Southwire Surge Guard* RV Power Protection

Model 34950

50A Surge Guard* Portable Device with LCD Display

Southwire Surge Guard* RV power protection devices protect your RV from low quality or incorrect shore power. Normally, shore power should be around 115–120 Volts AC from L1 or L2 to Neutral, or 240V from L1 to L2. When power falls too far outside this range, it represents a poor or hazardous condition to your RV's electrical system. Surge Guard RV power protection devices provide protection to your RV by turning off power when the line voltages L1 or L2 fall below 102 Volts AC or go above 136 Volts AC.

This device will protect your electrical system from a reverse polarity condition which indicates that the hot and neutral lines of shore power are swapped or reversed. This can be hazardous to equipment and safety. Your device will not connect power to your RV until the reverse polarity fault is corrected.

In the event your Surge Guard device is not functioning as expected, perform the following troubleshooting steps in order to determine and correct any malfunctions. Note: Testing should be performed with AC units and electrical appliances turned off, then verified with appliances turned on.

Connect the shore power cord to a 240V, 50A power source. The LCD screen will display “DELAY” for 10 seconds while the Surge Guard device is monitoring the incoming power. Note that this guide also applies if using 120V, 30A power with a suitable adapter. The device will take 128 seconds to reset if the power is shut off due to a high/low voltage fault.

PROBLEM TROUBLESHOOTING STEPS
Coach powers up after 10 seconds, but then turns off after another 7-10 seconds. The device may be operating properly, and you may have a low voltage condition. In this case, turn off as many loads as possible. It is not safe to operate some equipment with low voltage. Verify that the input voltage is greater than 102VAC with loads turned on and off.
Coach does not power up after 10 seconds after connecting to shore power. Check the LCD display and the Caution When Flashing light (Red LCD). Check voltage with voltmeter at connection.
LCD shows a fault such as "L1 or L2 LOW" or "L1 or L2 HIGH" and the "CAUTION WHEN FLASHING" light is blinking. There could be an open conductor or unsafe power. Check the input connectors, shore power cord, and adapter (if applicable). Call Southwire Technical Support at 1-800-780-4324.
L1 and L2 are within range (102 – 136VAC) and there is no power. Call Southwire Technical Support at 1-800-780-4324.
LCD screen displays “REVERSE POLARITY” and the "CAUTION WHEN FLASHING" light is blinking. Shore power connections are reversed and you have an unsafe condition. In this case, notify your park of the condition in order to correct the fault.
A fault occurs such as a "L1 LOW" or "L1 HIGH" during normal operation when shore power is within good operating range. The device will turn off power to the RV and will display a fault message on the LCD display. If the power returns to normal, the device will display "DELAY" on the LCD screen and will wait 128 seconds before turning power to the RV back on.

1. Low Voltage – If the input voltage drops below 102VAC for more than 7 seconds, the power will be removed to protect your electronics. This condition may be caused by overloading the park's power grid. Try reducing your loads. Otherwise, do not operate until power is restored to safe levels. Once the voltage returns to the acceptable range, the unit will take 128 seconds to restore power.
2. High Voltage - If the input voltage increases above 136VAC for more than 7 seconds, power will be removed to protect your electronics. Do not operate until power is restored to safe levels. Once the voltage returns to the acceptable range, the unit will take 128 seconds to restore power.
3. Line 1, Line 2, or Neutral Open – Check all input wiring to the device. Check the shore power cord and wiring from the generator if applicable. Check/replace adapter if reducing down to 120V, 20A service. Notify park for shore power problems if applicable.
4. Caution When Flashing Light – If the caution light is on, read the LCD indicator for any possible fault.

TROUBLESHOOTING ERROR CODES

ERROR MESSAGE DESCRIPTION
REPLACE SURGE Surge Expended: The Surge Guard built-in surge protection has been sacrificed to protect your equipment and is no longer functioning properly. The unit is recommended to be replaced.
OPEN GROUND Open Ground: Disconnect unit. Use a voltmeter to check the ground and neutral. Voltage should read -0-. If not, finding another power source is recommended.
REVERSE POLARITY Any Line Wired to Neutral: Use a voltmeter to check for voltage on ground or neutral. Voltage should read -0-. If not, finding another power source is recommended.
L2 HIGH WAS 137V
L1 HIGH WAS 137V
High Voltage: Voltage is over recommended operation, check with power source to lower voltage to >136V.
L1 LOW WAS 99V
L2 LOW WAS 99V
Low Voltage: Voltage is under recommended operation, check with power source to raise voltage to <102V.
NEUTRAL
WAS 65A
High Neutral Current: Voltage on neutral return over 65A on load side. Check with voltmeter to verify voltage on the neutral at the connection. If voltage exists, it is recommended to find another power source.
L1 AMPS
WAS 56A
Current High: Current exceeds the recommended operation. Check connection with voltmeter and verify voltages are within normal operation. If not, it is recommended to find another power source.
RECEPT
OVERHEAT
Over Temperature: Temperature exceeds the recommended operation. Check connection with voltmeter and verify voltages are within normal operation. If temperature exceeds, disconnect unit, allow to cool completely and recommend to find another power source.
GND HIGH
WAS 35V
High Ground Voltage: Voltage between neutral and ground is over allowable threshold. Most common cause is no neutral/ground bond at the service panel. Use voltmeter to check each line to neutral, then each line to ground. If there is a difference in potential, consult with a qualified electrician.
OPEN
NEUTRAL
Load Side Open Neutral: Unit has sensed an open neutral on the coach side. Call Southwire technical support at the number listed below.

PDF preview unavailable. Download the PDF instead.

506-00023A-34950-Troubleshooting-Guide Adobe PDF Library 15.0 Adobe InDesign CC 2017 (Windows)

Related Documents

Preview Southwire Surge Guard RV Power Protection: Comprehensive Guide
Explore the full range of Southwire Surge Guard RV power protection solutions, including portable surge protectors, hardwires, and automatic transfer switches. Protect your RV from electrical hazards like surges, voltage fluctuations, and wiring faults with advanced features and reliable performance.
Preview Southwire CSA FAS/LVT Fire Alarm Signaling and Low Voltage Thermostat Cable
Detailed specifications and applications for Southwire CSA FAS/LVT cables, designed for fire alarm signaling systems and low voltage thermostat applications. Features include temperature ratings, construction details, and available configurations.
Preview Southwire 1970 Series X-Treme Box Temporary Power Distribution Unit
Information on the Southwire 1970 Series X-Treme Box, a rugged and safe temporary power distribution unit for job sites. Features include weather-proof receptacles, premium electrical components, and GFCI protection for each 20A outlet. Available in sled base and roll cage versions.
Preview Southwire Elite 300 Series Portable Power Station: Operating and Maintenance Instructions
Comprehensive guide to operating, charging, and maintaining the Southwire Elite 300 Series Portable Power Station (Model 53251). Includes technical specifications, display features, charging methods, powering devices, troubleshooting, safety instructions, and warranty information.
Preview Southwire HS285® Ultra-High Strength ACSS Conductor Technical Specifications
Explore the technical specifications and benefits of Southwire's HS285® Ultra-High Strength ACSS Conductor, designed for superior performance, increased line capacity, and cost-effective reconductoring in overhead power transmission.
Preview Southwire CDL6S-16WPCS-U LED Recessed Luminaires Specifications | ENERGY STAR Certified
Detailed specifications for the Southwire CDL6S-16WPCS-U LED recessed luminaires, a ENERGY STAR certified light fixture. Includes information on lumens, color temperature, power, CRI, and more.
Preview Southwire CDL6S-16WPCS-U LED Recessed Luminaires Specifications | ENERGY STAR Certified
Detailed specifications for the Southwire CDL6S-16WPCS-U LED recessed luminaires, a Southwire product certified by ENERGY STAR. Includes information on lumens, color temperature, power, CRI, and more.
Preview Southwire LED Overhead Lights Operating Instructions T90060, T90100, T90150, T90200
Operating instructions, installation guide, and warranty information for Southwire T90060, T90100, T90150, and T90200 LED Overhead Lights. Includes product specifications, wiring instructions, safety warnings, and claims procedure.