Haier Round Flow Cassette Air Conditioner

The Haier Round Flow Cassette is an ideal choice for offices, shops, hotels, and restaurants, offering consistent ventilation and advanced air distribution.

Key Features

Technical Specifications

The following tables detail the technical specifications for various Haier Round Flow Cassette models.

Cooling and Heating Performance Data

Model Cooling Output (kW) Heating Output (kW) Cooling Power Input (kW) Heating Power Input (kW) EER COP Pdesign Cooling (kW) Pdesign Heating (kW) SEER SCOP Annual Energy Consumption Cooling (kWh/a) Annual Energy Consumption Heating (kWh/a)
AB71S2SR1FA(H) / 1U71S2SR3FA 7.1 (2.0~8.2) 7.9 (2.5~8.5) 2.20 (0.50~4.00) 2.13 (0.50~4.00) 3.23 3.72 7.1 5.0 6.10 (A++) 4.00 (A+) 406 1831
AB105S2SR1FA(H) / 1U105S2SQ1FA 9.5 (2.5~10.0) 10.5 (3.0~12.5) 2.79 (0.50~4.00) 2.83 (0.50~4.00) 3.40 3.71 9.5 7.2 6.20 (A++) 4.05 (A+) 544 2792
AB125S2SR1FA(H) / 1U125S2SN3FA 12.4 (3.0~13.0) 13.5 (4.0~15.5) 4.13 (1.00~6.00) 3.85 (1.00~6.00) 3.00 3.50 12.50 8.30 6.10 (A++) 4.00 (A+) 736 3003
AB140S2SR1FA(H) / 1U140S2SN2FA 13.4 (3.5~14.0) 13.4 (3.5~14.0) 5.51 (1.00~6.50) 5.77 (1.00~6.50) 2.43 2.60 13.40 8.50 5.60 (A+) 4.00 (A+) 838 3032
AB140S2SR1FA(H) / 1U140S2SN2FB 15.0 (4.0~15.5) 15.0 (4.0~15.5) 5.51 (1.00~6.50) 5.77 (1.00~6.50) 2.43 2.60 13.40 8.50 5.62 (A+) 4.00 (A+) 838 3032
AB140S2SR1FA(H) / 1U140S2SP2FA 15.0 (4.5~16.0) 15.0 (4.5~16.0) 4.86 (1.00~6.00) 4.67 (1.00~6.00) 2.54 2.63 13.60 8.50 5.70 (A+) 3.94 (A) 800 3768
AB140S2SR1FA(H) / 1U140S2SP2FB 15.0 (4.5~16.0) 15.0 (4.5~16.0) 5.03 (1.00~6.50) 5.26 (1.00~6.50) 2.80 3.06 13.60 10.00 5.70 (A+) 3.99 (A) 782 3859
AB160S2SR1FA(H) / 1U160S2SP1FB 16.0 (5.0~17.0) 16.0 (5.0~17.0) 5.77 (1.00~6.50) 5.70 (1.00~6.50) 2.98 3.04 15.00 11.00 5.96 (A+) 3.99 (A) 880 3748

Indoor Unit Specifications

Parameter Unit AB71S2SR1FA(H) AB105S2SR1FA(H) AB125S2SR1FA(H) AB140S2SR1FA(H) AB160S2SR1FA(H)
Power Supply Ph/V/Hz 1/220~240/50/60 1/220~240/50/60 1/220~240/50/60 1/220~240/50/60 1/220~240/50/60
Airflow (H/M/L/Q) m³/h 1260/1100/900/700 1920/1750/1550/1250 1950/1650/1480/1250 1950/1650/1480/1250 2050/1950/1650/1300
Sound Power (High) dB 57 62 64 64 65
Sound Pressure (H/M/L/Q) dB(A) 42/40/38/35 45/42/38/34 47/44/38/34 47/44/38/34 48/44/38/34
Net Dimensions (W x D x H) mm 840x840x204 840x840x246 840x840x288 840x840x288 840x840x288
Packing Dimensions (W x D x H) mm 978x978x269 978x978x269 978x978x353 978x978x353 978x978x353
Net/Gross Weight kg 23/28 24/31 27/33 27/33 27/33
Panel Model - PB-950QB(H) PB-950QB(H) PB-950QB(H) PB-950QB(H) PB-950QB(H)
Panel Net Dimensions (W x D x H) mm 950x950x50 950x950x50 950x950x50 950x950x50 950x950x50
Panel Packing Dimensions (W x D x H) mm 1013x1035x125 1013x1035x125 1013x1035x125 1013x1035x125 1013x1035x125
Panel Net/Gross Weight kg 5.5/8.5 5.5/8.5 5.5/8.5 5.5/8.5 5.5/8.5

Outdoor Unit Specifications

Parameter Unit AB71S2SR1FA(H) AB105S2SR1FA(H) AB125S2SR1FA(H) AB140S2SR1FA(H) AB160S2SR1FA(H)
Power Supply Ph/V/Hz 1/220~240/50/60 1/220~240/50/60 1/220~240/50/60 3/380-415/50/60 3/380-415/50/60
Power Cable N x mm² 3 x 4.0 3 x 4.0 3 x 6.0 5 x 4.0 5 x 4.0
Connection Cable N x mm² 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5 4 x 2.5
Sound Power (High) dB 68 66 68 72 72
Sound Pressure (High) dB(A) 54 53 54 58 58
Max. Operating Current (Cooling/Heating) A 13.1 16.5 6.8 26.0 26.0
Max. Starting Current (Cooling/Heating) A 2.0 3.0 1.0 4.0 4.0
Net Dimensions (W x D x H) mm 890x340x705 920x372x765 920x372x765 950x370x965 950x370x965
Packing Dimensions (W x D x H) mm 1046x460x780 1036x478x820 1085x485x830 1050x485x1130 1050x485x1130
Net/Gross Weight kg 44.0/48.0 60.0/65.0 61.0/66.0 84.0/89.0 84.0/89.0
Compressor Type - Twin Rotary Inverter Twin Rotary Inverter Twin Rotary Inverter Twin Rotary Inverter Twin Rotary Inverter

Installation Data

Parameter Unit AB71S2SR1FA(H) AB105S2SR1FA(H) AB125S2SR1FA(H) AB140S2SR1FA(H) AB160S2SR1FA(H)
Refrigerant - R32 R32 R32 R32 R32
Liquid Line Diameter mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Gas Line Diameter mm (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Standard Pipe Length (no charge) m 10 30 30 30 30
Max. Pipe Length m 50 50 50 50 50
Max. Height Difference (Indoor/Outdoor) m 30 30 30 30 30
Factory Refrigerant Charge kg 1.23 1.70 1.70 2.30 2.30
Factory Refrigerant Charge TCO₂eq 0.83 1.15 1.15 1.55 1.55
Additional Charge per meter g/m 45 45 45 45 45
Operating Limits - Cooling (Indoor/Outdoor) °C -20~46 -20~46 -20~46 -20~46 -20~46
Operating Limits - Heating (Indoor/Outdoor) °C -20~24 -20~24 -20~24 -20~24 -20~24

Note: Data provided in this catalog is indicative and may vary. Please verify data with your supplier before purchasing.

PDF preview unavailable. Download the PDF instead.

251007 PF Com Round Flow Kassette Mono-DE Adobe InDesign 20.3 (Windows) 3-Heights(TM) PDF Optimization Shell 5.9.1.5 (http://www -tools.com)

Related Documents

Preview Haier Round Flow Cassette Air Conditioner Specifications and Features
Detailed specifications and features of the Haier Round Flow Cassette air conditioning unit, including performance data, dimensions, and installation information.
Preview Haier Cassette 360° Air Conditioner Specifications and Features
Detailed specifications, features, and performance data for the Haier Cassette 360° air conditioning unit, including cooling and heating capacities, energy efficiency ratings, sound levels, and installation dimensions.
Preview Haier Round Flow Cassette Air Conditioner: Features and Specifications
Explore the Haier Round Flow Cassette air conditioner, a versatile solution for commercial spaces. This document details its key features, including Fresh Air technology, 8-way airflow, and Wi-Fi control, alongside a summary of its comprehensive technical specifications across various models.
Preview Haier Maxi Split Range Air Conditioner Specifications
Detailed specifications and configuration options for the Haier Maxi Split Range of air conditioning units, including indoor and outdoor unit compatibility, capacity, and required accessories.
Preview Haier 1-Way Cassette Air Conditioner Technical Specifications
Comprehensive technical specifications for Haier's 1-Way Cassette air conditioning units, detailing performance data, dimensions, power requirements, and installation details for models AB25S2SA1FA(H), AB35S2SA1FA(H), AB50S2SA1FA(H), and AB71S2SA1FA(H).
Preview Haier Cassette 620 Air Conditioner: Specifications and Features
Detailed specifications, key features, and performance data for the Haier Cassette 620 series of ceiling-mounted air conditioners, including models AB25S2SC2FA(H), AB35S2SC2FA(H), and AB50S2SC2FA(H).
Preview Haier 1-Way Cassette Air Conditioner - Technical Specifications and Features
Explore the Haier 1-Way Cassette air conditioner, a sleek and space-saving solution for offices and commercial spaces. Discover its key features like compact design, UVC sterilization, and fresh air circulation, along with detailed technical specifications for cooling and heating performance.
Preview Haier Ducted Slim Low Pressure Air Conditioner Specifications
Technical specifications for the Haier Ducted Slim Low Pressure air conditioning units, including performance data, dimensions, and installation details for models ranging from 2.5kW to 7.1kW.