Lennox CK40CT Indoor Coils
Residential Product Specifications (EHB)
Product Type: Indoor Coils
Capacity Range: 1.5 to 5 Tons
Coils are furnished with a factory installed R-410A expansion valve. An R-454B expansion valve may be substituted. Refer to page 5 for R-454B Refrigerant Conversion details.
Model Number Identification
The model number follows the format CK40CT-XX-YY, where:
- CK40CT: Base model designation indicating an Upflow | Cased | Quantum™ Coil with TXV Furnished, compatible with R-410A / R-454B.
- XX: Represents the Nominal Cooling Capacity (Tonnage).
- YY: Represents the Cabinet Width Identifier.
- Revision Level (e.g., 01): Indicates specific configuration, such as R-410A TXV installed.
Example Breakdown: CK40CT-36A-01
- 36: Nominal Cooling Capacity (3 tons)
- A: Cabinet Width (14-1/2 inches)
- 01: Revision Level (R-410A TXV installed)
Nominal Cooling Capacity Mapping:
Size Code | Nominal Cooling Capacity |
---|---|
18/24 | 1.5/2 tons |
24 | 2 tons |
30 | 2.5 tons |
30/36 | 2.5/3 tons |
36 | 3 tons |
48 | 3.5/4 tons |
49 | 4 tons |
50/60 | 4/5 tons |
60 | 5 tons |
Cabinet Width Mapping:
Identifier | Cabinet Width |
---|---|
A | 14-1/2 in. |
B | 17-1/2 in. |
C | 21 in. |
D | 24-1/2 in. |
Furnaces with the same letter designation physically match the indoor coil.
Approvals and Warranty
Approvals
- Tested with matching air conditioners and heat pump units in the Lennox Research Laboratory environmental test room in accordance with AHRI Standard 210/240-2023.
- AHRI Certified system match-ups and expanded ratings available at www.LennoxPros.com.
- Air resistance tests conducted in Lennox Laboratory air test chamber.
Coils can be field configured for use with R-454B refrigerant during initial installation only. Modifications after initial installation are not permitted.
Warranty
- All other covered components:
- Limited five years in residential installations.
- Limited one year in non-residential installations.
Refer to Lennox® Basic Limited Warranty at www.Lennox.com for additional details.
Features
Applications
- 1.5 to 5 ton nominal sizes.
- Lennox designed upflow cased indoor coils are easily installed with most Lennox upflow furnaces.
- Factory installed R-410A check/expansion valve.
- Coils can be field converted for use with R-454B refrigerant.
Coil Construction (Quantum™ Coil)
- Lennox designed and fabricated coil.
- Aluminum tubing, hairpins, distributor, and header tubes.
- Copper refrigerant sweat connections on both liquid and suction lines for easy brazing.
- Ripple-edged aluminum fins for enhanced heat transfer.
- Lanced fins maximize fin surface area exposure to the air stream.
- Helical grooved tubing provides superior heat transfer.
- Twin coil construction assembled in an "A" configuration for large surface area.
- High pressure testing ensures leak-proof construction.
Refrigerant Line Connections
- Copper refrigerant sweat connections on both liquid and suction lines for easy brazing.
- Lines extend outside of the cabinet for ease of connection.
- Refer to dimension drawings for locations.
Anti-Microbial Drain Pan
- Non-corrosive, UV-resistant polymer drain pan with dual FPT drain connections.
- Anti-Microbial additive resists mold and mildew growth on the drain pan, improving indoor air quality and reducing drain line blockage.
R-410A Check and Expansion Valve
- For use with R-410A systems.
- Wide range valve with Chatleff style fitting.
- Factory installed on all models.
R-454B Refrigerant Conversion
Additional components are required for conversion to R-454B Refrigerant:
- Refrigerant Detection System (RDS) Coil Sensor Kit
- Refrigerant Detection System (RDS) Blower Control Board
- R-454B Check and Expansion Valve
Optional Accessories
Refrigerant Detection System (RDS) Coil Sensor Kit
- Complies with UL 60335-2-40 approved standard.
- Required for all systems using R-454B refrigerant.
- Consists of RDS sensor, lineset sleeves, mounting brackets, and A2L labeling.
- Ensures safe operation for systems equipped with R-454B refrigerant.
- Indoor sensor detects any R-454B refrigerant.
Refrigerant Detection System (RDS) Blower Control Board
- Communicating Blower Control Board (Universal): Compatible with any Lennox® communicating furnace or any non-communicating 24-volt furnace.
- Non-Communicating Blower Control Board: Compatible with any non-communicating 24-volt furnace.
Standard Features (Related to RDS)
- Complies with UL 60335-2-40 approved standard.
- Connects to the RDS sensor.
- Supports up to two RDS Sensors (factory setting).
- Acts as an interface between the indoor unit and thermostat to control the system.
- Ensures safe operation for systems equipped with R-454B refrigerant.
- Prevents compressor and heating operation if R-454B refrigerant is detected until it is no longer present.
- Energizes the blower if R-454B refrigerant is detected to mitigate concentrations in the conditioned space.
- Multi-color LED for system status and troubleshooting aid.
- Flashing LED codes for system status (Green/Blue) and sensor errors (Red).
- Alarm relay can trigger an external alarm if R-454B refrigerant is detected.
- Zone relay opens all zone dampers (if part of a zoning system) if R-454B refrigerant is detected.
- Disables power to non-communicating thermostats to prevent demand if R-454B refrigerant is detected.
- On system start-up, the blower runs for five minutes and all thermostat demands are disabled.
- Dimensions (H x W x D): 7-7/16 x 7-7/16 x 2-1/2 inches (189 x 189 x 127 mm).
Refer to Installation Instructions for additional information.
R-454B Check and Expansion Valve
- For use with R-454B systems.
- Wide range valve with Chatleff style fitting.
- Replaces factory-installed TXV, internal to the cabinet.
Cabinet
- Pre-painted heavy gauge steel.
- Insulated with thick fiberglass insulation.
- Flanges provided in outlet for ease of duct connection.
- Coil slides out of cabinet for ease of servicing.
- Removable panels provide access to the coil.
- Refrigerant lines extend outside of the cabinet for easy installation.
Furnace Match-Up
- Coils exactly match corresponding furnaces with the same letter designation in the model number.
- No adaptor required.
- Engaging holes furnished on the cabinet for alignment with the furnace.
Specifications
R-454B Refrigerant Conversion - Order Separately
Description | Order No. | |
---|---|---|
Refrigerant Detection System (RDS) Coil Sensor Kit | 26Z69 | |
Refrigerant Detection System (RDS) Blower Control Board | Any Lennox® Communicating Furnace or any Non-Communicating 24V Furnace (Universal) | 27A03 |
Any Non-Communicating 24V Furnace | 27A02 |
Note: Communicating Blower Control Board and Sensor can be used universally with Lennox® communicating furnaces or any non-communicating 24-volt furnace. Non-Communicating Blower Control Board and Sensor can be used with any non-communicating 24-volt furnace.
Note: Order R-454B Expansion Valve separately.
Optional R-454B TXV Substitution
Note: Additional components are required for R-454B Conversion. See Optional Accessories table.
Size | Order Number |
---|---|
18/24 | 26Z70 |
24 | 26Z70 |
30 | 26Z70 |
30/36 | 26Z70 |
36 | 26Z70 |
48 | 26Z71 |
49 | 26Z71 |
50/60 | 26Z71 |
60 | 26Z72 |
Air Resistance
Size | Air Volume | Total Resistance | |
---|---|---|---|
cfm | Dry Coil (in. w.g.) | Wet Coil (in. w.g.) | |
18/24A, 18/24B | 400 | 0.06 | 0.08 |
600 | 0.11 | 0.17 | |
800 | 0.18 | 0.25 | |
1000 | 0.27 | 0.39 | |
1200 | 0.37 | 0.52 | |
24A | 400 | 0.05 | 0.05 |
600 | 0.09 | 0.10 | |
800 | 0.16 | 0.18 | |
1000 | 0.23 | 0.26 | |
1200 | 0.32 | 0.36 | |
24B | 400 | 0.03 | 0.04 |
600 | 0.07 | 0.09 | |
800 | 0.11 | 0.15 | |
1000 | 0.17 | 0.22 | |
1200 | 0.23 | 0.31 | |
30A | 600 | 0.07 | 0.08 |
800 | 0.12 | 0.13 | |
1000 | 0.18 | 0.20 | |
1200 | 0.26 | 0.28 | |
1400 | 0.34 | 0.37 | |
30B | 600 | 0.06 | 0.06 |
800 | 0.09 | 0.11 | |
1000 | 0.13 | 0.16 | |
1200 | 0.19 | 0.23 | |
1400 | 0.25 | 0.31 | |
30/36A | 800 | 0.13 | 0.14 |
1000 | 0.19 | 0.21 | |
1200 | 0.27 | 0.30 | |
1400 | 0.34 | 0.39 | |
1600 | 0.45 | 0.51 | |
30/36B, 30/36C | 800 | 0.08 | 0.11 |
1000 | 0.13 | 0.16 | |
1200 | 0.17 | 0.21 | |
1400 | 0.22 | 0.28 | |
1600 | 0.29 | 0.34 | |
36A | 800 | 0.13 | 0.14 |
1000 | 0.19 | 0.21 | |
1200 | 0.27 | 0.30 | |
1400 | 0.34 | 0.39 | |
1600 | 0.45 | 0.51 | |
36B | 800 | 0.08 | 0.11 |
1000 | 0.13 | 0.16 | |
1200 | 0.17 | 0.21 | |
1400 | 0.22 | 0.28 | |
1600 | 0.29 | 0.34 | |
48B | 1000 | 0.13 | 0.13 |
1200 | 0.18 | 0.18 | |
1400 | 0.23 | 0.24 | |
1600 | 0.30 | 0.31 | |
1800 | 0.37 | 0.40 | |
48C | 1000 | 0.07 | 0.09 |
1200 | 0.10 | 0.12 | |
1400 | 0.13 | 0.16 | |
1600 | 0.16 | 0.20 | |
1800 | 0.20 | 0.24 | |
49C | 1200 | 0.08 | 0.12 |
1400 | 0.13 | 0.17 | |
1600 | 0.17 | 0.22 | |
1800 | 0.22 | 0.28 | |
2000 | 0.28 | 0.35 | |
50/60C | 1200 | 0.13 | 0.17 |
1400 | 0.18 | 0.23 | |
1600 | 0.23 | 0.29 | |
1800 | 0.28 | 0.37 | |
2000 | 0.34 | 0.43 | |
60D | 1400 | 0.11 | 0.15 |
1600 | 0.14 | 0.18 | |
1800 | 0.17 | 0.21 | |
2000 | 0.21 | 0.27 | |
2200 | 0.25 | 0.32 | |
2400 | 0.30 | 0.37 | |
60C | 1400 | 0.15 | 0.19 |
1600 | 0.19 | 0.23 | |
1800 | 0.24 | 0.28 | |
2000 | 0.29 | 0.34 | |
2200 | 0.33 | 0.40 | |
2400 | 0.39 | 0.46 |
Dimensions
Diagrammatic representations of the coil dimensions are provided. Key dimensions include:
- Front View: Shows Liquid Line, Suction Line, RDS Coil Sensor Wiring Inlet, Inlet Opening, Condensate Drains.
- Top View: Shows Outlet Opening.
- Side View: Shows Air Flow, Inlet Opening.
Detailed measurements (in inches and millimeters) for various models are presented in the table below.
Size | A | B | C | D | E | F | G | H | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
in. | mm | in. | mm | in. | mm | in. | mm | in. | mm | in. | mm | in. | mm | in. | mm | |
18/24A | 14-1/2 | 368 | 16-1/2 | 419 | 13 | 330 | 13-3/8 | 340 | 7-1/4 | 185 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
18/24B | 17-1/2 | 445 | 16-1/2 | 419 | 16 | 406 | 16-3/8 | 416 | 7-1/4 | 185 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
30/36A | 14-1/2 | 368 | 24-1/2 | 622 | 13 | 330 | 13-3/8 | 340 | 13-1/2 | 343 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
30/36B | 17-1/2 | 445 | 24-1/2 | 622 | 16 | 406 | 16-3/8 | 416 | 13-1/2 | 343 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
30/36C | 21 | 533 | 24-1/2 | 622 | 19-1/2 | 495 | 19-7/8 | 505 | 13-1/2 | 343 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
36A | 14-1/2 | 368 | 24-1/2 | 622 | 13 | 330 | 13-3/8 | 340 | 13-1/2 | 343 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
36B | 17-1/2 | 445 | 24-1/2 | 622 | 16 | 406 | 16-3/8 | 416 | 13-1/2 | 343 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
24A | 14-1/2 | 368 | 18-1/2 | 470 | 13 | 330 | 13-3/8 | 340 | 9-3/4 | 248 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
24B | 17-1/2 | 445 | 18-1/2 | 470 | 16 | 406 | 16-3/8 | 416 | 9-3/4 | 248 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
30A | 14-1/2 | 368 | 22-1/2 | 572 | 13 | 330 | 13-3/8 | 340 | 11-1/2 | 292 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
30B | 17-1/2 | 445 | 22-1/2 | 572 | 16 | 406 | 16-3/8 | 416 | 11-1/2 | 292 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
48B | 17-1/2 | 445 | 27-1/2 | 699 | 16 | 406 | 16-3/8 | 416 | 12-1/2 | 318 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
48C | 21 | 533 | 27-1/2 | 699 | 19-1/2 | 495 | 19-7/8 | 505 | 12-1/2 | 318 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
50/60C | 21 | 533 | 27-1/2 | 699 | 19-1/2 | 495 | 19-7/8 | 505 | 12-1/2 | 318 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
60D | 24-1/2 | 622 | 29-1/2 | 749 | 23 | 584 | 23-3/8 | 594 | 10 | 254 | 3-5/8 | 92 | 2-5/8 | 66 | 2-3/8 | 60 |
49C | 10 | 254 | 3-5/8 | 92 | 29-1/2 | 749 | 2-3/8 | 60 | 2-5/8 | 66 | ||||||
60C | 14-1/2 | 368 | 3-5/8 | 92 | 31-1/2 | 800 | 2-3/8 | 60 | 2-5/8 | 66 |