Southwire CSA FAS/LVT Fire Alarm Signaling and Low Voltage Thermostat Cable
This document provides detailed specifications, applications, and product information for Southwire's CSA FAS/LVT cables, designed for reliable performance in fire alarm signaling systems and low voltage thermostat applications.
Product Overview
The Southwire® CSA FAS/LVT cable is a CSA Fire Alarm Signaling (FAS) Cable and Low Voltage Thermostat (LVT) Cable. It is available with either a Red Jacket or a Brown Jacket. The cable features unshielded construction with solid bare copper conductors.
Temperature Ratings:
- FAS: Rated -20°C to 105°C
- LVT: Rated -20°C to 60°C
The cable is designed for durability and ease of use, incorporating a ripcord under the jacket for simplified jacket stripping.
Applications
Southwire® FAS/LVT is suitable for the following installations:
- Connecting Fire Alarm Signaling devices within a fire protective signaling system.
- Low Voltage Thermostat applications in HVAC Systems.
- Where FAS 105 cable is specified (300V).
- Where LVT 60 cable is specified (30V).
Standards & References
- Listed to CSA C22.2, No. 208
- File listing LL90458
- Flame Tests: CSA FT4
Features
- Rated for temperature range of -20°C to 105°C (FAS) or -20°C to 60°C (LVT).
- High-grade PVC flame retardant insulation and jacket materials provide excellent color definition and workability.
- Ripcord under jacket for jobsite ease of use.
Construction
Southwire® FAS/LVT is manufactured with solid bare copper conductors and color-coded PVC insulation. Conductors are twisted unless noted. A rugged, flame-retardant, flexible PVC jacket is extruded over the cable core. A ripcord is included under the jacket for jobsite jacket strip-back. Colors and packaging indicated in the tables are the most popular, and others may be available.
Print Legend (Typical)
SOUTHWIRE LL90458 F CSA FAS 105°C 300V FT4 2/C 18 AWG (0.824mm²) CSA LVT 60°C 30V FT4
Specifications
AWG | No. of Cond. | Color Code | Insulation Thickness (Inches) | Jacket Thickness (Inches) | Nominal Wall Diameter (Inches) | Nominal Diameter (Inches) | Weight (Lbs/Mft) | Capacitance (pF/ft) | |
---|---|---|---|---|---|---|---|---|---|
Red Part Code | Brown Part Code | ||||||||
2 flat | A | B | 0.033 | 0.032 | .162 x .218 | 19.3 | 29.8 | ||
18 | 3 | A | B | 0.033 | 0.032 | .232 | 26.7 | 25.4 | |
4 | A | B | 0.033 | 0.035 | .251 | 33.3 | 25.4 | ||
5 | A | C | 0.035 | 0.035 | .272 | 39.6 | 25.4 | ||
6 | A | C | 0.035 | 0.035 | .295 | 47.6 | 25.4 | ||
8 | A | C | 0.035 | 0.035 | .318 | 60.5 | 25.4 | ||
16 | 3 | A | 0.035 | 0.035 | .242 | 36.1 | 28.0 | ||
5 | A | 0.035 | 0.035 | .289 | 54.0 | 28.0 |
All dimensions are nominal and subject to normal manufacturing tolerances.
Color Code A: Black, Red, Green, Blue, Brown, Orange, Black/White, Red/White
Color Code B: Black, White, Red, Green
Color Code C: Black, White, Red, Blue, Orange, Yellow, Green, Brown
Put-Ups
Put-up codes indicate spool sizes. Add a two-digit suffix from the table below to the six-digit base part number. Consult your distributor for minimum order quantities, lead times, and premium pricing.
Code | Spool (Meters) | Spool (Feet) | 18 AWG Part No.s | 16 AWG Part No.s |
---|---|---|---|---|
75 | 75 | 246 | 75 | 03 |
15 | 150 | 492 | 15 | 01 |
30 | 300 | 984 | 30 | 02 |
Common Items
Part Number | Construction | Color Code | Jacket Color | Packaging |
---|---|---|---|---|
55765975 | FAS 18/2 Sol BC Flat | Bk, Rd | Red | 246Sp (75M) |
55765915 | FAS 18/2 Sol BC Flat | Bk Rd | Red | 429Sp (150M) |
55765930 | FAS 18/2 Sol BC Flat | Bk, Rd | Red | 984Sp (300M) |
55762275 | FAS 18/3 Sol BC Twst | Bk, Rd, Gn | Red | 246Sp (75M) |
55762215 | FAS 18/3 Sol BC Twst | Bk, Rd, Gn | Red | 429Sp (150M) |
55762230 | FAS 18/3 Sol BC Twst | Bk, Rd, Gn | Red | 984Sp (300M) |
55762475 | FAS 18/4 Sol BC Twst | Bk, Rd, Gn, Be | Red | 246Sp (75M) |
55762415 | FAS 18/4 Sol BC Twst | Bk, Rd, Gn, Be | Red | 429Sp (150M) |
55762430 | FAS 18/4 Sol BC Twst | Bk, Rd, Gn, Be | Red | 984Sp (300M) |
55762675 | FAS 18/5 Sol BC Twst | Bk, Rd, Gn, Be, Bn | Red | 246Sp (75M) |
55762615 | FAS 18/5 Sol BC Twst | Bk, Rd, Gn, Be, Bn | Red | 429Sp (150M) |
55762630 | FAS 18/5 Sol BC Twst | Bk, Rd, Gn, Be, Bn | Red | 984Sp (300M) |
55762875 | FAS 18/6 Sol BC Twst | Bk, Rd, Gn, Be, Bn, Oe | Red | 246Sp (75M) |
55762815 | FAS 18/6 Sol BC Twst | Bk, Rd, Gn, Be, Bn, Oe | Red | 429Sp (150M) |
55762830 | FAS 18/6 Sol BC Twst | Bk, Rd, Gn, Be, Bn, Oe | Red | 984Sp (300M) |
55765775 | FAS 18/8 Sol BC Twst | Bk, Rd, Gn, Be, Bn, Oe, Bk/We, Rd/We | Red | 246Sp (75M) |
55765730 | FAS 18/8 Sol BC Twst | Bk, Rd, Gn, Be, Bn, Oe, Bk/We, Rd/We | Red | 984Sp (300M) |
57993402 | FAS 16/3 Sol BC Twst | Bk, Rd, Gn | Red | 984Sp (300M) |
58072602 | FAS 16/5 Sol BC Twst | Bk, Rd, Gn, Be, Bn | Red | 984Sp (300M) |
55765875 | FAS 18/2 Sol BC Flat | Bk, We | Brown | 246Sp (75M) |
55765815 | FAS 18/2 Sol BC Flat | Bk, We | Brown | 429Sp (150M) |
55765830 | FAS 18/2 Sol BC Flat | Bk, We | Brown | 984Sp (300M) |
55762175 | FAS 18/3 Sol BC Twst | Bk, We, Rd | Brown | 246Sp (75M) |
55762115 | FAS 18/3 Sol BC Twst | Bk, We, Rd | Brown | 429Sp (150M) |
55762375 | FAS 18/4 Sol BC Twst | Bk, We, Rd, Gn | Brown | 246Sp (75M) |
55762575 | FAS 18/5 Sol BC Flat | Bk, We, Rd, Be, Oe | Brown | 246Sp (75M) |
55762515 | FAS 18/5 Sol BC Flat | Bk, We, Rd, Be, Oe | Brown | 429Sp (150M) |
55762775 | FAS 18/6 Sol BC Flat | Bk, We, Rd, Be, Oe, Yw | Brown | 246Sp (75M) |
55763015 | FAS 18/8 Sol BC Flat | Bk, We, Rd, Be, Oe, Yw, Gn, Bn | Brown | 246Sp (75M) |
Additional Considerations
- Store indoors, in a dry, climate-controlled location maintained above 0°C.
- If stored below 0°C, bring to above 0°C for 24 hours prior to working cables.
- Maintain project conditions above 0°C and normal humidity during installation.
- Never apply paint over cable. Field application of paint on cable invalidates the material's flame retardant properties, flame test listings, and any smoke-generation listings inherent in the material.