SHUT-OFF DAMPERS
Airflow setting and control
Damper 11055116
RGE Ø355 Manual and Motorised with kit
The RGE damper uses a motor or manual operation to balance and isolate a circular ducting system, while ensuring a very low leak rate.
PRODUCT BENEFITS
- Class C airtight performance as per EN 1751
- Manual or motorised operation using plate kit
Principles of Operation
The flap of the RGE manual damper is opened and closed by rotating a handle or using a motor after a motor plate is installed. If it is closed, the airtight seal is formed by the moulded seal on the disc.
Product Description
The RGE damper balances airflow and isolates a circular ducting system. It features a sealed disc to minimise air leaks between upstream and of the damper in the closed position and double-lip airtight seals on each junction to minimise leaks with the rest of the system. Its top jumper enables overlaid insulation without covering the lockable handle.
Fields of Application
Non-residential buildings
Installation
- Installed in circular ducts.
Diagram illustrating the installation of a motorisation plate onto the RGE damper. It shows a circular duct connection, the damper body, and a mounting plate with a central shaft connection, labeled 'For CM model only' and indicating a Ø12 connection.
Reference Arguments
- Damper air tightness provided by jointed disk (overmoulding on disk providing good long-term resistance).
- Double-lip airtight seal on each junction.
- RGE: screw-locked adjustment handle. Zamak shafts.
- Upper jumper provides overlaid insulation without covering handle.
- To motorise RGE dampers beyond 355 mm: order the universal adapter plate (11055122) separately to enable installation of any motor.
- Motor power: 2 N/m for RGE Ø 125 to 200, 4-5 N/m for RGE Ø 250 to 500.
- Beyond Ø 500 mm, for reasons of mechanical resistance, use a CRGE volume control damper with connecting plates of the same Ø as the ducting.
Main Characteristics
- Galvanised steel construction.
- Airtight performance upstream/downstream of disc: class 4 as per EN 1751.
- Class C product airtight performance as per EN 12237.
- Motor plate ordered separately.
- Motor ordered separately: 4-5 N.m for RGE Ø 355 to 450 and 10 N.m for RGE Ø 500 mm.
- Temperature range: 0 to 120°C.
Dimensional Data
Variants | H (mm) | L (mm) | Ø (mm) | Weight (kg) |
---|---|---|---|---|
11055116 | 85 | 200 | 355 | 2,94 |
Schematic drawing of the RGE damper showing its circular profile with dimensions labeled: H (height) 85 mm, L (length) 200 mm, and Ø (diameter) 355 mm. Additional internal dimensions are indicated as 165 mm and 126 mm.
Regulatory Data
Variants | Airtightness class | Upstream/downstream airtightness class |
---|---|---|
11055116 | C | 4 |
Accessories
Description | Variants |
---|---|
MOTOR PLATE KIT FOR DIAMETERS 355 to 500 mm | 11055122 |
LM MOTOR 24A ON/OFF | 11055042 |
LM MOTOR 230A ON/OFF | 11055051 |
LM MOTOR 230A SR PROPORTIONAL | 11055052 |
LM MOTOR 24A SR PROPORTIONAL | 11055053 |
LF MOTOR 24 SR PROPORTIONAL | 11055054 |
MOTOR LF230 ON/OFF | 11055081 |
LF MOTOR 24 ON/OFF | 11055082 |