Comfort-Aire BHD-501 Owner's Manual

This Owner's Manual is provided and hosted by Appliance Factory Parts.

Appliance Factory Parts
Experts in BBQ, Humidifier, & Appliance Parts
1-800-955-7075

Shop genuine replacement parts for COMFORT-AIRE BHD-501

Find Your COMFORT-AIRE Dehumidifier Parts - Select From 129 Models


HEAT CONTROLLER, INC.

Comfort Cire

Dehumidifier

MODELS: BHD-301, BHD-501, BHD-651

Service Manual

CAUTION


CONTENTS

1. PREFACE

2. CIRCUIT DIAGRAM

3. DISASSEMBLY INSTRUCTIONS

4. TROUBLESHOOTING GUIDE

5. EXPLODED VIEWS

6. REPLACEMENT PARTS LIST


1. PREFACE

This Service Manual provides various service information, including the mechanical and electrical parts. This dehumidifier was manufactured and assembled under the strict quality control procedures. The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.

1.1 SAFETY PRECAUTIONS

1.2 FEATURES AND DIMENSIONS

1.2.1 FEATURES

1.2.2 DIMENSIONS (mm/in)

A diagram showing the front and side dimensions of the dehumidifier. Front view shows dimensions 385 mm (15 5/32 in). Side view shows dimensions 340 mm (13 3/8 in) width and 540 mm (21 1/4 in) height.

Figure 1

1.3 SPECIFICATIONS

ITEMS MODELS BHD-301 BHD-501 BHD-651
CAPACITY(Pints/24hrs) 30 50 65
POWER SUPPLY(Phase, V,Hz) 115V,60Hz 115V,60Hz 115V,60Hz
INPUT(W) 480 630 830
RUNNING CURRENT(A) 5.9 5.7 8.4
ENERGY FACTOR(L/kw.h) 1.23 1.56 1.54
REFRIGERANT R134a R22 R22
REFRIGERANT CHARGE, oz(g) 5.29(150) 7.23(205) 8.82(250)
THERMISTOR OPEN 33.8°F(1±0.5°C) 33.8°F(1±0.5°C)
CLOSE 50°F(10±0.5°C) 50°F(10±0.5°C)
SOLENOID VALVE Using Temp/Humid.:-4~122°F(-20~50°C)/95%RH ↓ Rating: 7W/90mA Using Temp/Humid.:-4~122°F(-20~50°C)/95%RH ↓ Rating: 7W/90mA
COMPRESSOR MODEL No. LX86HAQG QA084CBC QA114CBD
TYPE P6R8MC
P.T.C ASSEMBLY "WORKING TIME:0.3~1.3sec RETURN TIME:65sec"
MAXIMUM AMPERE 10A
VOLTAGE 200V
P.I.D. ECTOR OVERLOAD PROTECTOR FOR COMPRESSOR INTERNAL PROTECTOR(FUSE)FOR MOTOR INTERNAL PROTECTOR(FUSE)FOR MOTOR INTERNAL PROTECTOR(FUSE)FOR MOTOR
CAPACITOR 35µF,270VAC 35µF,270VAC 35µF,270VAC
MOTOR ASSEMBLY, SINGLE Shaded pole motor, 72W/1.4A, Thermal cutoff:266°F/130°C Shaded pole motor 91W/1.8A, Thermal cutoff:266°F/130°C Shaded pole motor 91W/1.8A, Thermal cutoff:266°F/130°C
SWITCH ASSEMBLY, MICRO 15A/250VAC 15A/250VAC 15A/250VAC
OUTSIDED MENSIONS WxHxD, mm(in) 385X540X340(15 5/32 x 21 1/4 x 13 3/8) 385X540X340(15 5/32 x 21 1/4 x 13 3/8) 385X540X340(15 5/32 x 21 1/4 x 13 3/8)
NET WEIGHT,kg(lbs) 23.1(51) 20.4(45) 22.2(49)

*NOTE: Specifications are subject to minor change without notice for further improvement.

1.4 CONTROL TYPE

1.4.1 Mechanical type

A diagram shows the control panel with knobs for Humidity Control and Fan Speed, and an Auto Shut-Off indicator light.

Figure 2

Humidity Control

When you first use the dehumidifier, turn the humidity control to 5 or 6. If you still have moisture, turn the humidity control to a higher setting. MAX is the highest setting. When excess moisture and dampness odors are gone, adjust the control to a lower setting. Use the dehumidifier as long as excess moisture is present.

Fan Speed

The fan control adjusts the fan speed. Set the fan control to HIGH for maximum moisture removal. When the humidity has been reduced and quiet operation is preferred, set the fan control to LOW.

Auto Shut-Off

1.4.2 Electronic type

A diagram shows the electronic control panel with digital displays for humidity and timer settings, and buttons for Power, Timer, and Humidity Control.

Figure 3

Fan Speed
Timer
Bucket Full Indicator

This light glows when the water bucket is full and needs to be emptied.

Auto Restart

Once power is restored after a power outage, the unit returns to its previous operation setting after a 2 minute delay. The fan runs immediately when the power is restored.

Power

Operation starts when this button is pressed and stops when the button is pressed again.

Humidity Control

1.5 HOW TO OPERATE DEHUMIDIFIER

1.5.1 HOW DOES THE DEHUMIDIFIER WORK?

Moist, humid air is drawn over a cold refrigerated dehumidifying coil. Moisture in the air condenses on this coil and drains into a bucket (or through the bucket into a hose and drain).

Dry, clean air is drawn over the condenser where it is actually heated several degrees and discharged out the rear grill into the room. (See Figure 4)

A diagram illustrates the airflow through the dehumidifier, showing humid air entering, passing over the evaporator coil, collecting in the bucket, and dry air being discharged.

Figure 4

1.5.2 LOCATION FOR THE DEHUMIDIFIER

A diagram shows the recommended spacing around the dehumidifier for optimal air circulation.

Figure 5

The operation of dehumidifier in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet, unless there is adequate circulation of air in and out of the area.

1.5.3 MICRO SWITCH

The micro switch assembly, which is located on the drain pan of inside unit, automatically shuts off the dehumidifier when the bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again turns itself on.

1.5.4 AUTO DEFROST

When frost builds up on the cooling coils, the unit will automatically cycle off until the frost disappears. The fan continues to run.

NOTE: The unit will not operate satisfactorily if the room temperature is below 65°F (18°C). If the dehumidifier is operated in low temperature conditions frost can form in the evaporator coil and the unit will cycle ON/OFF repeatedly. In this case, please check your room temperature conditions and stop the unit.

NOTE: The low temperature operation feature in the BHD-501 and BHD-651 models will continuously cycle up to a temperature of 42°F (6°C).

1.5.5 HUMIDITY CONTROLLER

1.5.5.1 Mechanical Type

A diagram shows a circular dial for humidity control with settings from Off to Max, and corresponding relative humidity percentages.

Figure 6

The humidity control can be set anywhere between Off and Max for normal operation. If you need more dehumidification, turn the Humidity Control toward Max. If you need less dehumidification, turn the Humidity Control toward Off. The relative humidity range is from 20% to 80%. (See Figure 6) Turn the Humidity Control to Off to stop the unit manually.

1.5.5.2 Electronic Type

A diagram shows the electronic control panel with displays for current and set humidity, and buttons for Power and Humidity Control.

Figure 7

The humidity control can be set 'on' or 35%-70% RH(Relative Humidity) for normal operation. (See Figure 7) If you need drier air, press the SET Humidity Control button. If you need moister air, press the PRESENT Humidity Control button. Press the Power button to stop the unit manually.

1.5.6 DRYER (BHD-301)

Dryer is used to prevent capillary blockage from moisture in the refrigerant system and H/E, condenser and evaporator. Also, dryer is used to remove corrosion of the components.

NOTE: When dryer is replaced, proper injection to capillary is needed. On opening the dryer, it should be welded instantly. The oxidization of dryer inside and all tubes inside after welding can be prevented.

A diagram shows a dryer component.

Figure 8

2. CIRCUIT DIAGRAM

MODEL: BHD-301

A wiring diagram for the BHD-301 model, showing connections between the main PCB, various switches, motor, compressor, and other components.

NO. DESCRIPTION PART NO. BHD-301 Q'TY RE- MARKS
1 POWER CORD ASSEMBLY 6411A20001Z 1 S
2 SWITCH, ROCKER 6600FX5001G 1 S
3 MOTOR ASSEMBLY 4681A20040J 1 S
4 PTC ASSEMBLY 6748C-0003D 1 S
5 RE-COMPRESSOR, SET 2521C-A8626 1 S
6 OLP 6750C-0009E 1 S
7 PWB(PCB) ASSEMBLY, DISPLAY 6871A20289B 1 S
8 SENSOR ASSEMBLY 6877A30013L 1 S
9 SWITCH ASSEMBLY, ROTARY 6601A30001B 1 S
10 SWITCH ASSEMBLY, MICRO 6600A30003C 1 S
11 PWB(PCB) ASSEMBLY, MAIN 6871A10142A 1 S

* S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS

MODEL: BHD-501/BHD-651

A wiring diagram for the BHD-501/BHD-651 models, showing connections between the main PCB, various switches, motor, compressor, and other components.

NO. DESCRIPTION PART NO. BHD-501 PART NO. BHD-651 Q'TY RE- MARKS
1 POWER CORD ASSEMBLY 6411A20001Z 6411A20001Z 1 S
2 MOTOR ASSEMBLY 4681A20040J 4681A20040K 1 S
3 CAPACITOR OCZZA20001R OCZZA20005J 1 S
4 COMPRESSOR, SET 2520UCAA014 2520UCBA007 1 S
5 OLP. 6750U-L058A 6750U-L048A 1 S
6 PWB(PCB) ASSEMBLY, DISPLAY 6871A20460A 6871A20460A 1 S
7 SENSOR ASSEMBLY 6877A30013L 6877A30013L 1 S
8 SWITCH ASSEMBLY, MICRO 6600A30003C 6600A30003C 1 S
9 PWB(PCB) ASSEMBLY, MAIN 6871A10141C 6871A10141C 1 S
10 COIL ASSEMBLY, SOLENOID 6421A20003V 6421A20003V 1 S

* S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS

3. DISASSEMBLY INSTRUCTIONS

3.1 MECHANICAL PARTS

3.1.1 BUCKET AND AIR FILTER
  1. Turn the Humidity Control off (Mechanical type) or press the power button off. (Electronic type)
  2. Disconnect the power supply.
  3. Remove the bucket. (See Figure 9)
  4. Pull out the air filter. (See Figure 10)

Figure 9 shows how to remove the bucket. Figure 10 shows how to remove the air filter.

3.1.2 FRONT CASE AND REAR GRILLE
  1. Remove 2 screws which fasten the front grille.
  2. Pull the front grille forward and upward. (See Figure 11)
  3. Remove 6 screws that secure the rear grille.
  4. Remove the rear grille. (See Figure 12)

Figure 11 shows how to remove the front grille. Figure 12 shows how to remove the rear grille.

3.1.3 CABINET AND CONTROL BOX
  1. Remove the Bucket, the Air filter and Front grille according to the procedure above.
  2. Remove 1 screw that fastens Control box. (See Figure 13)
  3. Remove 9 screws on all sides of the cabinet.
  4. Lift the Cabinet from the base. (See Figure 13)
  5. Remove a screw fasten the earth wire on the inside of control box.
  6. Remove 1 screw that fasten control box and unhook control box from hook on the shroud. (See Figure 14)

Figure 13 shows lifting the cabinet. Figure 14 shows removing the control box.

3.2 CONTROL PARTS

3.2.1 POWER CORD ASSEMBLY
  1. After opening the control box, remove the screw that holds the ground wire. (See Figure 15)
  2. Disconnect the remaining leads of the power cord from the PWB(PCB) ASSEMBLY, MAIN, then remove it from the control box.

Figure 15 illustrates removing the ground wire screw and disconnecting the power cord leads.

3.2.2 SENSOR ASSEMBLY
  1. Disconnect the sensor assembly from the PWB(PCB) ASSEMBLY, MAIN.
  2. Remove the screw which fastens the humidity sensor. (See Figure 16)
  3. Remove the thermistor from the holder. (See Figure 16)
  4. Disconnect the switch wires from the micro switch assembly. (See Figure 16)

Figure 16 illustrates removing the humidity sensor, thermistor, and micro switch wires.

3.2.3 PWB(PCB) ASSEMBLY, MAIN
  1. Disconnect all leads of the motor and the compressor from PWB(PCB) ASSEMBLY, MAIN.
  2. Remove the screw which fastens the PWB(PCB) ASSEMBLY, MAIN and pull it out after unhooking from 2 rectangular holes of the control box (lower). (See Figure 17)

Figure 17 illustrates removing the main PWB(PCB) assembly.

3.2.4 CAPACITOR (Except BHD-301)
  1. Remove the screw that fastens the capacitor. (See Figure 17)
  2. Disconnect all leads from the capacitor and then remove it from control box.
3.2.5 MICRO SWITCH ASSEMBLY
  1. Turn the nut counterclockwise and pull out the micro switch from the drain pan. (See Figure 18)

Figure 18 illustrates removing the micro switch assembly.

3.2.6 COIL ASSEMBLY, SOLENOID (BHD-501, BHD-651)
  1. Disconnect the housing of the COIL ASSEMBLY, SOLENOID from the PCB(PWB) ASSEMBLY, MAIN.
  2. Remove the screw that fastens the COIL ASSEMBLY, SOLENOID. (See Figure 19)
  3. Pull it out upwards.

Figure 19 illustrates removing the solenoid coil assembly.

3.2.7 CONTROL PANEL
3.2.6.1 CONTROL PANEL - Mechanical Type (BHD-301)
  1. Disconnect housing and all leads of the rocker switch, SWITCH ASSEMBLY, ROTARY and PWB(PCB) ASSEMBLY, DISPLAY from PWB(PCB) ASSEMBLY, MAIN (3.1.3)
  2. Pull out the knob assembly.
  3. Remove the nut which fastens the SWITCH ASSEMBLY, ROTARY.
  4. Remove the knob of the rotary switch by pulling it upward.
  5. Pull out the rocker switch by pushing the hooks on the both sides of rocker switch.
  6. Pull out the PWB(PCB) ASSEMBLY, DISPLAY after turning over both hooks of the display cover.

Figure 20 illustrates the disassembly of the control panel for the mechanical type.

3.2.6.2 CONTROL PANEL - Electronic Type (BHD-501, BHD-651)
  1. Disconnect the housing of the PWB(PCB) ASSEMBLY, DISPLAY from PWB(PCB) ASSEMBLY, MAIN (3.1.3).
  2. Remove 6 screws that secure the PWB(PCB) ASSEMBLY, DISPLAY to the display cover.

Figure 21 illustrates the disassembly of the control panel for the electronic type.

3.2.8 FAN AND MOTOR
  1. Turn the nut left and full out the Fan by hands carefully.
  2. Remove 2 screws that fasten Heat Exchange.
  3. Lift the H/E and open the H/E around 45 degree clockwise carefully. (See Figure 22)
  4. Unfasten 3 screws that secure the Motor and earth wire. (See Figure 23)
  5. Remove the Motor.

Figure 22 shows lifting the Heat Exchange. Figure 23 shows removing the motor.

3.2.9 SHROUD AND DRAIN PAN
  1. Discharge the refrigerant by using a refrigerant Recovery System.
  2. After purging the unit completely, unbrace the Discharge and the Suction tube connected compressor carefully.
  3. Remove 2 screws that fasten the H/E.
  4. Unfasten 2 screws that secure the shroud on the sides and then lift shroud from the drain pan. (See Figure 24)
  5. Unfasten 2 screws that secure the drain pan to base pan. (See Figure 25)
  6. Pull the drain pan backward then take it up from the base. (See Figure 25)

Figure 24 shows removing the shroud. Figure 25 shows removing the drain pan.

3.3 REFRIGERATING CYCLE

3.3.1 CONDENSER, EVAPORATOR AND CAPILLARY TUBE

  1. Remove the insulation on the Heater/Evaporator (H/E) assembly
  2. Pierce the pinch-off tube to discharge the refrigerant, using a refrigerant recovery system.
  3. After discharging the refrigerant completely, remove 2 screws between the housing assembly and the H/E. (See Figure 26)
  4. Lift the H/E and open the H/E around 45 degree counterclockwise carefully.
  5. Unbraze each of interconnecting tubes of the evaporator and condenser carefully.
  6. Remove the H/E assembly from the orifice. (See Figure 27)
  7. Unbraze the capillary tube at the connections of the condenser and evaporator. (See Figure 28)
  8. Remove 4 screws between the condenser and evaporator. (See Figure 28)

Figure 26 shows removing screws between housing and H/E. Figure 27 shows removing H/E assembly. Figure 28 shows unbrazing capillary tube and removing screws.

3.3.2 PTC OR OVERLOAD PROTECTOR (OLP) FOR RECIPROCATING COMPRESSOR (BHD-301)

  1. Discharge the refrigerant by using a refrigerant Recovery System.
  2. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
  3. Remove the screw or nut which fastens the terminal cover
  4. Disconnect the lead wire from the overload protector or PTC assembly.
  5. Remove the overload protector(OLP) or PTC assembly. (See Figure 29)

Figure 29 illustrates removing the overload protector or PTC assembly.

3.3.3 COMPRESSOR

  1. Discharge the refrigerant by using a refrigerant Recovery System.
  2. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
  3. Remove the nuts and washers which fasten the compressor. (See Figure 30)
  4. Remove the compressor. (See Figure 30)

Figure 30 illustrates removing the compressor.

3.4 HOW TO REPLACE THE REFRIGERATION SYSTEM

  1. When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system.
  2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
  3. Solder service valves into the pinch-off tube ports, leaving the valves open.
  4. Solder the pinch-off tubes with service valves.
  5. After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.
  6. Evacuate as follows.
    1. Connect the vacuum pump, as illustrated in Figure 31A.
    2. Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.
    3. CAUTION: If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
    4. Operate the vacuum pump for 20 to 30 minutes, until 600 microns of vacuum are obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
    5. Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C. Discharge the line at the manifold connection.
    6. The system is now ready for final charging.
  7. Recharge as follows :
    1. Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
    2. Connect the charging cylinder as shown in Figure 31B. With valve C open, discharge the hose at the manifold connection.
    3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.
    4. If more charge is required, the high-side will not take it. Close valve A.
    5. With the unit running, open valve B and add the balance of the charge.
      • Do not add the liquid refrigerant to the Low-side.
      • Watch the Low-side gauge; allow pressure to rise to 30 lbs.
      • Turn off valve B and allow pressure to drop.
      • Repeat steps B and C until the balance of the charge is in the system.
    6. When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.

Figure 31A shows the vacuum pulling process. Figure 31B shows the charging process.

NOTE: REFRIGERANT R134a IS USED IN SOME MODELS. CHECK THE SPECIFICATION LABEL ON THE CABINET.

When discharging refrigerant R134a, purging instrument should be used only for R134a, without mixing that of refrigerant R22. When checking the leakage of refrigerant R134a, leakage test tool should be used only for R134a. The pump for discharging should be high efficiency. Final discharging value must be managed below 0.5 Torr. Maximum water should be less than 150mg in the cycle-all tubes and H/E assembly-system. If water quantity is over 150mg, it causes acid or corrosion in the cycle system and the capillary tube to be clogged by water and harmful materials. Models charged with refrigerant R134a should be used dryer to prevent water from overflowing.

4. TROUBLESHOOTING GUIDE

CONDITION CAUSE REMEDY
1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) No power
Poor plug contact at outlet.
Bucket is full.
Humidity control is at Off position
Wire disconnected or loose
Check power supply at outlet. Correct if none.
Install plug properly or replace it.
If Auto Shut Off lights, empty the bucket and replace properly.
Turn the humidity control switch toward Max.
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
2. Motor runs but compressor does not run. Capacitor.
(Discharge capacitor before testing.)
Voltage (115V ± 10%)
Wiring
Rotary switch
Defrost control
Capacitor
(Discharge capacitor before servicing.)
Compressor
Overload protector (OLP)
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
It must be between 103.5V and 126.5V. If not within limits, call an electrician
Check the wire connections; If loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires.
Check the wire connections; If not according to the wiring diagram, correct the connections.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open.
The Defrost Control senses frost build-up on the evaporator coil and automatically shuts off the compressor. The fan continues to run, drawing air across the coil, and melting the frost. When the coil is defrosted, the compressor automatically restarts, and dehumidifying resumes.
Check the capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor OLP if externally mounted. Replace if open. (If the compressor temperature is high, remove OLP, cool, and retest.)
3. Does not defrost control. Defrost control is defective. Check defrost control, replace it.
4. Insufficient dehumidification Low relative humidity
Poor air circulation
H/E clogged with dust and dirt
Air filter is dirty.
Motor is not operating.
Turn dehumidifier off.
Move dehumidifier to obtain free and unobstructed air circulation.
Clean evaporator and/or condenser assembly
Clean it.
Check Motor, repair or replace it.
5. Noisy operating Fan
Loose foreign material inside the housing.
Tube hits frame.
Fan blade hits frame
Internal compressor noise.
Loose set screws
Worn bearings of Motor Assembly
If cracked, out of balance, or partially missing, replace it
Remove it.
Adjust tubing routine carefully.
Check Motor Mount. If loose, tighten it.
Replace compressor.
Tighten them.
If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor assembly.
6. Water drips The bucket is not installed properly.
Connection may be loose.
Leak in bucket
Water drips when bucket removed for emptying.
Bucket overflows.
The bucket should be properly positioned on the hangers of the drain pan.
Check connection and repair.
Replace bucket.
Before removing bucket, the unit should be turned off.
Check micro switch and float.
7. Compressor cycles on overload protector. (OLP) High or low line voltage. (115V ± 10%)
Poor air circulation.
Heat Exchange clogged with dust or dirt.
Motor
Bad PTC assembly (if assembled)
Short circuit or ground in electrical circuit
Unit pressures not equalized
Capacitor
Wiring
Refrigeration system
Stuck compressor
Overload protector (OLP)
Check line voltage. It must be between 103.5V and 126.5V volts. If intermittent, provide new supply.
Move dehumidifier for free and unobstructed air flow.
Clean dust or dirt on the Heat Exchange.
If not running, determine the cause. Replace if required.
Check PTC, Repair.
Check electrical circuit. Repair.
Allow 2 or 3 minutes for pressure to equalize before starting compressor.
Test the capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
Check compressor, replace compressor
Check OLP, if externally mounted. Replace if open. (If the compressor temperature is high, remove the OLP, cool, and retest.)

5. EXPLODED VIEWS

MODEL: BHD-301

An exploded view diagram of the BHD-301 dehumidifier, showing all parts with corresponding numbers.

MODEL: BHD-501

An exploded view diagram of the BHD-501 dehumidifier, showing all parts with corresponding numbers.

MODEL: BHD-651

An exploded view diagram of the BHD-651 dehumidifier, showing all parts with corresponding numbers.

6. REPLACEMENT PARTS LIST

MODEL: BHD-301

LOCATION NO. DESCRIPTION PART NO. BHD-301 REMARK
130411 BASE ASSEMBLY 3041A10042C
130900 CABINET 3090A10042A
135312 FRONT GRILLE, ASSEMBLY 3531A10285D
330870 DRAIN PAN ASSEMBLY 3087A10019B
148390 TANK ASSEMBLY, BUCKET 4839A10002A
149410 KNOB ASSEMBLY 4941A30019B
152302 FILTER(MECH), AIR 5230A20040A
162615 SENSOR ASEMBLY 6877A30013L
249950 CONTROL BOX, ASSEMBLY 4995A20359J
264110 POWER CORD, ASSEMBLY 6411A20001Z
266002 SWITCH, ROCKER 6600FX5001G
266003 SWITCH ASSEMBLY, ROTARY 6601A30001B
266011 SWITCH ASSEMBLY, MICRO 6600A30003C
268712 PWB(PCB)ASSEMBLY, DISPLAY 6871A20289B
268714 PWB(PCB)ASSEMBLY, MAIN 6871A10142A
346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY, SUCTION 5211A10464A
352113 TUBE ASSEMBLY, DISCHARGE 5211A11019A
552111 TUBE ASSEMBLY, CAPILLARY 5211A30720A
354210 EVAPORATOR, ASSEMBLY 5421A10009P
554030 CONDENSOR ASSEMBLY 5403A10008N
558511 DRIER ASSEMBLY 5851A30001A
554160 COMPRESSOR, SET 2521C-A8626
359012 FAN, TURBO 5900A20007A
567502 OLP 6750C-0009E
349600 MOUNT, MOTOR 4960A20009B
667482 PTC ASSEMBLY 6748C-0003D
436500 HANDLE 3650A20004A
144410 CASTER ASSEMBLY, ROLLER 4441A30001B
238310 ESCUTCHEON 3831A20079G
235512 COVER ASSEMBLY, DISPLAY 3551A20122A
752140 HOSE, CONNECTOR 5214A20027A
550140 ISOLATOR, COMP 5040AR4195A
149980 SHROUD 4998A10034A
435300 REAR GRILLE 3530A10193A

MODEL: BHD-501

LOCATION NO. DESCRIPTION PART NO. BHD-501 REMARK
130411 BASE ASSEMBLY 3041A10042A
130900 CABINET 3090A10042A
135312 FRONT GRILLE, ASSEMBLY 3531A10254C
330870 DRAIN PAN ASSEMBLY 3087A10019A
148390 TANK ASSEMBLY, BUCKET 4839A10002A
152302 FILTER(MECH), AIR 5230A20040A
162615 SENSOR ASEMBLY 6877A30013L
WOCZZ CAPACITOR OCZZA20001R
249950 CONTROL BOX, ASSEMBLY 4995A20359E
264110 POWER CORD, ASSEMBLY 6411A20001Z
266011 SWITCH ASSEMBLY, MICRO 6600A30003C
268712 PWB(PCB)ASSEMBLY, DISPLAY 6871A20460A
268714 PWB(PCB)ASSEMBLY, MAIN 6871A10141C
346811 MOTOR ASSEMBLY 4681A20040J
35211A TUBE ASSEMBLY, SUCTION 5211A10428A
352113 TUBE ASSEMBLY, DISCHARGE 5211A11016A
552204 COIL ASSEMBLY, SOLENOID 6421A20003V
354210 EVAPORATOR, ASSEMBLY 5421A10009J
554030 CONDENSOR ASSEMBLY 5403A10008A
554160 COMPRESSOR, SET 2520UCAA014
359012 FAN, TURBO 5900A20007A
567502 OLP 6750U-L058A
349600 MOUNT, MOTOR 4960A20009B
436500 HANDLE 3650A20004A
144410 CASTER ASSEMBLY, ROLLER 4441A30001B
238310 ESCUTCHEON 3831A20079C
235512 COVER ASSEMBLY, DISPLAY 3551A20109A
752140 HOSE, CONNECTOR 5214A20027A
550140 ISOLATOR, COMP 4830A30005A
149980 SHROUD 4998A10034A
435300 REAR GRILLE 3530A10193A

MODEL: BHD-651

LOCATION NO. DESCRIPTION PART NO. BHD-651 REMARK
130411 BASE ASSEMBLY 3041A10042A
130900 CABINET 3090A10042A
135312 FRONT GRILLE, ASSEMBLY 3531A10254C
330870 DRAIN PAN ASSEMBLY 3087A10019A
148390 TANK ASSEMBLY, BUCKET 4839A10002A
152302 FILTER(MECH), AIR 5230A20040A
162615 SENSOR ASEMBLY 6877A30013L
WOCZZ CAPACITOR OCZZA20005J
249950 CONTROL BOX, ASSEMBLY 4995A20359L
264110 POWER CORD, ASSEMBLY 6411A20001Z
266011 SWITCH ASSEMBLY, MICRO 6600A30003C
268712 PWB(PCB)ASSEMBLY, DISPLAY 6871A20460A
268714 PWB(PCB)ASSEMBLY, MAIN 6871A10141C
346811 MOTOR ASSEMBLY 4681A20040K
35211A TUBE ASSEMBLY, SUCTION 5211A10460A
352113 TUBE ASSEMBLY, DISCHARGE 5211A20868B
552204 COIL ASSEMBLY, SOLENOID 6421A20003V
354210 EVAPORATOR, ASSEMBLY 5421A10009H
554030 CONDENSOR ASSEMBLY 5403A10008L
554160 COMPRESSOR, SET 2520UCBA007
359012 FAN, TURBO 5900A20007A
567502 OLP 6750U-L048A
349600 MOUNT, MOTOR 4960A20009B
436500 HANDLE 3650A20004A
144410 CASTER ASSEMBLY, ROLLER 4441A30001B
238310 ESCUTCHEON 3831A20079C
235512 COVER ASSEMBLY, DISPLAY 3551A20109A
752140 HOSE, CONNECTOR 5214A20027A
550140 ISOLATOR, COMP 4830A30005A
149980 SHROUD 4998A10034A
435300 REAR GRILLE 3530A10193A

Specifications and performance data subject to change without notice.

HEAT CONTROLLER, INC.
1900 WELLWORTH AVENUE JACKSON, MICHIGAN 49203
THE QUALITY LEADER IN CONDITIONING AIR

P/No.: 3828A31001C

Models: BHD-501, BHD Series Dehumidifier, BHD Series, Dehumidifier

File Info : application/pdf, 28 Pages, 3.05MB

PDF preview unavailable. Download the PDF instead.

116979-8

References

FPDF 1.86 AFP

Related Documents

Preview Comfort-Aire WHD-130B Whole House Dehumidifier - Improve Home Comfort
Learn about the Comfort-Aire WHD-130B whole house dehumidifier. This guide covers its benefits, specifications, operation, installation, and features designed to enhance home comfort and air quality by effectively removing excess humidity.
Preview Comfort-Aire Dehumidifiers: Features, Benefits, and Specifications
Explore the range of Comfort-Aire dehumidifiers, highlighting their features, energy efficiency, and how to select the right model for your home. Includes detailed specifications and selection guides.
Preview Comfort Aire BHD-50B Dehumidifier Specifications | ENERGY STAR Certified
View the official ENERGY STAR certification specifications for the Comfort Aire BHD-50B dehumidifier, including water removal capacity and energy efficiency.
Preview Comfort Aire BHD-50B Dehumidifier Specifications | ENERGY STAR Certified
Explore the specifications for the Comfort Aire BHD-50B dehumidifier, an ENERGY STAR certified product. Learn about its water removal capacity, energy efficiency, and market availability.
Preview COMFORT-AIRE A-VFH24TB-1 Owner's Manual and Replacement Parts List
Comprehensive owner's manual and replacement parts list for the COMFORT-AIRE A-VFH24TB-1 InverterFlex Series Outdoor Ductless Mini-Split system. Includes an exploded view diagram and detailed parts table.
Preview COMFORT-AIRE TGR42C Owner's Manual and Replacement Parts
This document provides the owner's manual and replacement parts list for the COMFORT-AIRE TGR42C packaged gas/electric HVAC unit. It details various components and their part numbers for different TGR series models, manufactured by Heat Controller, Inc.
Preview Comfort-Aire Product Guide: Residential and Commercial Heating and Air Conditioning Equipment
A comprehensive product guide from Comfort-Aire showcasing their extensive line of residential and commercial heating and air conditioning equipment, including furnaces, heat pumps, air handlers, coils, and more.
Preview Comfort-Aire Century Floor/Ceiling Mount Indoor Unit Replacement Parts List
Replacement parts list and exploded view diagrams for Comfort-Aire and Century Floor/Ceiling Mount Indoor Units, models B-VHP18UA-1 and B-VHP24UA-1. Includes detailed part numbers for maintenance and repair.