

31.8

42.5

Capacity (H/M/L)

kW

Heating

Water pressure drop

kPa

5.81/5.17/4.43 30.2

6.7/6/5.28 39.7

Power input

W

50

66

Sound pressure level

dB(A)

39/33/28

40/34/29

Fan motor

Type Quantity

Low noise 4-speed fan motor 1

Type Fan
Quantity

Tangential fan 1

Row

2

Diameter

mm

7

Tube pitch(a) x row pitch(b)

mm

21×13.37

Dimension (W×H×D)

mm

Coil

Fin spacing

mm

785×315×26.74 1.5

Fin type

Hydrophilic aluminium

Circuit

5

Max. working pressure

MPa

1.6

Net dimensions (W×H×D)

mm

1072×315×230

Packing size (W×H×D)

mm

Body

Net weight

kg

1180×415×315

15.8

15.8

Gross weight

kg

19.4

19.4

Pipe

Water inlet/outlet pipe

inch

G3/4

connections Drain pipe

mm

OD20

Note:

1. H: high speed; M: medium speed; L: low speed

2. Cooling Conditions: entering water 7°C, temperature rise 5°C, entering air temperature 27°C DB,19°C WB.

Heating Conditions: entering water 50°C, Entering air temperature 20°C, the same water flow as the cooling conditions.

3. Noise is tested in semi-anechoic test room.

5

Clima Flex Wall Mounted FCU (S type panel)
7. Dimension
CLIFC-W-250, CLIFC-W-300, CLIFC-W-400

CLIFC-W 2015-05

CLIFC-W-500, CLIFC-W-600

6

CLIFC-W 2015-05
8. Wiring Diagrams

Clima Flex Wall Mounted FCU (S type panel)

7

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

9. Capacity Tables

Cooling Capacity: Remark: EWT: Enter Water Temp. (°C)
DB: Dry Bulb Temp. (°C)

t: Temperature Difference (°C) WB: Wet Bulb Temp. (°C)

TC: Total Cooling Capacity (kW) WF: Water Flow (m3/h)

SC: Sensible Cooling Capacity (kW) WPD: Water Pressure Drop (kPa)

CLIFC-W-250

Air inlet condition

EWT t

DB:21 WB:15

DB:26.7 WB:19.4

DB:27 WB:19

DB:29 WB:21

DB:33 WB:25

TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD

3 2.17 1.58 0.62 55.8 3.35 2.02 0.96 132.6 3.28 2.11 0.94 127.2 3.67 1.92 1.05 158.7 4.93 2.39 1.41 287.4

4 2.05 1.49 0.44 27.8 3.22 1.96 0.69 68.9 3.17 2.05 0.68 66.7 3.52 1.86 0.76 82.4 4.78 2.32 1.03 151.9

5 5 1.89 1.43 0.33 15.2 3.08 1.89 0.53 40.4 3.02 1.98 0.52 38.8 3.39 2.93 0.58 48.7 4.63 2.28 0.80 91.1

6 1.73 1.37 0.25 8.8 2.94 1.84 0.42 25.6 2.89 1.91 0.41 24.6 3.24 1.72 0.46 30.9 4.52 2.20 0.65 60.2 7 1.55 1.28 0.19 5.2 2.80 1.75 0.34 17.0 2.74 1.85 0.34 16.2 3.10 1.65 0.38 20.8 4.36 2.13 0.54 41.3 3 1.97 1.49 0.56 45.6 3.16 1.94 0.91 118.0 3.09 2.02 0.89 112.7 3.48 1.84 1.00 143.0 4.74 2.32 1.36 265.7

4 1.83 1.42 0.39 22.1 3.04 1.87 0.65 61.2 2.96 1.95 0.64 58.3 3.34 1.78 0.72 74.1 4.59 2.24 0.99 140.0

6 5 1.69 1.35 0.29 12.1 2.89 1.80 0.50 35.5 2.83 1.90 0.49 34.1 3.21 1.71 0.55 43.7 4.44 2.16 0.76 83.8 6 1.51 1.29 0.22 6.8 2.75 1.75 0.39 22.3 2.69 1.83 0.39 21.3 3.05 1.63 0.44 27.4 4.33 2.09 0.62 55.2 7 1.33 1.20 0.16 3.8 2.61 1.67 0.32 14.7 2.54 1.78 0.31 14.0 2.91 1.56 0.36 18.4 4.17 2.05 0.51 37.8 3 1.76 1.40 0.50 36.5 2.95 1.84 0.85 102.9 2.89 1.94 0.83 98.5 3.28 1.75 0.94 126.6 4.52 2.20 1.29 240.8 4 1.61 1.34 0.35 17.3 2.83 1.78 0.61 53.2 2.76 1.87 0.59 50.4 3.15 1.69 0.68 65.7 4.40 2.16 0.95 128.7
7 5 1.46 1.28 0.25 9.0 2.69 1.72 0.46 30.7 2.63 1.81 0.45 29.4 2.99 1.62 0.52 38.1 4.25 2.09 0.73 76.8

6 1.28 1.21 0.18 4.9 2.55 1.67 0.36 19.1 2.50 1.75 0.36 18.5 2.86 1.55 0.41 24.1 4.14 2.01 0.59 50.5 7 1.11 1.11 0.14 2.7 2.41 1.59 0.30 12.6 2.33 1.69 0.29 11.8 2.71 1.48 0.33 15.9 3.98 1.94 0.49 34.4 3 1.54 1.32 0.44 28.0 2.75 1.76 0.79 89.4 2.69 1.85 0.77 85.2 3.08 1.65 0.88 111.8 4.33 2.13 1.24 221.0 4 1.39 1.28 0.30 12.8 2.63 1.70 0.57 45.9 2.55 1.81 0.55 43.2 2.93 1.60 0.63 57.0 4.17 2.05 0.90 115.7

8 5 1.23 1.20 0.21 6.4 2.50 1.63 0.43 26.5 2.42 1.73 0.42 24.9 2.80 1.54 0.48 33.4 4.06 1.97 0.70 70.1 6 1.10 1.10 0.16 3.6 2.33 1.58 0.33 16.1 2.29 1.67 0.33 15.5 2.66 1.46 0.38 21.0 3.91 1.94 0.56 45.1 7 0.96 0.96 0.12 2.0 2.20 1.51 0.27 10.5 2.13 1.61 0.26 9.8 2.49 1.40 0.31 13.5 3.77 1.86 0.46 30.9 3 1.32 1.25 0.38 20.5 2.56 1.69 0.73 77.2 2.49 1.77 0.71 73.0 2.87 1.57 0.82 97.4 4.14 2.05 1.19 202.0 4 1.20 1.20 0.26 9.5 2.41 1.62 0.52 38.7 2.34 1.72 0.50 36.4 2.72 1.51 0.59 49.3 3.98 1.97 0.86 105.5
9 5 1.10 1.07 0.19 5.2 2.28 1.56 0.39 22.2 2.21 1.66 0.38 20.8 2.59 1.45 0.45 28.6 3.87 1.90 0.67 63.7

6 0.97 0.97 0.14 2.8 2.13 1.50 0.31 13.4 2.06 1.61 0.29 12.5 2.46 1.38 0.35 17.8 3.71 1.86 0.53 40.6

7 0.79 0.79 0.10 1.4 1.97 1.43 0.24 8.4 1.91 1.53 0.23 7.9 2.28 1.32 0.28 11.3 3.58 1.79 0.44 27.8 3 1.16 1.16 0.33 15.9 2.35 1.60 0.67 64.9 2.25 1.70 0.65 59.8 2.67 1.49 0.77 84.3 3.95 1.94 1.13 183.9 4 1.07 1.07 0.23 7.6 2.20 1.54 0.47 32.2 2.13 1.65 0.46 30.0 2.52 1.43 0.54 42.0 3.78 1.90 0.81 95.1

10 5 0.95 0.95 0.16 3.9 2.06 1.49 0.35 18.0 1.97 1.59 0.34 16.5 2.38 1.37 0.41 24.1 3.67 1.83 0.63 57.1 6 0.82 0.82 0.12 2.0 1.92 1.42 0.27 10.8 1.83 1.53 0.26 9.9 2.23 1.30 0.32 14.6 3.51 1.78 0.50 36.3 7 0.52 0.52 0.06 0.6 1.75 1.36 0.21 6.6 1.67 1.48 0.20 6.0 2.08 1.23 0.26 9.4 3.35 1.71 0.41 24.4 3 1.02 1.02 0.29 12.4 2.12 1.53 0.61 52.9 2.04 1.62 0.59 49.2 2.46 1.41 0.70 71.2 3.72 1.86 1.07 163.7

4 0.94 0.94 0.20 5.8 1.98 1.47 0.43 26.2 1.91 1.56 0.41 24.1 2.32 1.35 0.50 35.7 3.57 1.81 0.77 84.7 11 5 0.81 0.81 0.14 2.8 1.83 1.42 0.32 14.3 1.75 1.53 0.30 13.0 2.17 1.29 0.37 20.0 3.46 1.75 0.59 50.8
6 0.65 0.65 0.09 1.2 1.67 1.36 0.24 8.2 1.61 1.46 0.23 7.6 2.01 1.22 0.29 11.9 3.30 1.70 0.47 32.1

7 0.44 0.44 0.05 0.4 1.49 1.31 0.18 4.8 1.43 1.43 0.18 4.5 1.85 1.15 0.23 7.4 3.15 1.63 0.39 21.5

3 0.90 0.90 0.26 9.6 1.89 1.45 0.54 42.3 1.80 1.57 0.52 38.4 2.23 1.33 0.64 58.8 3.51 1.79 1.01 145.8 4 0.80 0.80 0.17 4.2 1.75 1.40 0.38 20.4 1.67 1.51 0.36 18.4 2.10 1.27 0.45 29.3 3.37 1.73 0.72 75.3 12 5 0.69 0.69 0.12 2.0 1.60 1.35 0.28 10.9 1.52 1.46 0.26 9.8 1.95 1.21 0.33 16.1 3.24 1.67 0.56 44.5

6 0.41 0.41 0.06 0.5 1.42 1.31 0.20 6.0 1.41 1.38 0.20 5.9 1.78 1.15 0.26 9.4 3.08 1.62 0.44 28.0 7 0.34 0.34 0.04 0.3 1.26 1.26 0.15 3.4 1.30 1.30 0.16 3.7 1.62 1.08 0.20 5.7 2.93 1.56 0.36 18.6 3 0.78 0.78 0.22 7.1 1.65 1.39 0.47 32.3 1.56 1.51 0.45 28.7 2.01 1.26 0.58 47.8 3.29 1.72 0.94 127.8 4 0.66 0.66 0.14 2.9 1.51 1.34 0.33 15.2 1.46 1.43 0.31 14.2 1.87 1.20 0.40 23.2 3.15 1.65 0.68 65.9 13 5 0.48 0.48 0.08 1.0 1.35 1.32 0.23 7.8 1.37 1.37 0.23 7.9 1.72 1.14 0.30 12.6 3.01 1.59 0.52 38.5 6 0.32 0.32 0.05 0.3 1.23 1.23 0.18 4.5 1.27 1.27 0.18 4.8 1.55 1.08 0.22 7.1 2.85 1.55 0.41 24.0 7 0.24 0.24 0.03 0.1 1.12 1.12 0.14 2.7 1.17 1.17 0.14 3.0 1.36 1.02 0.17 4.0 2.71 1.48 0.33 15.9

8

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Cooling capacity table

CLIFC-W-300

Air inlet condition

EWT t

DB:21 WB:15

DB:26.7 WB:19.4

DB:27 WB:19

DB:29 WB:21

DB:33 WB:25

TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD

3 2.46 1.78 0.70 67.6 3.78 2.28 1.08 160.5 3.71 2.38 1.06 154.1 4.14 2.17 1.19 192.1 5.57 2.70 1.60 348.0

4 2.31 1.68 0.50 33.6 3.64 2.21 0.78 83.5 3.58 2.31 0.77 80.8 3.98 2.10 0.86 99.7 5.40 2.61 1.16 183.9

5 5 2.13 1.61 0.37 18.4 3.48 2.13 0.60 48.9 3.41 2.24 0.59 47.0 3.82 3.30 0.66 59.0 5.23 2.57 0.90 110.3

6 1.95 1.54 0.28 10.7 3.33 2.07 0.48 31.0 3.26 2.16 0.47 29.8 3.66 1.95 0.52 37.5 5.10 2.49 0.73 72.9

7 1.75 1.44 0.21 6.3 3.16 1.98 0.39 20.6 3.09 2.09 0.38 19.7 3.50 1.87 0.43 25.2 4.93 2.40 0.61 50.0

3 2.22 1.68 0.64 55.3 3.57 2.19 1.02 142.9 3.49 2.28 1.00 136.4 3.93 2.07 1.13 173.1 5.36 2.61 1.54 321.7

4 2.06 1.60 0.44 26.8 3.43 2.11 0.74 74.1 3.35 2.21 0.72 70.6 3.77 2.01 0.81 89.7 5.19 2.53 1.11 169.6

6 5 1.90 1.53 0.33 14.6 3.26 2.04 0.56 42.9 3.20 2.14 0.55 41.3 3.62 1.93 0.62 52.9 5.01 2.44 0.86 101.5

6 1.71 1.46 0.25 8.2 3.11 1.98 0.45 27.1 3.03 2.06 0.43 25.8 3.44 1.84 0.49 33.2 4.89 2.36 0.70 66.9

7 1.50 1.35 0.18 4.7 2.94 1.89 0.36 17.9 2.87 2.01 0.35 17.0 3.29 1.77 0.40 22.2 4.71 2.31 0.58 45.8

3 1.98 1.58 0.57 44.1 3.33 2.08 0.96 124.6 3.26 2.19 0.93 119.2 3.70 1.97 1.06 153.4 5.10 2.49 1.46 291.6 4 1.82 1.52 0.39 20.9 3.20 2.01 0.69 64.5 3.11 2.12 0.67 61.0 3.55 1.91 0.76 79.6 4.97 2.44 1.07 155.9 7 5 1.65 1.44 0.28 10.9 3.03 1.94 0.52 37.2 2.97 2.04 0.51 35.6 3.38 1.83 0.58 46.1 4.80 2.36 0.83 93.0

6 1.45 1.37 0.21 5.9 2.88 1.88 0.41 23.2 2.82 1.97 0.40 22.4 3.23 1.75 0.46 29.2 4.67 2.27 0.67 61.2 7 1.26 1.26 0.15 3.2 2.72 1.80 0.33 15.3 2.63 1.91 0.32 14.3 3.06 1.68 0.38 19.2 4.50 2.19 0.55 41.7 3 1.74 1.50 0.50 33.9 3.11 1.99 0.89 108.2 3.03 2.09 0.87 103.2 3.48 1.86 1.00 135.4 4.89 2.40 1.40 267.6

4 1.57 1.45 0.34 15.5 2.97 1.92 0.64 55.6 2.88 2.04 0.62 52.3 3.31 1.81 0.71 69.0 4.71 2.31 1.01 140.1 8 5 1.39 1.36 0.24 7.8 2.82 1.84 0.49 32.1 2.73 1.95 0.47 30.2 3.17 1.74 0.54 40.5 4.59 2.23 0.79 84.9
6 1.25 1.25 0.18 4.4 2.64 1.79 0.38 19.5 2.58 1.89 0.37 18.7 3.01 1.65 0.43 25.4 4.41 2.19 0.63 54.6 7 1.09 1.09 0.13 2.4 2.48 1.71 0.30 12.7 2.40 1.82 0.30 11.9 2.82 1.59 0.35 16.3 4.26 2.10 0.52 37.4 3 1.49 1.41 0.43 24.8 2.89 1.90 0.83 93.5 2.81 2.00 0.80 88.3 3.24 1.77 0.93 118.0 4.67 2.31 1.34 244.6 4 1.35 1.35 0.29 11.5 2.73 1.83 0.59 46.9 2.64 1.94 0.57 44.1 3.08 1.71 0.66 59.7 4.50 2.23 0.97 127.7 9 5 1.25 1.21 0.21 6.3 2.58 1.76 0.44 26.9 2.50 1.87 0.43 25.2 2.93 1.63 0.50 34.6 4.37 2.14 0.75 77.1 6 1.09 1.09 0.16 3.3 2.41 1.69 0.35 16.3 2.32 1.81 0.33 15.1 2.77 1.56 0.40 21.5 4.19 2.10 0.60 49.1 7 0.89 0.89 0.11 1.6 2.23 1.61 0.27 10.2 2.15 1.73 0.26 9.5 2.58 1.49 0.32 13.7 4.05 2.02 0.50 33.7 3 1.31 1.31 0.38 19.3 2.65 1.80 0.76 78.6 2.54 1.92 0.73 72.4 3.02 1.68 0.86 102.1 4.46 2.19 1.28 222.7 4 1.20 1.20 0.26 9.1 2.49 1.74 0.53 39.0 2.40 1.86 0.52 36.3 2.84 1.62 0.61 50.9 4.27 2.14 0.92 115.1 10 5 1.08 1.08 0.19 4.7 2.32 1.68 0.40 21.8 2.22 1.80 0.38 20.0 2.69 1.54 0.46 29.2 4.14 2.07 0.71 69.2 6 0.92 0.92 0.13 2.4 2.16 1.61 0.31 13.1 2.07 1.73 0.30 12.0 2.52 1.47 0.36 17.7 3.96 2.01 0.57 44.0 7 0.59 0.59 0.07 0.7 1.98 1.54 0.24 8.0 1.88 1.67 0.23 7.3 2.35 1.39 0.29 11.4 3.78 1.93 0.46 29.5 3 1.16 1.16 0.33 15.0 2.39 1.72 0.69 64.1 2.31 1.83 0.66 59.6 2.77 1.59 0.79 86.2 4.20 2.10 1.21 198.2 4 1.06 1.06 0.23 7.1 2.24 1.66 0.48 31.7 2.15 1.77 0.46 29.2 2.62 1.53 0.56 43.2 4.03 2.05 0.87 102.6 11 5 0.92 0.92 0.16 3.4 2.07 1.60 0.36 17.3 1.98 1.72 0.34 15.8 2.45 1.45 0.42 24.2 3.90 1.98 0.67 61.5 6 0.73 0.73 0.10 1.5 1.89 1.53 0.27 10.0 1.81 1.65 0.26 9.2 2.27 1.38 0.33 14.5 3.72 1.92 0.53 38.9 7 0.49 0.49 0.06 0.5 1.68 1.48 0.21 5.8 1.62 1.62 0.20 5.4 2.09 1.30 0.26 9.0 3.55 1.84 0.44 26.0 3 1.02 1.02 0.29 11.7 2.14 1.64 0.61 51.3 2.04 1.77 0.58 46.5 2.52 1.50 0.72 71.2 3.97 2.02 1.14 176.6 4 0.90 0.90 0.19 5.1 1.98 1.59 0.43 24.7 1.88 1.71 0.40 22.3 2.37 1.44 0.51 35.4 3.80 1.96 0.82 91.1 12 5 0.78 0.78 0.13 2.4 1.81 1.53 0.31 13.2 1.71 1.65 0.29 11.9 2.20 1.37 0.38 19.5 3.66 1.89 0.63 53.9 6 0.47 0.47 0.07 0.6 1.61 1.48 0.23 7.2 1.59 1.56 0.23 7.1 2.01 1.29 0.29 11.4 3.48 1.83 0.50 33.9 7 0.39 0.39 0.05 0.3 1.42 1.42 0.17 4.2 1.47 1.47 0.18 4.4 1.83 1.22 0.22 6.9 3.31 1.76 0.41 22.5 3 0.88 0.88 0.25 8.7 1.87 1.57 0.54 39.1 1.76 1.70 0.50 34.8 2.27 1.42 0.65 57.8 3.72 1.94 1.07 154.8 4 0.75 0.75 0.16 3.5 1.71 1.51 0.37 18.4 1.65 1.62 0.35 17.2 2.11 1.35 0.45 28.0 3.56 1.87 0.76 79.8 13 5 0.54 0.54 0.09 1.2 1.53 1.49 0.26 9.4 1.54 1.54 0.27 9.6 1.94 1.29 0.33 15.2 3.40 1.80 0.58 46.6 6 0.36 0.36 0.05 0.4 1.39 1.39 0.20 5.4 1.44 1.44 0.21 5.8 1.75 1.22 0.25 8.6 3.22 1.75 0.46 29.1 7 0.27 0.27 0.03 0.1 1.27 1.27 0.16 3.3 1.32 1.32 0.16 3.6 1.53 1.15 0.19 4.8 3.06 1.68 0.38 19.2

9

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

Cooling capacity table

CLIFC-W-400

Air inlet condition

EWT t

DB:21 WB:15

DB:26.7 WB:19.4

DB:27 WB:19

DB:29 WB:21

DB:33 WB:25

TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD

3 2.71 1.97 0.78 82.6 4.18 2.52 1.20 196.2 4.09 2.63 1.17 188.3 4.57 2.40 1.31 234.8 6.15 2.98 1.76 425.2

4 2.55 1.86 0.55 41.1 4.02 2.44 0.86 102.0 3.95 2.55 0.85 98.7 4.39 2.32 0.94 121.9 5.96 2.89 1.28 224.7

5 5 2.36 1.78 0.41 22.5 3.84 2.36 0.66 59.7 3.77 2.47 0.65 57.4 4.22 3.65 0.73 72.1 5.77 2.84 0.99 134.8

6 2.15 1.70 0.31 13.0 3.67 2.29 0.53 37.9 3.60 2.39 0.52 36.4 4.04 2.15 0.58 45.8 5.63 2.75 0.81 89.1

7 1.93 1.60 0.24 7.7 3.49 2.18 0.43 25.2 3.41 2.30 0.42 24.0 3.87 2.06 0.48 30.8 5.44 2.65 0.67 61.1

3 2.45 1.86 0.70 67.5 3.94 2.42 1.13 174.6 3.85 2.52 1.10 166.7 4.34 2.29 1.24 211.6 5.92 2.89 1.70 393.1

4 2.28 1.77 0.49 32.7 3.79 2.33 0.81 90.6 3.70 2.44 0.79 86.3 4.17 2.22 0.90 109.6 5.73 2.79 1.23 207.2

6 5 2.10 1.68 0.36 17.9 3.60 2.25 0.62 52.5 3.53 2.37 0.61 50.4 4.00 2.13 0.69 64.7 5.54 2.70 0.95 124.0

6 1.89 1.61 0.27 10.0 3.43 2.18 0.49 33.1 3.35 2.28 0.48 31.5 3.80 2.04 0.54 40.6 5.40 2.60 0.77 81.7

7 1.66 1.50 0.20 5.7 3.25 2.08 0.40 21.8 3.17 2.22 0.39 20.7 3.63 1.95 0.45 27.2 5.21 2.56 0.64 55.9

3 2.19 1.74 0.63 53.9 3.68 2.30 1.06 152.3 3.60 2.42 1.03 145.7 4.08 2.18 1.17 187.4 5.63 2.75 1.61 356.3 4 2.01 1.68 0.43 25.6 3.53 2.22 0.76 78.8 3.44 2.34 0.74 74.6 3.92 2.11 0.84 97.3 5.49 2.70 1.18 190.4 7 5 1.82 1.60 0.31 13.4 3.35 2.14 0.58 45.4 3.28 2.26 0.56 43.5 3.73 2.02 0.64 56.4 5.30 2.60 0.91 113.6

6 1.60 1.51 0.23 7.2 3.18 2.08 0.46 28.3 3.12 2.18 0.45 27.3 3.56 1.93 0.51 35.7 5.16 2.51 0.74 74.7 7 1.39 1.39 0.17 4.0 3.01 1.98 0.37 18.6 2.91 2.11 0.36 17.4 3.37 1.85 0.41 23.5 4.97 2.41 0.61 51.0 3 1.92 1.65 0.55 41.5 3.43 2.20 0.98 132.3 3.35 2.30 0.96 126.1 3.84 2.06 1.10 165.5 5.40 2.65 1.55 327.0

4 1.73 1.60 0.37 19.0 3.28 2.13 0.71 68.0 3.18 2.25 0.68 63.9 3.65 2.00 0.79 84.3 5.21 2.56 1.12 171.2 8 5 1.53 1.50 0.26 9.5 3.11 2.04 0.54 39.2 3.02 2.16 0.52 36.9 3.50 1.92 0.60 49.5 5.06 2.46 0.87 103.7
6 1.38 1.38 0.20 5.3 2.91 1.97 0.42 23.8 2.85 2.08 0.41 22.9 3.32 1.83 0.48 31.0 4.88 2.41 0.70 66.7 7 1.20 1.20 0.15 3.0 2.74 1.88 0.34 15.5 2.66 2.01 0.33 14.5 3.11 1.75 0.38 19.9 4.70 2.32 0.58 45.7 3 1.64 1.56 0.47 30.3 3.19 2.10 0.91 114.3 3.10 2.21 0.89 107.9 3.58 1.96 1.03 144.2 5.16 2.56 1.48 298.9 4 1.49 1.49 0.32 14.0 3.01 2.03 0.65 57.2 2.92 2.14 0.63 53.9 3.40 1.89 0.73 73.0 4.97 2.46 1.07 156.0 9 5 1.38 1.33 0.24 7.7 2.85 1.94 0.49 32.8 2.76 2.07 0.47 30.8 3.23 1.80 0.56 42.3 4.83 2.37 0.83 94.2 6 1.21 1.21 0.17 4.1 2.66 1.87 0.38 19.9 2.57 2.00 0.37 18.5 3.06 1.72 0.44 26.3 4.62 2.31 0.66 60.0 7 0.98 0.98 0.12 2.0 2.46 1.78 0.30 12.5 2.38 1.91 0.29 11.6 2.85 1.64 0.35 16.7 4.47 2.23 0.55 41.2 3 1.45 1.45 0.42 23.6 2.93 1.99 0.84 96.1 2.81 2.13 0.80 88.5 3.33 1.86 0.96 124.7 4.92 2.41 1.41 272.1 4 1.33 1.33 0.29 11.2 2.75 1.92 0.59 47.6 2.65 2.05 0.57 44.4 3.14 1.78 0.67 62.2 4.72 2.37 1.01 140.7 10 5 1.19 1.19 0.20 5.7 2.57 1.86 0.44 26.6 2.46 1.99 0.42 24.4 2.97 1.70 0.51 35.7 4.57 2.28 0.79 84.5 6 1.02 1.02 0.15 2.9 2.39 1.77 0.34 16.0 2.28 1.91 0.33 14.6 2.78 1.62 0.40 21.7 4.37 2.22 0.63 53.7 7 0.65 0.65 0.08 0.9 2.18 1.70 0.27 9.8 2.08 1.84 0.26 8.9 2.60 1.54 0.32 13.9 4.18 2.13 0.51 36.0 3 1.28 1.28 0.37 18.3 2.64 1.90 0.76 78.3 2.55 2.03 0.73 72.8 3.06 1.76 0.88 105.3 4.64 2.32 1.33 242.1 4 1.17 1.17 0.25 8.6 2.48 1.84 0.53 38.7 2.38 1.95 0.51 35.7 2.89 1.68 0.62 52.8 4.45 2.26 0.96 125.3 11 5 1.01 1.01 0.17 4.1 2.29 1.77 0.39 21.1 2.18 1.90 0.38 19.2 2.70 1.60 0.46 29.5 4.31 2.18 0.74 75.2 6 0.80 0.80 0.12 1.8 2.08 1.69 0.30 12.2 2.00 1.82 0.29 11.3 2.51 1.52 0.36 17.7 4.11 2.13 0.59 47.5 7 0.54 0.54 0.07 0.6 1.86 1.63 0.23 7.1 1.79 1.79 0.22 6.6 2.31 1.43 0.28 11.0 3.92 2.04 0.48 31.8 3 1.13 1.13 0.32 14.3 2.36 1.81 0.68 62.7 2.25 1.95 0.64 56.8 2.78 1.66 0.80 87.0 4.38 2.23 1.26 215.7 4 0.99 0.99 0.21 6.2 2.19 1.75 0.47 30.2 2.08 1.89 0.45 27.3 2.62 1.59 0.56 43.3 4.20 2.16 0.90 111.3 12 5 0.86 0.86 0.15 3.0 2.00 1.69 0.34 16.1 1.89 1.83 0.33 14.5 2.43 1.51 0.42 23.8 4.04 2.08 0.69 65.9 6 0.52 0.52 0.07 0.7 1.77 1.63 0.25 8.8 1.76 1.72 0.25 8.7 2.22 1.43 0.32 13.9 3.84 2.03 0.55 41.5 7 0.43 0.43 0.05 0.4 1.57 1.57 0.19 5.1 1.62 1.62 0.20 5.4 2.02 1.34 0.25 8.4 3.65 1.95 0.45 27.5 3 0.97 0.97 0.28 10.6 2.06 1.73 0.59 47.8 1.95 1.88 0.56 42.5 2.51 1.57 0.72 70.7 4.10 2.14 1.18 189.1 4 0.83 0.83 0.18 4.3 1.89 1.67 0.41 22.5 1.82 1.79 0.39 21.0 2.33 1.49 0.50 34.3 3.93 2.06 0.84 97.5 13 5 0.60 0.60 0.10 1.4 1.68 1.65 0.29 11.5 1.70 1.70 0.29 11.7 2.14 1.42 0.37 18.6 3.75 1.98 0.65 57.0 6 0.40 0.40 0.06 0.4 1.53 1.53 0.22 6.6 1.59 1.59 0.23 7.1 1.94 1.34 0.28 10.5 3.56 1.93 0.51 35.6 7 0.29 0.29 0.04 0.2 1.40 1.40 0.17 4.0 1.46 1.46 0.18 4.4 1.69 1.27 0.21 5.9 3.37 1.85 0.41 23.5

10

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Cooling capacity table

CLIFC-W-500

Air inlet condition

EWT t

DB:21 WB:15

DB:26.7 WB:19.4

DB:27 WB:19

DB:29 WB:21

DB:33 WB:25

TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD

3 3.51 2.55 1.01 60.4 5.42 3.26 1.55 143.4 5.30 3.40 1.52 137.6 5.92 3.11 1.70 171.6 7.97 3.86 2.29 310.8

4 3.31 2.41 0.71 30.1 5.21 3.16 1.12 74.6 5.12 3.31 1.10 72.1 5.69 3.01 1.22 89.1 7.73 3.74 1.66 164.3

5 5 3.05 2.31 0.53 16.4 4.98 3.05 0.86 43.7 4.88 3.20 0.84 42.0 5.47 4.73 0.94 52.7 7.48 3.68 1.29 98.6

6 2.79 2.21 0.40 9.5 4.76 2.97 0.68 27.7 4.67 3.09 0.67 26.6 5.23 2.78 0.75 33.5 7.30 3.56 1.05 65.1

7 2.50 2.07 0.31 5.6 4.53 2.83 0.56 18.4 4.42 2.99 0.54 17.6 5.01 2.67 0.62 22.6 7.05 3.43 0.87 44.7

3 3.18 2.40 0.91 49.4 5.11 3.13 1.46 127.6 4.99 3.27 1.43 121.9 5.62 2.97 1.61 154.7 7.67 3.74 2.20 287.4

4 2.95 2.29 0.63 23.9 4.91 3.02 1.05 66.2 4.79 3.16 1.03 63.1 5.40 2.87 1.16 80.1 7.42 3.62 1.60 151.5

6 5 2.72 2.18 0.47 13.1 4.67 2.91 0.80 38.3 4.58 3.07 0.79 36.9 5.18 2.76 0.89 47.3 7.18 3.50 1.23 90.6

6 2.45 2.09 0.35 7.3 4.45 2.83 0.64 24.2 4.34 2.95 0.62 23.0 4.92 2.64 0.71 29.7 6.99 3.37 1.00 59.8

7 2.15 1.94 0.26 4.2 4.21 2.70 0.52 15.9 4.11 2.87 0.50 15.2 4.70 2.53 0.58 19.9 6.75 3.31 0.83 40.9

3 2.84 2.26 0.81 39.4 4.77 2.98 1.37 111.3 4.67 3.13 1.34 106.5 5.29 2.82 1.52 137.0 7.30 3.56 2.09 260.5 4 2.61 2.17 0.56 18.7 4.58 2.88 0.98 57.6 4.45 3.03 0.96 54.5 5.08 2.73 1.09 71.1 7.11 3.50 1.53 139.2 7 5 2.35 2.07 0.41 9.8 4.34 2.77 0.75 33.2 4.25 2.93 0.73 31.8 4.84 2.62 0.83 41.2 6.87 3.37 1.18 83.1

6 2.07 1.96 0.30 5.3 4.12 2.69 0.59 20.7 4.04 2.82 0.58 20.0 4.62 2.50 0.66 26.1 6.68 3.25 0.96 54.6 7 1.80 1.80 0.22 2.9 3.89 2.57 0.48 13.6 3.77 2.74 0.46 12.7 4.37 2.40 0.54 17.2 6.44 3.13 0.79 37.2 3 2.49 2.14 0.71 30.3 4.45 2.85 1.27 96.7 4.34 2.99 1.24 92.2 4.97 2.67 1.43 121.0 6.99 3.43 2.00 239.0

4 2.24 2.07 0.48 13.9 4.25 2.75 0.91 49.7 4.12 2.92 0.89 46.7 4.73 2.59 1.02 61.7 6.75 3.31 1.45 125.2 8 5 1.99 1.94 0.34 7.0 4.04 2.64 0.69 28.7 3.91 2.80 0.67 27.0 4.53 2.48 0.78 36.2 6.56 3.19 1.13 75.8
6 1.78 1.78 0.26 3.9 3.77 2.56 0.54 17.4 3.70 2.70 0.53 16.7 4.31 2.37 0.62 22.7 6.32 3.13 0.91 48.8 7 1.56 1.56 0.19 2.2 3.55 2.44 0.44 11.3 3.44 2.61 0.42 10.6 4.03 2.27 0.50 14.6 6.10 3.01 0.75 33.4 3 2.13 2.02 0.61 22.1 4.13 2.72 1.18 83.6 4.02 2.86 1.15 78.9 4.64 2.54 1.33 105.4 6.68 3.31 1.92 218.5 4 1.93 1.93 0.42 10.3 3.90 2.62 0.84 41.8 3.78 2.77 0.81 39.4 4.40 2.45 0.95 53.3 6.44 3.19 1.38 114.1 9 5 1.78 1.73 0.31 5.6 3.69 2.51 0.64 24.0 3.58 2.68 0.61 22.5 4.19 2.34 0.72 30.9 6.26 3.07 1.08 68.9 6 1.56 1.56 0.22 3.0 3.45 2.42 0.49 14.5 3.32 2.59 0.48 13.5 3.97 2.23 0.57 19.2 5.99 3.00 0.86 43.9 7 1.28 1.28 0.16 1.5 3.19 2.31 0.39 9.1 3.08 2.48 0.38 8.5 3.69 2.13 0.45 12.2 5.79 2.89 0.71 30.1 3 1.88 1.88 0.54 17.2 3.79 2.58 1.09 70.2 3.64 2.75 1.04 64.7 4.32 2.40 1.24 91.2 6.38 3.13 1.83 198.9 4 1.72 1.72 0.37 8.2 3.56 2.48 0.76 34.8 3.43 2.66 0.74 32.4 4.07 2.31 0.87 45.5 6.11 3.07 1.31 102.8 10 5 1.54 1.54 0.26 4.2 3.32 2.40 0.57 19.5 3.18 2.58 0.55 17.8 3.85 2.21 0.66 26.1 5.92 2.96 1.02 61.8 6 1.32 1.32 0.19 2.1 3.10 2.30 0.44 11.7 2.96 2.48 0.42 10.7 3.60 2.10 0.52 15.8 5.67 2.88 0.81 39.3 7 0.84 0.84 0.10 0.6 2.83 2.20 0.35 7.2 2.69 2.39 0.33 6.5 3.37 1.99 0.41 10.2 5.42 2.76 0.67 26.3 3 1.66 1.66 0.47 13.4 3.42 2.47 0.98 57.3 3.30 2.62 0.95 53.2 3.97 2.28 1.14 77.0 6.02 3.01 1.72 177.0 4 1.51 1.51 0.33 6.3 3.21 2.38 0.69 28.3 3.08 2.53 0.66 26.1 3.75 2.18 0.81 38.6 5.77 2.93 1.24 91.6 11 5 1.31 1.31 0.23 3.0 2.96 2.29 0.51 15.4 2.83 2.47 0.49 14.1 3.50 2.08 0.60 21.6 5.59 2.83 0.96 55.0 6 1.04 1.04 0.15 1.3 2.70 2.20 0.39 8.9 2.59 2.35 0.37 8.2 3.25 1.97 0.47 12.9 5.33 2.75 0.76 34.7 7 0.71 0.71 0.09 0.4 2.40 2.12 0.30 5.2 2.32 2.32 0.28 4.8 2.99 1.86 0.37 8.0 5.08 2.64 0.62 23.2 3 1.46 1.46 0.42 10.4 3.06 2.35 0.88 45.8 2.91 2.53 0.84 41.5 3.61 2.15 1.03 63.6 5.68 2.89 1.63 157.7 4 1.29 1.29 0.28 4.6 2.83 2.27 0.61 22.1 2.69 2.45 0.58 19.9 3.39 2.05 0.73 31.6 5.44 2.80 1.17 81.4 12 5 1.11 1.11 0.19 2.2 2.59 2.19 0.45 11.8 2.45 2.37 0.42 10.6 3.15 1.96 0.54 17.4 5.23 2.70 0.90 48.2 6 0.67 0.67 0.10 0.5 2.30 2.12 0.33 6.5 2.28 2.23 0.33 6.3 2.88 1.85 0.41 10.2 4.98 2.62 0.71 30.3 7 0.55 0.55 0.07 0.3 2.04 2.04 0.25 3.7 2.10 2.10 0.26 4.0 2.62 1.74 0.32 6.2 4.73 2.52 0.58 20.1 3 1.26 1.26 0.36 7.7 2.67 2.24 0.77 35.0 2.52 2.43 0.72 31.1 3.25 2.03 0.93 51.7 5.32 2.78 1.52 138.3 4 1.07 1.07 0.23 3.2 2.45 2.16 0.53 16.5 2.36 2.32 0.51 15.3 3.02 1.93 0.65 25.0 5.09 2.67 1.09 71.3 13 5 0.77 0.77 0.13 1.1 2.18 2.13 0.38 8.4 2.21 2.21 0.38 8.6 2.78 1.84 0.48 13.6 4.86 2.57 0.84 41.6 6 0.52 0.52 0.07 0.3 1.99 1.99 0.28 4.8 2.05 2.05 0.29 5.2 2.51 1.74 0.36 7.7 4.61 2.50 0.66 26.0 7 0.38 0.38 0.05 0.1 1.82 1.82 0.22 3.0 1.89 1.89 0.23 3.2 2.20 1.64 0.27 4.3 4.37 2.40 0.54 17.2

11

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

Cooling capacity table

CLIFC-W-600

Air inlet condition

EWT t DB:26.7 WB:19.4

DB:27 WB:18

DB:27 WB:19

DB:27 WB:20

DB:29 WB:21

TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD TC SC WF WPD

3 4.13 3.00 1.19 80.7 6.37 3.84 1.83 191.7 6.24 4.00 1.79 183.9 6.97 3.66 2.00 229.4 9.38 4.55 2.69 415.4

4 3.89 2.84 0.84 40.2 6.13 3.72 1.32 99.7 6.02 3.89 1.30 96.4 6.70 3.54 1.44 119.1 9.09 4.40 1.95 219.5

5 5 3.59 2.71 0.62 21.9 5.86 3.59 1.01 58.3 5.74 3.77 0.99 56.1 6.44 5.56 1.11 70.4 8.80 4.33 1.51 131.7

6 3.28 2.60 0.47 12.7 5.60 3.49 0.80 37.0 5.49 3.64 0.79 35.6 6.15 3.28 0.88 44.7 8.59 4.18 1.23 87.0

7 2.94 2.43 0.36 7.5 5.32 3.33 0.65 24.6 5.20 3.51 0.64 23.5 5.89 3.15 0.72 30.1 8.30 4.04 1.02 59.7

3 3.74 2.83 1.07 66.0 6.01 3.69 1.72 170.6 5.87 3.85 1.68 162.9 6.62 3.49 1.90 206.7 9.02 4.40 2.59 384.1

4 3.47 2.69 0.75 32.0 5.77 3.56 1.24 88.5 5.63 3.72 1.21 84.3 6.35 3.38 1.37 107.1 8.73 4.26 1.88 202.4

6 5 3.20 2.57 0.55 17.4 5.49 3.43 0.94 51.2 5.38 3.61 0.93 49.2 6.10 3.25 1.05 63.2 8.44 4.11 1.45 121.1

6 2.88 2.45 0.41 9.8 5.23 3.33 0.75 32.3 5.11 3.47 0.73 30.8 5.79 3.10 0.83 39.6 8.23 3.97 1.18 79.9

7 2.53 2.28 0.31 5.6 4.96 3.17 0.61 21.3 4.83 3.38 0.59 20.3 5.53 2.97 0.68 26.6 7.94 3.90 0.98 54.6

3 3.34 2.66 0.96 52.7 5.61 3.51 1.61 148.8 5.49 3.69 1.57 142.4 6.23 3.32 1.78 183.1 8.59 4.18 2.46 348.1

4 3.07 2.55 0.66 25.0 5.38 3.38 1.16 77.0 5.24 3.56 1.13 72.9 5.98 3.21 1.29 95.0 8.37 4.11 1.80 186.1

7 5 2.77 2.43 0.48 13.0 5.11 3.26 0.88 44.4 5 3.44 0.86 42.5 5.69 3.08 0.98 55.1 8.08 3.97 1.39 111.0

6 2.44 2.31 0.35 7.0 4.84 3.17 0.69 27.7 4.75 3.32 0.68 26.7 5.43 2.94 0.78 34.8 7.86 3.82 1.13 73.0

7 2.11 2.11 0.26 3.9 4.58 3.02 0.56 18.2 4.43 3.22 0.54 17.0 5.14 2.82 0.63 23.0 7.58 3.68 0.93 49.8

3 2.93 2.52 0.84 40.5 5.23 3.35 1.50 129.2 5.11 3.51 1.46 123.2 5.85 3.14 1.68 161.7 8.23 4.04 2.36 319.5

4 2.64 2.44 0.57 18.5 5.00 3.24 1.08 66.4 4.85 3.43 1.04 62.4 5.57 3.04 1.20 82.4 7.94 3.90 1.71 167.3

8 5 2.34 2.29 0.40 9.3 4.75 3.10 0.82 38.3 4.60 3.29 0.79 36.0 5.33 2.92 0.92 48.3 7.72 3.75 1.33 101.3

6 2.10 2.10 0.30 5.2 4.44 3.01 0.64 23.2 4.35 3.17 0.62 22.3 5.06 2.78 0.73 30.3 7.43 3.68 1.07 65.2

7 1.83 1.83 0.23 2.9 4.18 2.87 0.51 15.1 4.05 3.07 0.50 14.2 4.74 2.67 0.58 19.5 7.17 3.54 0.88 44.6

3 2.50 2.37 0.72 29.6 4.86 3.20 1.39 111.7 4.73 3.36 1.35 105.5 5.46 2.99 1.57 140.9 7.86 3.90 2.25 292.1

4 2.27 2.27 0.49 13.7 4.59 3.09 0.99 55.9 4.45 3.26 0.96 52.6 5.18 2.88 1.11 71.3 7.58 3.75 1.63 152.4

9 5 2.10 2.03 0.36 7.5 4.34 2.96 0.75 32.1 4.21 3.15 0.72 30.1 4.93 2.75 0.85 41.3 7.36 3.61 1.27 92.1

6 1.84 1.84 0.26 4.0 4.05 2.85 0.58 19.4 3.91 3.05 0.56 18.1 4.67 2.62 0.67 25.7 7.05 3.53 1.01 58.7

7 1.50 1.50 0.18 2.0 3.75 2.71 0.46 12.2 3.62 2.91 0.44 11.4 4.34 2.50 0.53 16.4 6.81 3.40 0.84 40.2

3 2.21 2.21 0.63 23.0 4.46 3.04 1.28 93.9 4.28 3.24 1.23 86.4 5.08 2.83 1.46 121.8 7.50 3.68 2.15 265.9

4 2.03 2.03 0.44 10.9 4.18 2.92 0.90 46.5 4.04 3.13 0.87 43.4 4.78 2.72 1.03 60.8 7.19 3.61 1.55 137.4

10 5 1.81 1.81 0.31 5.6 3.91 2.83 0.67 26.0 3.74 3.03 0.64 23.8 4.53 2.60 0.78 34.9 6.97 3.48 1.20 82.6

6 1.55 1.55 0.22 2.8 3.64 2.71 0.52 15.7 3.48 2.91 0.50 14.3 4.24 2.47 0.61 21.2 6.67 3.38 0.96 52.5

7 0.99 0.99 0.12 0.8 3.33 2.59 0.41 9.6 3.17 2.81 0.39 8.7 3.96 2.34 0.49 13.6 6.37 3.25 0.78 35.2

3 1.95 1.95 0.56 17.9 4.03 2.90 1.15 76.5 3.88 3.09 1.11 71.2 4.67 2.68 1.34 102.9 7.08 3.54 2.03 236.6

4 1.78 1.78 0.38 8.4 3.77 2.80 0.81 37.8 3.62 2.97 0.78 34.8 4.41 2.57 0.95 51.6 6.79 3.45 1.46 122.4

11 5 1.54 1.54 0.27 4.1 3.48 2.69 0.60 20.6 3.33 2.90 0.57 18.8 4.12 2.45 0.71 28.9 6.57 3.33 1.13 73.4

6 1.23 1.23 0.18 1.8 3.17 2.58 0.46 11.9 3.05 2.77 0.44 11.0 3.82 2.32 0.55 17.3 6.27 3.24 0.90 46.4

7 0.83 0.83 0.10 0.6 2.83 2.49 0.35 6.9 2.73 2.73 0.34 6.5 3.52 2.19 0.43 10.8 5.98 3.10 0.73 31.0

3 1.72 1.72 0.49 13.9 3.60 2.76 1.03 61.2 3.43 2.98 0.98 55.5 4.24 2.53 1.22 85.0 6.68 3.41 1.92 210.8

4 1.52 1.52 0.33 6.1 3.33 2.67 0.72 29.5 3.17 2.88 0.68 26.6 3.99 2.42 0.86 42.3 6.40 3.30 1.38 108.8

12 5 1.31 1.31 0.22 2.9 3.04 2.58 0.52 15.8 2.89 2.78 0.50 14.2 3.70 2.31 0.64 23.3 6.15 3.17 1.06 64.4

6 0.79 0.79 0.11 0.7 2.71 2.49 0.39 8.6 2.68 2.63 0.38 8.5 3.39 2.18 0.49 13.6 5.86 3.09 0.84 40.5

7 0.65 0.65 0.08 0.4 2.40 2.40 0.29 5.0 2.47 2.47 0.30 5.3 3.08 2.05 0.38 8.2 5.57 2.97 0.68 26.9

3 1.48 1.48 0.42 10.3 3.15 2.64 0.90 46.7 2.97 2.86 0.85 41.5 3.82 2.39 1.10 69.1 6.26 3.27 1.79 184.8

4 1.26 1.26 0.27 4.2 2.88 2.54 0.62 22.0 2.78 2.73 0.60 20.5 3.55 2.27 0.76 33.5 5.99 3.15 1.29 95.3

13 5 0.91 0.91 0.16 1.4 2.57 2.51 0.44 11.2 2.60 2.60 0.45 11.5 3.27 2.16 0.56 18.2 5.72 3.02 0.98 55.7

6 0.61 0.61 0.09 0.4 2.34 2.34 0.34 6.5 2.42 2.42 0.35 6.9 2.95 2.05 0.42 10.3 5.43 2.94 0.78 34.8

7 0.45 0.45 0.05 0.2 2.14 2.14 0.26 4.0 2.22 2.22 0.27 4.3 2.58 1.93 0.32 5.8 5.14 2.82 0.63 23.0

Cooling capacity modification coefficient table:

Speed

250

TC

SC

300

TC

SC

400

TC

SC

500

TC

SC

600

TC

SC

High

1

1

1

1

1

1

1

1

1

1

Mid

0.92

0.9

0.83

0.8

0.86

0.83

0.91

0.86

0.89

0.85

Low

0.82

0.8

0.71

0.7

0.73

0.7

0.78

0.75

0.79

0.75

12

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Heating Capacity:
Remark: t: Temperature Difference () WF: Water Flow (m3/h)

TH: Total Heating Capacity (kW) WPD: Water Pressure Drop (kPa)

CLIFC-W-250

Air inlet temp. (20 DB)

Water inlet temp. ()

t

35

40

45

50

55

60

65

70

TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD

10 1.15 0.10 1.2 1.80 0.15 2.8 2.49 0.21 5.4 3.14 0.27 8.7 3.80 0.33 12.6 4.46 0.38 17.5 5.11 0.44 22.9 5.75 0.49 29.0

8 1.27 0.14 2.2 1.98 0.21 5.4 2.65 0.28 9.6 3.31 0.36 15.0 3.94 0.42 21.3 4.58 0.49 28.8 5.23 0.56 37.4 5.87 0.63 47.2

6 1.47 0.21 5.3 2.14 0.31 11.2 2.78 0.40 18.8 3.45 0.49 29.0 4.10 0.59 41.0 4.74 0.68 54.9 5.35 0.77 69.7 6.03 0.86 88.6

CLIFC-W-300

Air inlet temp. (20 DB)

Water inlet temp. ()

t

35

40

45

50

55

60

65

70

TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD

10 1.33 0.11 1.5 2.08 0.18 3.7 2.89 0.25 7.1 3.64 0.31 11.3 4.40 0.38 16.6 5.17 0.45 22.9 5.92 0.51 30.0 6.67 0.57 38.0

8 1.47 0.16 2.9 2.29 0.25 7.0 3.07 0.33 12.6 3.83 0.41 19.6 4.57 0.49 27.9 5.31 0.57 37.7 6.06 0.65 49.1 6.81 0.73 61.9

6 1.71 0.24 6.9 2.48 0.36 14.7 3.22 0.46 24.6 4.00 0.57 38.0 4.76 0.68 53.7 5.50 0.79 71.9 6.20 0.89 91.3 6.99 1.00 116.1

CLIFC-W-400

Air inlet temp. (20 DB)

Water inlet temp. ()

t

35

40

45

50

55

60

65

70

TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD

10 1.49 0.13 2.1 2.34 0.20 5.1 3.25 0.28 9.7 4.10 0.35 15.5 4.95 0.43 22.7 5.82 0.50 31.3 6.66 0.57 41.0 7.50 0.65 52.0

8 1.66 0.18 4.0 2.58 0.28 9.6 3.46 0.37 17.3 4.31 0.46 26.8 5.14 0.55 38.2 5.98 0.64 51.6 6.82 0.73 67.1 7.66 0.82 84.7

6 1.92 0.28 9.5 2.80 0.40 20.1 3.62 0.52 33.7 4.50 0.65 52.0 5.35 0.77 73.5 6.19 0.89 98.4 6.98 1.00 124.9 7.87 1.13 158.9

CLIFC-W-500

Air inlet temp. (20 DB)

Water inlet temp. ()

t

35

40

45

50

55

60

65

70

TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD

10 1.99 0.17 1.6 3.13 0.27 3.9 4.33 0.37 7.5 5.46 0.47 11.9 6.60 0.57 17.4 7.76 0.67 24.1 8.88 0.76 31.5 10.00 0.86 40.0

8 2.21 0.24 3.1 3.44 0.37 7.4 4.61 0.50 13.3 5.75 0.62 20.7 6.85 0.74 29.4 7.97 0.86 39.7 9.09 0.98 51.7 10.21 1.10 65.1

6 2.56 0.37 7.3 3.73 0.53 15.4 4.83 0.69 25.9 6.00 0.86 40.0 7.13 1.02 56.5 8.25 1.18 75.7 9.30 1.33 96.1 10.49 1.50 122.3

CLIFC-W-600

Air inlet temp. (20 DB)

Water inlet temp. ()

t

35

40

45

50

55

60

65

70

TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD

10 2.29 0.20 2.0 3.59 0.31 4.9 4.98 0.43 9.4 6.28 0.54 14.9 7.59 0.65 21.8 8.93 0.77 30.1 10.21 0.88 39.4 11.50 0.99 50.0

8 2.54 0.27 3.8 3.96 0.43 9.2 5.30 0.57 16.6 6.61 0.71 25.8 7.88 0.85 36.7 9.17 0.99 49.7 10.45 1.12 64.6 11.74 1.26 81.4

6 2.94 0.42 9.1 4.29 0.61 19.3 5.56 0.80 32.4 6.90 0.99 50.0 8.20 1.18 70.7 9.49 1.36 94.6 10.70 1.53 120.1 12.06 1.73 152.8

13

Clima Flex Wall Mounted FCU (S type panel)

Heating capacity modification coefficient table:

250

300

Speed

TH

TH

High

1

1

Mid

0.92

0.83

Low

0.83

0.71

Altitude modification coefficient table:

Altitude (m)

TC

500

0.98

1000

0.97

1500

0.95

2000

0.94

2500

0.93

3000

0.91

10. Sound Levels

Test condition

400 TH 1 0.85 0.73
SC 0.95 0.91 0.86 0.82 0.78 0.74

CLIFC-W 2015-05

500

600

TH

TH

1

1

0.89

0.90

0.76

0.79

TH 0.95 0.91 0.86 0.82 0.78 0.7

Unit Number
1 2 3 4 5

Model
CLIFC-W-250 CLIFC-W-300 CLIFC-W-400 CLIFC-W-500 CLIFC-W-600

Sound pressure level under three speeds of fan (dB(A))

H

M

L

30

24

20

35

29

24

37

31

26

39

33

28

40

34

29

14

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

11. Exploded View
CLIFC-W-250, CLIFC-W-300, CLIFC-W-400, CLIFC-W-500, CLIFC-W-600

No. 1 2 3 4 5 8 9 10 11 11.1 11.2 11.3 11.4 11.5 11.7 11.8 11.9 11.10 12 13 14 15

Part Name Panel ass'y Panel decorative plates Electrical cover Panel frame ass'y Screw cover Sealing plug Motor spud Motor E-part box ass'y Electric control box base Electric control box side panel electric control box cover Dial switch cover label Dial code switch board ass'y Terminal block, 5p Main control board ass'y Terminal block, 3p Capacitor Remote controller Remote controller bracket Air outet frame Stepper motor

Quantity 1 1 1 1 3 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. 16 17 18 19 20 21 21.1 21.2 21.3 21.4 21.5 21.8 21.9 21.10 21.11 22 23 24 25 26 27

Part Name Pipe clamp Chassis ass'y Drainage pan ass'y Cross fan Bearing block Evaporator ass'y Evaporator Evaporator Evaporator Evaporate connecting board Evaporate connecting board Water-outlet pipe ass'y Water-inlet pipe ass'y 3-Way valve Discharge valve Installation board ass'y Display board ass'y Air purify net Filter network Pipe temp. sensor ass'y Room temp sensor ass'y

Quantity 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1

15

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

12. Installation
12.1 Precautions
 Be sure to be in conformity with the local, national and international laws and regulations.  Read "PRECAUTIONS" carefully before installation.  The following precautions include important safty items. Observe them and never forget.  Keep the installation manual in a handy place for future reference.  Before out from factory, FAN COIL UNIT (AIR UNITS) has passed Fan Coil Overpressure Resistant Test,
Statically and Dynamically Balanced Adjustment, Noise Test, Air (cool) Volume Test, Electric Property Test, Outline Quality Detection. The safety precautions listed here are divided into two categories. In either case, important safety information is listed that must be read carefully. Warning: Failure to observe a warning may result in death. Caution: Failure to observe a caution may result in injury or damage to the equipment. After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.
 Warning:
 Be sure only trained and qualified service personnel to install, repair or service the equipment. Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
 Install according to the installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock and fire.
 When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
 Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, electrical shock and fire.
 The appliance must be installed 2.3m above floor.  The appliance shall not be installed in the laundry.  Before obtaining access to terminals, all supply circuits must be disconnected.  The appliance must be positioned so that the plug is accessible.  The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the
fluid flow.  For electrical work, follow the local national wiring standard, regulation the installation
instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock fire.  Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.  Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.  If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard.  An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.

16

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

 When carrying out piping connection, take care not to let air substances go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle.
 Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
 If the water leaks during installation, ventilate the area immediately.  After completing the installation work, check that the water does not leak.
The cool water in the unit is not lower than 3, hot water is not higher than 70. Water in the unit must clean, air quality must meet to the standard of PH=6.5~7.5.
 Caution:
 Ground the air conditioner. Do not connect the ground wire to gas or water pipes, lightning rod or telephone ground wire.Incomplete grounding may result in electric shocks.
 Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks.
 Connect the outdoor unit wires, and then connect the indoor unit wires. You are not allowed to connect the air conditioner with the power source until wiring and piping the air conditioner is done.
 While following the installation instructions, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage.
 Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
 This appliance is not intended for use by persons (including children) with reduced physical,sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
 Don't install the air conditioner in the following locations:  There is petrolatum existing.  There is salty air surrounding (near the coast).  There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).  The Volt vibrates violently (in the factories).  In buses or cabinets.  In kitchen where it is full of oil gas.  There is strong electromagnetic wave existing.  There are inflammable materials or gas.  There is acid or alkaline liquid evaporating.  Other special conditions.

17

Clima Flex Wall Mounted FCU (S type panel)

12.2 Accessory
Name

Shape

1. Screw ST3.9x25 for installation board

2. Plastic expanded tube

Quantity 3 3

CLIFC-W 2015-05
Function Secure the installation board

3. Wrapping tape

1

4. Drain pipe

1

5. Wall conduit cover

1

6. Remote controller 1
(including operation manual)

7. Frame

1

Hold the remote controller

8. Mounting screw (ST2.9 x 10-C-H)

2

Insulation the holder of remote controller

9. Alkaline dry batteries (AM4)

2

10. Owner's manual

1

11. Installation manual

1

12. seel gasket

4

For connecting water pipe

12.3 Remote controller installation
 Never throw or beat the controller.  Before installation, operate the remote controller to determine its location in a reception range.  Keep the remote controller at least 1m apart from the nearest TV set or stereoequipment. (it is
necessary to prevent image disturbances or noise interferences.)  Do not install the remote controller in a place exposed to direct sunlight or close to a heating source,
such as a stove.  Note that the positive and negative poles are right positions when loading batteries.  This information is subject to changes due to technological improvement without further notices.

SET TEMPERATURE(°C)

AUTO COOL DRY HEAT

FAN HIGH MED LOW

TEM P

MODE

ON/OFF

FAN SPEED

SWING

E C O N O M IC R U N N IN G

TIMER

VENT RESET LOCK CANCEL

Mounting screw B ST2.9x10-C-H

Remote controller
18

Remote controller holder

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

12.4 Indoor unit installation

12.4.1 Installation place

Installation in the following places may cause trouble. If it is unavoidable, please consult with the local

dealer.  A place full of machine oil.

 A saline place such as coast.  A place full of sulfide gas such as hot-spring resort.  Places where there are high frequency machines such as wireless equipment, welding machine, and

medical facility.  A place there is no combustive gases and volatile matter.  A place of special environmental conditions.

Indoor unit installation place  A place where is no obstacle near the inlet and outlet area.  A place which can bear the indoor unit.

 A place which is convenient to maintenance.  A place which provides the space around the indoor unit as required right in the diagram.  There is strong electromagnetic wave existing.

 A place which is far from heat, steam and inflammable gas.

12.4.2 Drilling a hole and mounting installation board

Installation Board and Its Direction (unit: mm)

250\300\400 type
mounting board of indoor unit

500\600 type mounting board of indoor unit

460

730

25 290
36 316

915

1070

the shape of indoor unit

the shape of indoor unit

Fix the installation board.  Install the installation board horizontally on structural parts on the wall with the spaces provided around
the plate.  In case of brick, concrete or similar type walls, make 5mm dia. holes on the wall. Insert clip anchors for
appropriate mounting screws.  Fix the installation board on the wall. Right installation

Tow Screw

Tow Screw

mounting board of indoor unit

horizontal line

19

Clima Flex Wall Mounted FCU (S type panel)
False installation
mounting board of indoor unit
horizontal line

mounting board of indoor unit

CLIFC-W 2015-05
horizontal line

Drilling a hole  Determine the pipe hole position using the installation board, and drill the pipe hole (N95mm) so it slants
slightly downward.  Always use a wall hole conduit when piercing metal lath, ply wood or metal plate. 12.4.3 Connective and drain pipe installation Drain pipe installation  Run the drain hose sloping downward. Do not install the drain hose as illustrated below.

Do not form a rise

Do not put the hose end into water

 When connection extended drain hose, insulate the connecting part of extended drain hose with a

shield pipe.

Shield pipe

Wall

Drain hose
Connection pipe installation

Extended drain hose

Left piping Left back piping

Right back piping

Right piping

 For the left-hand and rear-left-hand piping, install the piping as shown. Bend the connective pipe to be laid at 43mm height or less from the wall.

20

CLIFC-W 2015-05

Indoor unit outline

Clima Flex Wall Mounted FCU (S type panel)
Connective pipe

43

.

...........................................................................................................

.... ..
.. .. ..

.....
.... ..........

..

 Fix the end of the connective pipe. (Refer to Tightening Connection in WATER PIPING INSTALLATION) Cautions:  Connect the indoor unit first, then the outdoor unit. Bend and arrange the pipe carefully.  Do not allow the piping to let out from the back of the indoor unit.  Be careful not to let the drain hose slack.  Insulate both of the auxiliary piping.  Banding the drain hose under the auxiliary pipe. Piping and bandaging Wind the connective cable, drain hose and wiring with tape securely, evenly as shown below.  Because the condensed water from rear of the indoor unit is gathered in Pond Box and is piped out of
room. Do not put anything else in the box.

Indoor unit

Pond box

Connective cable

.. .

. . . .

. .

..

.. .

.

.

.. .. .

. . .
.

.. . .
..
.

. .

.

.. .

. .. . .

..

Pipe room
Connective pipe
Wrapping belt

Drain hose
12.4.4 Indoor unit installation  Pass the piping through the hole in the wall.  Put the claw at the back of the indoor unit on the hook of the installation board, move the Indoor Unit
from side to side to see that it is securely hooked.  Piping can easily lift the indoor unit by the cushioning material between the indoor unit and the wall. Get
it out after finish piping.  Push the lower part of the Indoor Unit up to the wall, and then move the Indoor Unit from side to side, up
and down to check if it is hooked securely.
hook

Cushioning material

21

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

12.5 Water pipe installation
Connection of the water pipe should be done by professionals. Double-span should be used when connecting pipes of Indoor Unit.

 At the first debugging, completely expel air from coils via expelling valve.

3-way valve (4.ports)

discharge valve

conector

12.6 Wiring chart
The wiring diagram please refers to chapter 8. Cautions:  The reserved function is indicated in broken line table, users can select it when necessary.  An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual
current device (RCD) with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule.  The appliance shall be installed in accordance with national wiring regulations. Take out the faceplate, and then dismantle the display cover
display cover plate

Individual connect the power cord and signal line, adjust the dial switch.

the wire holder of power cord(three-position)

the wire holder of signal line (five-position)

display cover plate

dial switch
12.6.1 Terminal Board Diagram Note: The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring
22

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

correctly and set system address and network address of indoor units.  Single phase indoor unit

Power supply

220-240V/1 ph/60Hz

Circuit breaker/fuse (A)

15/15

Indoor unit power wiring Ground wiring (mm2)

Below 20m Below 50m

Twisted pairwire 2.5 mm2 Twisted pairwire 6 mm2 2.5

Y/G

RED BLACK

WHITE BLUE
BLACK RED RED

XT1 L N

X YE 1 2
XT3

RED BLACK

INDOOR UNIT POWER 220-240V50Hz

To Central Control Monitor TO Timer (CCM)COMM. BUS

 Please adopt the shielded twisted-pair wire, and connect the shielded layer to E

DISPLAY BOARD

WIRE CONTROLLER

To wire controller
The reserved wire control function is indicated in broken line table, users can purchase the wire controller when necessary. 12.6.2 Network address setting Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner in LAN is set by code switch on Network Interface Module (NIM), and the set range is 0-63.

Toggle switch set

SW1
ON 12
ON 12
ON 12
ON 12

BCD E

B CDE

B CDE

B C DE

ENC2

F01 2

F 0 12

BCDE

34 56

~

F01

F 0 12

BCDE

23 456

~

F0 1

F 0 12

BCDE

34 56
2

~

F01

F 0 12

BCDE

234 56

~

34 5 6

34 5 6

34 5 6

34 5 6

Network address code
00~15
16~31 32~47 48-63

789A 789A 789A 789A

789A 789 A 78 9A
789A

23

Clima Flex Wall Mounted FCU (S type panel)
Functions of anti-cold wind and anti-hot wind
Toggle switch set SW2
ON 12
ON 12
ON 12
ON 12
12.7 Troubleshooting

Function selection
Anti-cold wind OFF, Anti-hot wind OFF
Anti-cold wind OFF, Anti-hot wind ON
Anti-cold wind ON, Anti-hot wind OFF
Anti-cold wind ON, Anti-hot wind ON

Malfunction code EE E3 E2 E8 E7

Malfunction DC motor malfunction T2 evaporator sensor malfunction T1 evaporator sensor malfunction Water-level alarm malfunction EEPROM communication error

Water-level alarm malfunction

CLIFC-W 2015-05

Water-level switch connecting wire between switch and main board gets loose

Exist

Reconnect and ensure that the connection is reliable.

OK
There is something wrong with the water-level switch

Exist

Replace switch

OK

Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)

Error

Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.

OK
Mainboard error: For example, getting wet

OK Replace mainboard

24

CLIFC-W 2015-05 T2 evaporator sensor malfunction

Clima Flex Wall Mounted FCU (S type panel)

T2 Connecting wire between sensor and mainboard gets loose

Exist

Reconnect and ensure that the connection is reliable.

OK

Temperature

sensor

is

short-circuited or punctured

Exist

Replace sensor

OK
Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)

Error

Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.

OK
Mainboard error: For example, getting wet

OK Replace mainboard

T1 evaporator sensor malfunction

T1 Connecting wire between sensor and mainboard gets loose

Exist

Reconnect and ensure that the connection is reliable.

OK

Temperature

sensor

is

short-circuited or punctured

Exist

Replace sensor

OK
Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent alignment)

Error

Reinstall chip, or install other chip with same model on the faulty unit, to check whether there is something wrong with chip.

OK
Mainboard error: For example, getting wet

OK Replace mainboard

25

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

12.7.1 Troubles and causes of air conditioner
If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer.  The operation lamp is flashing rapidly (twice every second)  This lamp is still flashing rapidly after turn off the power and turn on again.  Remote controller receives malfunction or the button does not work well.  A safety device such as a fuse, a breaker frequently actuates.  Water leaks from indoor unit.  Other malfunctions.

Symptoms Unit does not start

Causes
Power failure. Power switch is off. Fuse of power switch may have burned. Batteries of remote controller exhausted or other problem of controller.

Solution
Wait for the comeback of power. Switch on the power. Replace the fuse. Replace the batteries or check the controller.

Air flowing normally but completely can't cooling
Low cooling effect

Temperature is not set correctly.
Indoor unit heat exchanger is dirty. The air filter is dirty. Inlet of indoor units is blocked. Doors and windows are open Sunlight directly shine.
Too much heat resource. Outdoor temp. is too high.

Set the temperature properly.
Clean the heat exchanger.
Clean the air filter. Eliminate all dirties and make air smooth. Close doors and windows. Make curtains in order to shelter from sunshine. Reduce heat source. AC cooling capacity reduces (normal).

Low heating effect

Outdoor temperature is lower than 7 C . Doors and windows not completely closed.

Use heating device. Close doors and windows.

26

CLIFC-W 2015-05

12.7.2 Troubles and causes of remote controller Before asking for serving or repairing, check the following points.

Symptoms

Causes

The fan speed can not be changed.

Check whether the MODE indicated on the display is "AUTO"
Protection against hot wind in cooling mode.

Protection against cold wind in heating mode.

Clima Flex Wall Mounted FCU (S type panel)
Solution
When the automatic mode is selected, the air conditioner will automatically change the fan speed. Reduce the temperature of inlet in cooling mode rise the temperature of inlet in heating mode.

The remote controller signal is not transmitted even when the ON/OFF button is pushed.

Check whether the batteries in the remote controller are exhausted.

The power supply is off.

The TEMP. indicator does not come on.

Check whether the MODE indicated on the display is FAN ONLY

The temperature cannot be set during FAN mode.

The indication on the display disappears after a lapse of time.

Check whether the timer operation has come to an end when the TIMER OFF is indicated on the display.

The air conditioner operation will stop up to the set time

The TIMER ON indicator
goes off after a lapse of certain time.

Check whether the timer operation is started when the TIMER ON is indicated on the display.

Up to the set time, the air conditioner will automatically start and the appropriate indicator will go off.

No receiving tone sounds from the indoor unit even when the ON/OFF button is
pressed.

Check whether the signal transmitter of the remote controller is properly directed
to the infrared signal receiver of the indoor unit when the ON/OFF button is pressed.

Directly transmit the signal transmitter of
the remote controller to the infrared signal receiver of the indoor unit, and then repeatly push the ON/OFF button twice.

27

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

13. Controller

13.1 Standard Controller : Remote Controller R51/E
13.1.1 Specifications

Model

R51/E

Rated Voltage

3.0V

Lowest Voltage of CPU Emitting Signal

2.0V

Reaching Distance

8m (when using 3.0 voltage, it can get 11m)

Environment Temperature Range

-5 60 

13.1.2 Performance Features 1. Operating Mode: COOLHEATDRYFAN and AUTO. 2. Timer Setting Function in 24 hours. 3. Indoor Temperature Setting Range : 17~30. 4. LCD display for all functions. 5. Compatible with the former R11. 13.1.3 Function Buttons Introduction

1. TEMP DOWN Button: Push the TEMP DOWN button to decrease the indoor temperature setting or to adjust the timer in a counter-clockwise direction.
2. MODLE SELECT Button: Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates:
3. SWING Button: Push this switch button to change the louver angle.
28

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

4. RESET Button: When the RESET button is pushed, all of the current settings are cancelled and the control will return to the initial settings.
5. ECONOMIC RUNNING Button: Push this button to go into the Energy-Saving operation mode.
6. LOCK Button: Push this button to lock in all the current settings. To release settings, push again.
7. CANCEL Button: Push this button to cancel the TIMER settings.
8. TIMER Button: This button is used to preset the time ON (start to operate) and the time OFF (turn off the operation)
9. ON/OFF Button: Push this button to start the unit operation. Push the button again to stop the unit operation.
10. FAN SPEED Button: This button is used for setting fan speed in the sequence that goes from AUTO, LOW, MED to HIGH, and then back to Auto.
11. TEMP UP Button: Push this button to increase the indoor temperature setting or to adjust the timer in a counter-clockwise direction.
12. VENT Button: Push this button to set the ventilating mode. The ventilating mode will operate in the following sequence:

13.1.4 Indicators Introduction

1. TRANSMISSION Indicator: This indicator lights when remote controller transmits signals to indoor unit. 2. MODE Display: Shows the current operation mode - AUTO, COOL, DRY or HEAT. HEAT only available
for heat pump model. 3. HEAT PUMP ONLY- LOCK display is displayed by pushing the LOCK button. Push the LOCK button
again to clear display. 4. TIMER Display: This display area shows the settings of TIMER. That is, if only the starting time of
operation is set, it will display the TIMER ON. If only the turning off time of operation is set, it will display the TIMER OFF. If both operations are set, it will show TIMER ON OFF which indicates you have chosen to set both the starting time and off time. 5. FAN Display: When the FAN button is pushed, this signal indicator lights. 6. Digital Display Area: This area will show the temperature, and if in the TIMER mode, it will show the ON and OFF settings of the TIMER. NOTE: All items are shown in the Fig for the purpose of clear presentation, But during the actual operation only the relative functional items are shown on the display panel. 13.1.5 Operational Guidelines 13.1.5.1 Operating the Remote Controller
29

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

Install / Replace Batteries: The Remote Controller uses two alkaline dry batteries(R03/Ir03X2). 1. To install batteries, slide back the cover of the battery compartment and install the batteries according to the directions (+and -) shown on the Remote Controller. 2. To replace the old batteries , use the same method as mentioned above. Note : 1. When replacing batteries, do not use old batteries or a different type battery. This may cause the remote
controller to malfunction. 2. If you do not use the remote controller for several weeks remove the batteries. Otherwise battery leakage
may damage the remote controller. 3. The average battery life under normal use is about 6 months. 4. Replace the batteries when there is no answering beep from the indoor unit or if the Transmission
Indicator light fails to appear. 13.1.5.2 Automatic Operation When the Air Conditioner is ready for use, switch on the power and the OPERATION indicator lamp on the display panel of the indoor unit starts flashing. 1. Use the MODE select button to select AUTO. 2. Push the TEMP button to set the desired room temperature. The most comfortable temperature settings
are between 21 to 28. 3. Push the ON/OFF button to start the air conditioner. The OPERATION lamp on the display panel of the
indoor unit lights. The operating mode of AUTO FAN SPEED is automatically set and there are no indicators shown on the display panel of the remote controller. 4. Push the ON/OFF button again to stop the unit. Note : 1. In the AUTO mode, the air conditioner can logically choose the mode of COOL, FAN, HEAT and DRY by sensing the difference between the actual ambient room temperature and the set temperature on the remote controller.. 2. If the AUTO mode is not comfortable for you , the desired mode can be selected manually. 13.1.5.3 COOL, HEAT, and FAN ONLY Operation 1. If the AUTO mode is not comfortable, you may manually override the settings by using COOL, DRY, HEAT(HEAT PUMP units only), or FAN ONLY modes. 2. Push the TEMP button to set the desired room temperature. When in COOLING mode, the most comfortable settings are 21 or above. When in HEATING mode, the most comfortable settings are 28 or below. 3. Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW. 4. Push the ON/OFF button. The operation lamp lights and the air conditioner starts to run according to your settings. 5. Push the ON/OFF button again to stop. Note : The FAN ONLY mode cannot be used to control the temperature. While in this mode, only steps 13 and 4 may be performed. 13.1.5.4 Dry Operation 1. Push the MODE button to select DRY. 2. Push the TEMP button to set the desired temperature from 21 to 28. 3. Push the ON/OFF button. The operation lamp lights and the air conditioner starts to run in the DRY mode. 4. Push the ON/OFF button again to stop the unit. Note : Due to the difference of the set temperature of the unit and the actual indoor temperature, the Air

30

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Conditioner when in DRY mode will automatically operate many times without running the COOL and FAN mode. 13.1.5.5 Time Operation PUSH TIMER button to set the on and off times of the unit. 1. To set the STARTING time. 1.1 Please push the CANCEL button to cancel any former settings. 1.2 Push the TIMER button. The remote controller will show the TIMER and the signal "h" is shown on the
display panel. The control is now ready to reset the TIMER ON to start the operation. 1.3 Push the TEMP button ( or ) to set desired unit START time . 1.4 After setting the TIMER there will be a one-half second delay before the remote controller transmits the
signal to the Air Conditioner. Then, after approximately another 2 seconds, the set temperature will re-appear on the digital display. 2. To set the STOPPING time. 2.1 Please press the CANCEL button to cancel any former settings. 2.2 Push the TIMER button and the remote controller will show the last set time for the START operation and the signal "h" will be shown on the display panel. You are now ready to re-adjust the TIMER OFF to stop the operation. 2.3 Push the TEMP button to cancel the TIMER ON setting. The digital area will show "00". 2.4 Push the TIMER button and the remote controller will show the last set time for the STOP operation and the signal "h" will be shown on the display panel. You are now ready to reset the time of the STOP operation. 2.5 Push the TEMP button ( or ) to set the time you want to stop the operation. 2.6 After setting the TIMER there will be a one-half second delay before the remote controller transmits the signals to the Air Conditioner. Then after approximately another 2 seconds, the set temperature will re-appear on the digital display. 3. Set the STARTING & STOPPING time 3.1 Please press the CANCEL button to cancel any former settings. 3.2 Push the TIMER button and the remote controller will show the last setting time for START operation and the signal "h" will be shown on the display panel. You are now ready to readjust the TIMER ON to start the operation. 3.3 Push the TEMP button ( or ) to set the time you want to start the operation. 3.4 Push the TIMER button and the remote controller will show the last set time for STOP operation and the signal "h" will be shown on the display panel. You are now ready to reset the time of the STOP operation. 3.5 Push the TEMP button ( or ) to set the time you want to stop the operation. 3.6 After setting the TIMER there will be a one-half second delay before the remote controller transmits the signal to the Air Conditioner. Then, after approximately another 2 seconds ,the set temperature will re-appear on the digital display. Note : 1. Please reset the TIMER after cancelling the former time settings. 2. The setting time is relative time. That is the time set is based on the delay of the current time.

31

Clima Flex Wall Mounted FCU (S type panel)
13.2 Optional Controller
13.2.1 Wired Controller KJR-10B

CLIFC-W 2015-05

Name and function of LCD display on the wired controller
 FAN speed  MODE display

 LOCK display

 CLOCK display  OFF/ON display

 Economical operation display

 Temperature display

1. Mode select button (MODE): Press MODE button to select "COOL", "DRY" , "HEAT", or "FAN ONLY" mode.(HEAT is invalid for COOL ONLY wire controller.)
2. Fan speed button (FAN SPEED) Press FAN SPEED to select fan speed from "AUTO", "LOW"," MED" , and "HIGH". NOTE: some air conditioners have no MED fan speed, and then the MED is regarded as HIGH.
3. Economical operation displays: Press ECONOMICAL to display economical operation, if press ECONOMICAL again then the display disappears
4. Lock display Press LOCK to display the icon of LOCK. Press the button again then the icon of LOCK disappears. In the mode of LOCK, all the buttons are invalid except for LOCK button.
5. CLOCK display Usually display the clock set currently. Press the button CLOCK for 4 seconds, the HOUR part will flash, press button  and  to adjust HOUR. Press the button CLOCK again, the minute part flash, press button or to adjust MINUTE. After clock set or clock operation, it must press CONFIRM to complete the set.
6. TIMER ON/OFF display: Display ON at the state of TIMER ON adjustment or after only set the TIMER ON; Display OFF at the

32

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

state of TIMER OFF adjustment or after only set the TIMER OFF; Display ON/OFF if simultaneously set the mode of TIMER ON and TIMER OFF. 7. Temperature display area: Usually display the set temperature. Press the buttons of and to set temperature, at the mode of FAN, there is no figure display in the area.
Name and functions of buttons on the wired controller

ON / OFF button

Mode selection button 
Timer on button  Timer off button  Clock button  cOonkfirbmutbtoutnton  rRepelsaectebnuutttotonn 

TIMER ON CLOCK

ECONOMICAL

TIMER OFF COONKFIRM MODE FAN SPEED SWING

TEMP

RER ESPELTA C E L O C K

COOL H EATING

Fan speed selection
Adjust button  Adjust button  Swing button Economical button
COOL ONLY/COOL and Heating selection button

Lock button
1. Mode selection button: It is used to select mode, push the button one time, then the operation modes will change in turn as follows: AUTO COOLING DEHUMIDIFY HEATING FAN Remark: no heating mode if wire controller is set as the cool only.
2. Timer on button: Push the button to set TIMER ON, each time you push the button the time moves forward by 0.5 hours. When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If want to cancel the TIMER ON, then adjust the time of TIMER ON as 0.0
3. Timer off button: Push the button to set TIMER OFF, each time you push the button the time moves forward by 0.5 hours. When the set time is over 10 hours, each time you push the button the time moves forward by 1 hour. If want to cancel the TIMER OFF, then adjust the time of TIMER OFF as 0.0
4. CLOCK button: Normally display the clock set currently (display 12:00 for the first electrifying or resetting). When push the button for 4 seconds, the hour part on the clock display flashes every 0.5 seconds, then push button and to adjust hour; push the button CLOCK again, the minute part flashes every 0.5 seconds, then push and button to adjust minute. When set clock or alter clock setting, must push the confirm button to complete the setting.
5. Ok button: The button is used at the state of CLOCK adjustment. After select the time, push the button to confirm then exit, the current clock will display
6. Reset button (hidden): Use a small stick with a diameter of 1mm to push the RESET button to cancel the current settings and get into the condition of resetting.
7. ON/OFF button: Push the button at the condition of OFF, the OPERATION lamp lights, ans the wire controller enters into ON operation, simultaneously sends the information of operation mode set currently, temperature, fan speed, timer etc. Push the button at the conditionof ON, the OPERATION lamp extinguishes, simu-

33

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

ltaneously sends the OFF. If having set TIMER ON or TIMER OFF, the wire controller will cancel these settings before entering into OFF, close the concern indicator, and then send the OFF information. 8. Fan speed selection button (FAN SPEED) Select any one fan speed from "AUTO", "LOW"," MED" , and "HIGH". Each time push the button, the fan speed will change in turn as fellow.

9. Adjust button : Set indoor temperature up. If press and hold on, it will increase at 1 degree per 0.5 second.
10. Adjust button  : Set indoor temperature down. If press and hold on, it will decrease at 1degree per 0.5 second.
11. Swing button: Push this button for the first time when operation,it will start the swing function. Push the button for the second time, cancel the swing function. (The function is available matched with the concerned unit)
12. Economical button: Push the button to set the economical operation mode for air conditioner, push again then cancel the mode. The operation mode is suitable for sleeping time.
13. Cool only/cooling and heating selec- tion button (hidden): Use a small stick with a diameter of 1mm to push the button to switch modes.For COOLING ONLY type, it will be no heating mode when pressing MODE. The uniform mode is COOLING and HEATING at the factory.
14. Lock button (hidden): Use a small stick with the diameter of 1mm to push the LOCK button to lock the current setting, push the button again then cancel the setting.
Installation Wiring Principle Sketch:

Wire Joint, 5p

Infraed Pipe

+5V

Wire Controller

5-Core Shield Cable, the length is decided by installation

RUN GND Indoor Unit Switch Board

Indoor Unit
Installation description: When the air conditioner needs the constant frequency wire Controller, be sure adding a Wire Joint with 5 terminal named A, B, C, D, E in indoor unit, and fixing a infraed emitter whose anode and cathode connecting with A and B near the receiver in the Indoor Unit Switch Board, then connecting the terminal +5V, GND, Run in the Switch Board to C, D, E respectively.

NOTE Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks. Please leave enough long cable for maintenance of the Wire Controller Board.

34

CLIFC-W 2015-05
I
Wire Controller Top Cover Wire Controller LCD
Wire Controller Board
Wire Controller Bottom Cover
44

Wire Controller Back Cover

Clima Flex Wall Mounted FCU (S type panel)
Turn a screwdriver at the concave on bottom panel of the Wire Controller to remove the Back Cover
Holes matche with the 86X86 Wiring box

120 46 17
18

Wood Mounting

When installing the Wire

Screw (M4X20)

Controller Cover,be sure there is

a hole in the wall to avoid the Wire

49

When installing the Wire Controller, you should adjust the bottom of the Wire Controller Board to the Wire Controller Back Cover which should be fixed first, then press the other end of the Wire Controller Board.

Controller Back Cover being fixed directly to the wall which is not allowed for the Wire Joint extrudes out of the Wire Controller Back Cover

60

120

13.2.2 Wired Controller: KJR-12B

Name and function of LCD display on the wired controller 1 Operation mode indication

3 Follow me function 4 ON/OFF indication

2 Timer ON/OFF

1

2

5 Fan speed indication

1

12

6 Lock 7 Temperature display zone

35

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

1Operation mode indication: When press "MODE" button, the following mode can be selected in circle. AutoCool DryHeat Fan onlyAuto. For cooling only model, heat mode is skipped.
2Timer : When adjust setting on time or only on time is set, the "ON" is lighted. When adjust setting off time or only off time is set, the "OFF" is lighted. If on and off timer are both set, the"ON" and "OFF"are both lighted.
3Follow me function: There is a temperature sensor inside the wire controller, after setting temperature, it will compare the two temperatures, and the space of wire controller will be the same as setting temperature. It is available under cooling, heating, auto mode.
4ON/OFF indication : When it is on, the icon display, otherwise it is extinguished.
5Fan speed indication : There are four fan modes: low, middle, high, and auto. For some models, no middle fan then the middle fan is seen as high speed.
6Lock: When the "LOCK "button is pressed, the icon appear and other buttons is unable, press again, the icon disappear.
7Temperature display zone: Generally it displays setting temperature, it can be adjusted by press temperature button  and . But no display in fan mode.
Name and functions of buttons on the wired controller



ON / OFF BUTTON

MODE BUTTON



TIMER ON BUTTON 

TIMER OFF BUTTON 

FOLLOW ME BUTTON 

ELECTRICAL HEATER BUTTON



RESET BUTTON



TIMER ON
TIMER OFF

FOLLOW ME
AUXIL HEATER

ECO

MODE

FAN SPEED

SWING

TEMP

RESET LOCK

 ADJUST BUTTON 



ADJUST BUTTON 



SWING BUTTON

11

ECONOMY BUTTON

12
13
1Mode botton: When press this botton, the operation mode change as the following sequence:
AUTO  COOLDRYHEATFAN

FAN SPEED BUTTON LOCK BUTTON

Remark: For the cooling only model, the heating mode is skipped. 2Timer on button :

36

CLIFC-W 2015-05

Clima Flex Wall Mounted FCU (S type panel)

Press this button, timer on function is active. Then every press, the time increase 0.5h, after 10h, 1h increasement after each press. If cancel this Function, just set it to "0.0". 3Timer off button: Press this button, timer off function is active.Then every press, the time increase 0.5h, after 10h, 1h increasement after each press. If cancel this function, just set it to "0.0". 4Follow me button: When under cool, heat and auto mode, and press this button, follow me function is active. Press again, this function is ineffective. 5Electrical heater button : If press this button in heat mode, electrical heater function become ineffective. 6Reset button(hidden): Use a 1mm stick to press in the little hole, then the current setting is canceled. The wire controller enters into original state. 7ON/OFF button: When in off state, press this button, the indicator is on, the wire controller enter into on state, and send setting information to in door Pcb. When in on state, press this button, the indicator is off, and send instruction. If timer on or timer off has been set, it concel this setting then send instruction to stop the machine. 8Adjust button : Set indoor temperature up. If press and hold on, it will increase at 1°C (2°F) per 0.5 second. 9Adjust button  : Set indoor temperature down. If press and hold on, it will decrease at 1°C (2°F) per 0.5 second. 10Swing button: First press "start swing function"; second press "stop swing". (Match to some model with swing function). 11Economy operation button: Press this button, the indoor unit operates in economy mode, press again, exit this mode (it may be ineffective for some models) 12Fan speed button: Press this button consecutively; the fan speed will circle as follow:

13Lock button(hidden): When you push the LOCK button, all current settings are locked in and the wire controller does not accept any operation except that of the LOCK button. Use the lock mode when you want to prevent setting from being changed accidentally or play fully. Push the LOCK button again when you want to cancel the LOCK mode.
Installation Wiring Principle Sketch:

37

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

A Wire Controller B
C
D
E

5-terminal Group
Wires here adopts 5-core Shield Cable, the length should be accord with the actual conditions .

Installation description:

When it is necessary to use this controller, it needs to add a small 5-terminal group and fasten a infrared

emmiter near to the receiver in the switch board.Connecting the anode and cathode to AB of the Terminal

Group, also connect +5VGNDRUN of the switch board separately to the CDE of the 5-terminal Group.

Wire Controller Back Cover

Turn a screwdriver at the concave on bottom panel of the Wire Controller to remove the Back Cover

Wire Controller Top Cover
Wire Controller LCD

Holes matche with the 86X86 Wiring box

Wire Controller Board

Wire Controller Bottom Cover
44

120 46 17
18

Wood Mounting Screw (M4X20)
When installing the Wire Controller, you should adjust the bottom of the Wire Controller Board to the Wire Controller Back Cover which should be fixed first, then press the other end of the Wire Controller Board.

When installing the Wire Controller Cover,be sure there is a hole in the wall to avoid the Wire Controller Back Cover being fixed directly to the wall which is not allowed for the Wire Joint extrudes out of the Wire Controller Back Cover

49

60

120

Caution: The connecting wire should be a little longer as to take away the switch board easily for maintenance The connecting wire should be a little longer as to take away the controller easily for maintenance..

38

CLIFC-W 2015-05
13.2.3 Central Controller: MD-CCM03

Clima Flex Wall Mounted FCU (S type panel)

39

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

40

CLIFC-W 2015-05
Liquid crystal matrix display description:

Clima Flex Wall Mounted FCU (S type panel)

1. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure).
2. The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+ and 48+ on the left
Side, which indicate the address of the indoor unit. The sum of the horizontal coordinate and the vertical

coordinate of the grid is the address of the grid. Each grid corresponds to an indoor unit of this address. 3. One grid is composed of two blocks of different sizes. The status
Indication table is as follows:

Object

Status Constantly on

Slow blink

Fast blink

Big black block

In-service

Selected

Out of service

Small black block

Power on

Fault of indoor unit Power off

LCD display description 1. Description of the standby page 1) The LCD displays the standby page, 60 air conditioners are in service, of which 28 are powered on and
32 off. 2) In the matrix, the big dots of (00, 16+) and (15,32+) are luminous, and the small dots are not luminous. It
indicates the 32 air conditioners with the addresses from 16 to 47 are powered off. 3) In the matrix, the big and small dots of (09, 48+) and (12, 48+) are not luminous. It indicates the four air
conditioners with the addresses from 57 to 60 are outside the network. 4) All other big and small dots in the matrix are luminous. It indicates all other air conditioners are in the
network and powered on. 5) The address of the air conditioner is sum of the coordinates. For example, the address of (09, 48+) is
09+48=57. 6) The centralized controller keypad is locked, and the centralized controller communicates with the
computer normally.
41

Clima Flex Wall Mounted FCU (S type panel)

CLIFC-W 2015-05

Query page description
1) The LCD displays the query page, and the air conditioner with the address of 08 is being queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature 22°C, set temperature 20°C, cooling mode "lock".
2) In the matrix, only the big and small black dots at (00, 00+) and (01, 00+) are luminous. It indicates the in-service and power-on status of the air conditioners with the addresses of 00 and 01.
3) The centralized controller communicates with the computer normally.

Setting page description 1) The LCD displays the setting page, and queries the air conditioner with the address of 08. The mode of
the air conditioner with the address 08 is: Cooling, strong air, swing on, indoor temperature 28°C, set temperature 22°C, cooling. 2) In the matrix, only the big black dots from (08, 00+) to (16, 00+) are luminous. It indicates the air conditioners with the addresses from 08 to 16 are in service. 3) The centralized controller communicates with the computer normally.
Fault page display description 1) Query the air conditioner with the address of 08 in the query page. The air conditioner with the address
of 08 is faulty, and the fault code is 08. The big black dot below (08, 0+) blinks. 2) In the matrix, only the big and small black dots from (00, 00+) to (16, 15+) illuminate. It indicates the
in-service status of the air conditioners with the addresses of 00 and 01. 3) The centralized controller communicates with the computer normally.
42

Av. Central No. 285, Parque Logistico, Deleg. La Pila, San Luis Potosi, C.P. 78422 More Info (444) 161.50.43 info@clima-flex.com service@clima-flex.com ventas@clima-flex.com US Toll Free 01 800 201 48 16 Lada sin costo 01 800 890 59 17

/ComfortFlexMexico /ComfortFlexMx /Comfort-Flex /ClimaFlex


Adobe PDF Library 10.0