Eaton's Tripp Lite Series SmartPro® Extreme Temperature Network UPS Systems & Batteries, SmartRack® NEMA 3R Rack Enclosures
Power solutions designed for extreme temperatures
Unlike indoor network environments, the temperature in outdoor and remote network environments can fluctuate dramatically. Eaton Tripp Lite series extreme temperature network UPS systems and batteries are rated for operation in a wide range of temperatures, providing complete power protection in industrial, outdoor and transportation environments.
These TAA-compliant, pure sine wave UPS systems provide safe and reliable power to network equipment in traffic signals, parking ramp metering, oil fields and off-shore oil rigs, security systems, government and military facilities, tolling systems, railroad crossings, network closets at cell tower bases and other extremely hot or cold applications.
Key Features
- Rapid Deployment: All connections and controls are on the same side for ease of installation, use, and maintenance. UPS external battery connectors accommodate various Eaton Tripp Lite series extreme temperature battery solutions with multiple Ampere-hour capacities for varying runtime and fitment needs. Eaton Tripp Lite series SmartRack NEMA 3R racks and accessories offer the best protection for sensitive electronics stored in outdoor environments. Racks are available in various heights and colors.
- Robust Performance: Line-interactive technology ensures continuous operation through environmental and power quality issues. Built-in thermal management extends battery life and lowers maintenance costs. Pure sine wave output in both AC and battery modes offers continuous operation in traffic management systems, telecom edge, or surveillance equipment applications.
- Durable Construction: UPS and extreme temperature battery solutions provide reliable power protection in temperatures ranging from -40°F to +176°F (-40°C to +80°C). NEMA 3R-rated enclosures protect equipment against the ingress of water, solid foreign objects, and ice formation on the outside of the enclosure.
- Comprehensive Management and Maintenance: The LCD control panel offers a wide variety of UPS status and site power information, control options, UPS configuration settings, and event logs. Remote management reduces on-site response requests. Dry contacts allow industrial control management.
- Product Support: Eaton provides free product support via phone, email, or chat.
Product Specifications
UPS Systems
Model | VA/Watts* | Input/Output Voltage | Supported Battery System | Input/Output Connection | Operating Temperature | Rack Size | Dimensions (HxWxD) | Unit Weight |
---|---|---|---|---|---|---|---|---|
SMART1524ET | 2000/1600 | 120V | 24V (User-supplied) | Hardwire | -40°F to +176°F (-40°C to +80°C) | 3U | 5.2 x 15.8 x 9.5 in. (13.2 x 40.1 x 24.1 cm) | 32.4 lb. (14.7 kg) |
SMART1548ET | 2000/1600 | 120V | 48V (User-supplied) | Hardwire | -40°F to +176°F (-40°C to +80°C) | 3U | 5.2 x 15.8 x 9.5 in. (13.2 x 40.1 x 24.1 cm) | 32.4 lb. (14.7 kg) |
Note: 1. UPS unit comes with ANDERSON PA75 DC Connection kit. 2. Battery temperature sensor cable protects the battery system from overcharging in high-temp environments.
*Each UPS can provide the below output capacity based on ambient operating temperatures shown below:
- Output capacity: 2000VA/1600W (Ambient operating temperature: -40°C to +55°C)
- Output capacity: 1500VA/1200W (Ambient operating temperature: 55°C to 75°C)
- Output capacity: 1200VA/1000W (Ambient operating temperature: 75°C to 80°C)
Extreme Temperature Batteries (sold separately)
Model | Ampere Hour Rate | DC Voltage | Supported Battery | Input/Output Connection | Operating Temperature | Rack Size | Dimensions (HxWxD) | Unit Weight |
---|---|---|---|---|---|---|---|---|
RBC12V9ET | 8.5Ah | 12V | Connect multiple batteries of the same Ah in series/parallel to match UPS system voltage and application requirement (Max 200Ah per UPS) | T2 (M5 bolt) | -40°F to +167°F (-40°C to +75°C) | 1U | 3.88 x 5.94 x 2.55 in. (9.9 x 15.1 x 6.5 cm) | 5.77 lb. (2.6 kg) |
RBC12V20ET | 20Ah | 12V | 1U (M5 bolt) | -40°F to +167°F (-40°C to +75°C) | 6.5 x 7.12 x 2.99 in. (16.5 x 18.1 x 7.6 cm) | 14 lb. (6.4 kg) | ||
RBC12V55ET | 55Ah | 12V | 1U (M6 bolt) | -40°F to +167°F (-40°C to +75°C) | 8.12 x 8.98 x 5.45 in. (20.6 x 22.8 x 13.8 cm) | 39.45 lb. (17.9 kg) | ||
RBC12V100ET | 100Ah | 12V | 1U (M6 bolt) | -40°F to +167°F (-40°C to +75°C) | 8.41 x 12.15 x 6.65 in. (21.4 x 30.9 x 16.9 cm) | 66.56 lb. (30.2 kg) |
Accessories (User supplied):
- SMART1524ET - Connecting the Batteries to UPS recommended battery cable gauges are 6 AWG with a maximum recommended length of 6.56 ft. / 2 m.
- SMART1548ET - Connecting the Batteries to UPS recommended battery cable gauges are 8 AWG with a maximum recommended length of 6.56 ft. / 2 m.
- SMART1524ET - Requires a 24V 150A rated fuse bank. Recommended DC fusing should be installed 18 in. / 0.45 m from the battery system's positive connection wire to the UPS.
- SMART1548ET - Requires a 48V 70A rated fuse bank. Recommended DC fusing should be installed 18 in. / 0.45 m from the battery system's positive connection wire to the UPS.
NEMA 3R Outdoor Enclosures (Sold Separately)
Model | Cabinet Type | Fan Voltage | Equipment Mount | Input/Output Connection | Equipment Depth (Max) | Rack Size | Dimensions (HxWxD) | Cabinet Weight |
---|---|---|---|---|---|---|---|---|
SRN3RG12US | NEMA 3R | 120V | Front | NEMA 5-15P | 30 in. (76.2 cm) | 12U | 28.49 x 25.17 x 32.13 in. (72.4 x 63.9 x 81.6 cm) | 146.44 lb. (66.4 kg) |
SRN3RG12UHD | NEMA 3R | 120V | Side | NEMA 5-15P | 34 in. (86.4 cm) | 12U | 28.65 x 26.06 x 36.16 in. (72.7 x 66.2 x 91.8 cm) | 216.84 lb. (98.4 kg) |
SRN3RG18UHD | NEMA 3R | 120V | Side | NEMA 5-15P | 34 in. (86.4 cm) | 18U | 40.32 x 26.91 x 36.16 in. (102.4 x 68.4 x 91.8 cm) | 259.55 lb. (117.7 kg) |
Eaton Tripp Lite Series Extreme Temp Battery Runtime Chart
SMART1524ET (24V)
Operating Temp | Max Wattage Output | Load (Watts) | Backup Time @ 24VDC (min) | |
---|---|---|---|---|
24VDC 100Ah | 24VDC 200Ah | |||
75°C to 80°C | 150 | 800 | 300 | 599 |
300 | 350 | 235 | 301 | |
450 | 235 | 158 | ||
600 | 145 | 106 | ||
750 | 113 | 79 | ||
900 | 101 | 63 | ||
55°C to 75°C | 1000 | 91 | 48 | 95 |
1050 | 86 | 45 | 91 | |
1200 | 68 | 40 | 79 | |
1350 | 60 | 35 | 70 | |
1400 | 57 | 34 | 68 | |
1450 | 55 | 33 | 66 | |
-40°C to +55°C | 1500 | 54 | 32 | 63 |
1600 | 50 | 30 | 59 | |
1680 | 52 | 30 | 59 |
SMART1524ET + RBC12V55ET
Operating Temp | Max Wattage Output | Load (Watts) | Backup Time @ 24VDC (min) | |
---|---|---|---|---|
24VDC 55Ah | 24VDC 110Ah | |||
75°C to 80°C | 150 | 300 | 299 | 599 |
300 | 150 | 150 | 301 | |
450 | 106 | 106 | 211 | |
600 | 79 | 79 | 158 | |
750 | 63 | 63 | 127 | |
900 | 53 | 53 | 106 | |
55°C to 75°C | 1000 | 48 | 48 | 95 |
1050 | 45 | 45 | 91 | |
1200 | 40 | 40 | 79 | |
1350 | 35 | 35 | 70 | |
1400 | 34 | 34 | 68 | |
1450 | 33 | 33 | 66 | |
-40°C to +55°C | 1500 | 32 | 32 | 63 |
1600 | 30 | 30 | 59 |
SMART1548ET (48V)
Operating Temp | Max Wattage Output | Load (Watts) | Backup Time @ 48VDC (min) | |
---|---|---|---|---|
48VDC 100Ah | 48VDC 200Ah | |||
75°C to 80°C | 160 | 1581 | 320 | 1581 |
320 | 751 | 160 | 760 | |
480 | 491 | 103 | 491 | |
640 | 331 | 72 | 331 | |
800 | 268 | 54 | 268 | |
960 | 221 | 43 | 221 | |
55°C to 75°C | 1000 | 212 | 36 | 212 |
1120 | 189 | 31 | 189 | |
1200 | 176 | 29 | 176 | |
1280 | 136 | 27 | 136 | |
1440 | 120 | 24 | 120 | |
1600 | 106 | 22 | 106 | |
-40°C to +55°C | 1600 | 106 | 22 | 106 |
SMART1548ET + RBC12V55ET
Operating Temp | Max Wattage Output | Load (Watts) | Backup Time @ 48VDC (min) | |
---|---|---|---|---|
48VDC 55Ah | 48VDC 110Ah | |||
75°C to 80°C | 160 | 561 | 320 | 1123 |
320 | 282 | 160 | 564 | |
480 | 198 | 103 | 396 | |
640 | 149 | 72 | 297 | |
800 | 119 | 54 | 238 | |
960 | 99 | 43 | 198 | |
55°C to 75°C | 1000 | 95 | 35 | 190 |
1120 | 85 | 31 | 170 | |
1200 | 79 | 29 | 158 | |
1280 | 74 | 27 | 149 | |
1440 | 66 | 24 | 132 | |
1600 | 59 | 22 | 119 | |
-40°C to +55°C | 1600 | 59 | 22 | 119 |
SMART1548ET + RBC12V20ET
Operating Temp | Max Wattage Output | Load (Watts) | Backup Time @ 48VDC (min) | |
---|---|---|---|---|
48VDC 20Ah | 48VDC 40Ah | |||
75°C to 80°C | 160 | 204 | 320 | 408 |
320 | 103 | 160 | 205 | |
480 | 72 | 103 | 144 | |
640 | 54 | 72 | 108 | |
800 | 43 | 54 | 86 | |
960 | 36 | 43 | 72 | |
55°C to 75°C | 1000 | 35 | 36 | 69 |
1120 | 31 | 35 | 62 | |
1200 | 29 | 31 | 58 | |
1280 | 27 | 29 | 54 | |
1440 | 24 | 27 | 48 | |
1600 | 22 | 24 | 43 | |
-40°C to +55°C | 1600 | 22 | 24 | 43 |
Product Information
For more information, visit TrippLite.Eaton.com/SmartProUPS.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2024 Eaton. All Rights Reserved.
Printed in USA. 23-08-129. January 2024.
Eaton, Tripp Lite, SmartPro and PowerAlert are registered trademarks. All other trademarks are property of their respective owners.
Follow Eaton on social media for the latest product and support information: [Facebook Icon] [X Icon] [YouTube Icon]