Honeywell Home System Installation Guide

THX9321 Prestige® 2.0 THX9421 Prestige® IAQ 2.0 with EIM

With wireless accessories

NOTE: The TH9321 Prestige is no longer available. There are different versions of the TH9421 Prestige. The version in this document is no longer available.

Control for up to 4 Heat/2 Cool heat pump systems or up to 3 Heat/2 Cool conventional systems for residential and commercial applications.

Installation guide for:

Quick start guide

  1. Install thermostat.................................................................. page 3
  2. Install optional Equipment Interface Module (EIM)...........3
  3. Power optional accessories...........................................................4
  4. Link thermostat to wireless network .........................................5
  5. Link optional accessories to wireless network ......................6
  6. Install optional sensors ..................................................................7
  7. Setup installer options ....................................................................8

Important Notices

⚠️ DISCONNECT POWER BEFORE INSTALLATION. Can cause electrical shock or equipment damage.

MERCURY NOTICE: If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.

⚠️ Must be installed by a trained, experienced technician. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.

Your Resideo Advantage

RedLINK™ Compatible

Increase your content and profit per job by including RedLINK™ accessories that meet your customers' comfort and convenience needs. RedLINK accessories include the Wireless Outdoor Sensor, Portable Comfort Control (PCC), Equipment Interface Module (EIM), RedLINK Internet Gateway, Wireless Indoor Sensor, TrueSTEAM™ humidifier with Wireless Adapter, TrueZONE™ zoning panel with Wireless Adapter, Vent Boost Remote, and Entry/Exit Remote.

Customizable Service Reminders

Set up to 10 service reminders. Choose from the pre-set options or customize your own. Reminders based on date, outdoor temperature, or a dry contact input will alert customers with instructions to contact you for assistance.

Delta T Alerts and Diagnostics

Alerts give customers a sense of security while also enabling you to service or replace the equipment prior to a loss of heating or cooling. Based on limits you set at installation, customers can be alerted when their system is not operating as expected. The system alert will instruct customers to contact you for assistance. Requires EIM.

Delta T Installer Test

Save time by viewing Delta T while running a system test to verify proper operation. Requires EIM.

"S" Inputs – S1 and S2

Assignable inputs allow you to configure Indoor and Outdoor Temperature Sensors, Discharge and Return Air Sensors, or Dry Contact Devices. Dry Contact Devices can be used to trip pre-set or customized alerts on the thermostat home screen. Requires EIM.

User Interactions Log

The interaction log stores history of thermostat setting changes including temperature, system, and installer setup. You can use the interaction log to save time by determining if the issue is a system error or an accidental user error.

Configurable for Residential and Light Commercial Applications

One thermostat does it all to meet the needs of Residential and Light Commercial applications. Simply select Residential or Commercial during the installer setup. If Commercial is selected, the thermostat will use commercial language, meet building codes, and offer 365-day holiday scheduling.

USB Port for Quick Installer Setup

Save time by using a USB stick to upload installer settings and service reminders in one simple step.

Selectable Sensors

When paired with a Wireless Indoor Sensor(s), you have the ability to choose which sensor(s) to use for temperature, humidification, and dehumidification. They can be used in combination for temperature averaging—or individually—to condition humidity levels in separate spaces.

Installation Steps

1. Install thermostat

Diagram Description: "Diagrams show the wiring terminals for a thermostat and the Equipment Interface Module (EIM)."

When the THX9321 thermostat is used with the EIM, the relays in the thermostat do not function.

See pages 10-17 for detailed wiring guidelines.

2. Install Equipment Interface Module (if used)

[If no EIM is used, skip to Section 3.]

Use screws & anchors as appropriate for the mounting surface. Mount the EIM near the HVAC equipment, or on the equipment itself.

Strip 1/4" insulation, then insert wires as shown.

Diagram Description: "A diagram illustrates the Equipment Interface Module (EIM) with its various terminals labeled for wiring connections, including power, status LEDs, and connections for thermostat, sensors, and HVAC equipment."

NOTE: If you install more than one thermostat and EIM, the EIMs must be at least 2 feet apart.

If you are installing discharge and return air sensors, refer to the mounting instructions in the Alerts and Delta T Diagnostics Installation Instructions packed with the Prestige IAQ 2.0 kit.

3. Power optional accessories

[If no wireless accessories are used, skip to Section 4.]

Diagram Description: "Diagrams show the Wireless Outdoor Sensor, Wireless Indoor Sensor, and Portable Comfort Control, indicating where to install fresh AA lithium or AAA alkaline batteries."

RedLINK™ Internet Gateway

The RedLINK Internet Gateway gives your customers remote access to home climate-control systems from any location with Internet access. Using a Web browser, users can review and adjust indoor temperature, system mode, and other settings. The Gateway can also send alerts to as many as 6 email addresses if a problem occurs.

Diagram Description: "A diagram shows the RedLINK Internet Gateway connected to a router via an Ethernet cable (RJ45) and plugged into a wall electrical outlet."

NOTE: The current white gateway looks different than the legacy gateway shown here.

4. Link thermostat to the wireless network

(if used with an EIM or TrueZONE Wireless Adapter)

Link all components and RedLINK™ accessories to the wireless network.

Initial powerup

When the thermostat is first activated, it will lead you through the steps necessary to define and set up your system. The steps will change depending on the type of system and thermostat you're installing.

Setup options for THX9321

Setup options for THX9421

Link thermostat to EIM or TrueZONE® Wireless Adapter

Use the step-by-step thermostat menus to define your system type. When you reach the Wireless Setup screen, follow the steps below:

Press and release the CONNECT button at the EIM or Wireless Adapter, and make sure the "Connected" light is flashing green.

Diagram Description: "A diagram shows the EIM with its CONNECT button and status lights, and a thermostat screen prompting to press the CONNECT button."

"Connected" status light

While the EIM light is flashing, press NEXT to link the thermostat with the EIM. After a brief delay, the screen will display "Device Connected."

Navigation: At any screen, you can press HELP for more information, or press BACK to change earlier options.

5. Link optional accessories to wireless network

Diagram Description: "The thermostat displays an 'Add Device' screen with a timer and options to View Devices and Done."

While the Add Device screen is displayed on the thermostat, press and release the CONNECT button on each wireless device, as described below. Accessories need to be at least 2 feet away from the thermostat or EIM during the linking process.

Press DONE after all devices have been linked.

To add devices later: Press MENU > INSTALLER OPTIONS, enter date code (password) when prompted. The date code is printed on the back of the thermostat; or press MENU > EQUIPMENT STATUS to find the date code. After you enter the password, scroll down to press WIRELESS DEVICE MANAGER and then select ADD DEVICE.

Wireless outdoor sensor

Diagram Description: "Diagrams show the Wireless Outdoor Sensor and Wireless Indoor Sensor with their CONNECT buttons."

Press and release CONNECT. After a short delay, the thermostat will display "Wireless Outdoor Sensor added" on the Add Device screen.

Wireless indoor sensor

Press and release CONNECT. After a short delay, the status light will glow green for 15 seconds.

Portable Comfort Control

Diagram Description: "Diagram shows the Portable Comfort Control with its CONNECT button and screen."

Press CONNECT on the Portable Comfort Control display screen. Press DONE when the screen displays "Connected," then exit or continue to link another thermostat.

The linking procedure will time out if there is no keypress for 30 minutes. To begin again, press and hold in the lower right corner of the screen until the display changes (about 3 seconds).

RedLINK Internet Gateway

Diagram Description: "Diagram shows the RedLINK Internet Gateway with its PRESS AND RELEASE button."

Press and release the button on the bottom of the Internet Gateway. After a short delay, the RedLINK status light will glow steady green.

NOTE: This button is on the side of a current white Gateway.

The Internet Gateway must be registered online before use at www.mytotalconnectcomfort.com. Enter the MAC ID and MAC CRC numbers located on the bottom of the Internet Gateway. For additional information, see instructions provided with the device.

6. Install optional sensors

[If no sensors are used, skip to Section 7.]

To install outdoor air sensor

Diagram Description: "Diagrams show the outdoor air sensor and its mounting bracket."

  1. Mount the sensor on a vertical exterior wall, at least 6 inches below any overhang. Choose a location protected from direct sunlight.
  2. Place sensor securely in bracket, facing away from wall.

To install indoor air sensor

Diagram Description: "Diagrams show the indoor air sensor and its wallplate."

  1. Remove the wallplate and mount it 4 to 6 feet above the floor on an interior wall. Drill 3/16-inch holes for drywall, 7/32-inch for plaster.
  2. Attach sensor securely to wallplate as shown.

7. Setup Installer options (ISU)

To setup the thermostat, press MENU and scroll down to press INSTALLER OPTIONS. Enter the date code (password) when prompted. The date code is printed on the back of the thermostat; or press MENU > EQUIPMENT STATUS to find the date code. After you enter the password, press CREATE SETUP to setup the thermostat.

A brief summary of installer options follows (pages 8-9). You can download a complete list of all options at http://customer.resideo.com.

Installer Options (ISU)

7. Setup Installer options (ISU) - continued

Diagram Description: "A screenshot shows the Installer Options menu on the thermostat, with options like Create Setup, View/Edit Current Setup, Set Up Diagnostics, Installer Test, Data Logs, Wireless Device Manager, and Advanced Options."

TIP: You can use the thermostat USB port to download all system configuration and installer options, including your company name and contact information. You can upload this data to each thermostat you install, to save time.

Key: R: Residential, C: Commercial, B: Both. Thermostat functions marked in gray below require an EIM (see page 3).

Installer Options Table (Partial)

ISU Function ISU Function
1000Language3200-3220Heating Derivative, Integral, Throttling range
1010Residential/Commercial3240Minimum Compressor Off Time
1020Zone Number3260Extended Fan Run Time in Cool
1030Device Name3260Extended Fan Run Time in Heat
1030Device Name on Home Screen4000Number of Scheduled Periods
1040Programmable/Non-programmable4010Pre-occupancy Purge Duration
1050Fahrenheit/Celsius4020Override: Standard or Initiate Occupancy
1060Outdoor Air Sensor4030Override Duration
2000Heating System Type4050Minimum Recovery Settings - Heat
2010Heating Equipment Type4060Maximum Recovery Settings - Heat
2020-2100Heat Stages4070Minimum Recovery Settings - Cool
2050Geothermal Forced Air System4080Maximum Recovery Settings - Cool
2060Reversing Valve O/B4090Adaptive Intelligent Recovery
2070-2090Cool/Compressor Stages4100Minimum Cool Setpoint
2110Fan Operation in Heat4100Maximum Heat Setpoint
2120, 2180Backup Heat Type4110Keypad Lockout
2130, 2170Backup Heat Stages4120Entry/Exit Remote - Home/Occupied Cool Setpoint
2150, 2200Backup Heat Operation4120Entry/Exit Remote - Home/Occupied Heat Setpoint
2160, 2210Backup Heat Fan Operation4130Entry/Exit Remote - Away/Unoccupied Cool Setpoint
2190External Fossil Fuel Kit4130Entry/Exit Remote - Away/Unoccupied Heat Setpoint
2220A-L/A Terminal Setup4140Entry/Exit Remote - Vacation/Holiday Cool Setpoint
3000Manual/Auto Changeover4140Entry/Exit Remote - Vacation/Holiday Heat Setpoint
3000Auto Changeover Deadband5000Select Wired Sensors
3010Temperature Control Options5010Indoor Temperature Sensor Name
3020Finish With High Cool Stage5020Terminals Wired to Indoor Sensor
3021Finish With High Heat Stage5030Indoor Temperature Sensor Type
3030Staging Control - Cool Differentials5040Indoor Sensors Used for Temperature Control
3040-3060Staging Control - Heat Differentials5050Terminals Wired to Outdoor Sensor
3080, 3090Staging Control – Backup Heat Differentials5070Terminals Wired to Return Air Sensor
3110Backup Heat Upstage Timer5080Return Air Sensor Type
3120Outdoor Compressor Lockout
3120Outdoor Backup Heat Lockout
3130, 3150Heat Cycles Per Hour
3140Cool Cycles Per Hour
3160Backup Heat Cycles Per Hour
3170-3190Cooling Derivative, Integral, Throttling range

Installer Options Table (Continued)

ISU Function ISU Function
5090Terminals Wired to Discharge Air Sensor9130Dehumidifier Fan Control
5100Discharge Air Sensor Type9140Dehumidifier Lockout
5110A-Coil Low Temperature Cutoff9180Dehumidification Away Mode
6000Select the Dry Contacts in the System9190Dehumidification Away Mode - Fan Control
6010Terminals Wired to Remote Setback Dry Contact9200Dehumidification Away Mode - Low Limit Temperature
6020Remote Setback Dry Contact Setup9200Dehumidification Away Mode - Temperature Setting
6030Remote Setback Time Delay9200Dehumidification Away Mode - Dehumidification Setting
6040Remote Setback - Standby Cool Setpoint9210Dehumidifier Filter Replacement Reminder
6040Remote Setback - Standby Heat Setpoint10000Ventilation Type
6050Terminals Wired to Full Drain Pan Alert Dry Contact10020Terminals Wired to Ventilator/Fresh Air Damper
6060Full Drain Pan Alert Dry Contact Setup10050Ventilation Control Method
6070Terminals Wired to Dirty Filter Alert Dry Contact10060Ventilation Fan Control
6080Dirty Filter Alert Dry Contact Setup10090Number of Bedrooms
6090Terminals Wired to Water Leak Alert Dry Contact10090Size of House
6100Water Leak Alert Dry Contact Setup10100Enter Equipment Ventilation Rate
6110Terminals Wired to System Shutdown Alert Dry Contact10120Ventilation Percent On Time
6120System Shutdown Alert Dry Contact Setup10125Ventilation Priority
6130Terminals Wired to Service Needed Alert Dry Contact10130Ventilation Low Temperature Lockout
6140Service Needed Alert Dry Contact Setup10130Ventilation High Temperature Lockout
6150Terminals Wired to Fan Failure Alert Dry Contact10130Ventilation High Dewpoint Lockout
6160Fan Failure Alert Dry Contact Setup10140Lockout Ventilation on Hum/Dehum Calls
6170Terminals Wired to Custom Alert Dry Contact10160Ventilate on High Indoor Humidity
6180Custom Alert Dry Contact Setup10170Ventilator Core Cleaning Reminder
6190, 6200Custom Alert Name and Message10170Ventilator Filter Cleaning Reminder
7000Filter Type11000Number of UV Devices
7020Number of Air Filters11050UV Bulb Replacement Reminder
7110Air Filter Replacement Reminder11050UV Bulb 2 Replacement Reminder
7110Air Filter 2 Replacement Reminder12000Installer Custom Reminders
7120EAC Cell Cleaning Reminder13000Heat Delta T Diagnostics
7120EAC Pre-Filter Cleaning Reminder13010Cool Delta T Diagnostics
7120EAC Post-Filter Replacement Reminder13015Set Advanced Delta T Diagnostic Options
8000Humidifier Type13020Allow Delta T Diagnostics During Humidification
8010Indoor Sensor Used for Humidification Control13030Allow Delta T Diagnostics During Dehumidification
8030Terminals Wired to the Humidifier13040Allow Delta T Diagnostics During Ventilation
8050Humidification - Window Protection13050-13080Allow Heat Delta T Diagnostics: Temp & Humidity
8060System Modes Allowing Humidification13090-13120Allow Backup Heat Delta T Diagnostics: Temp & Humidity
8070Humidification Control13130-13160Allow Cool Delta T Diagnostics: Temp & Humidity
8080Humidifier Lockout13170Defrost Cycle
8100Clean Tank / Water Filter Replacement Reminder13180Delta T Alert Sensitivity
8100Humidifier Pad Replacement Reminder13190Display Delta T Alerts to User
9000Dehumidification Equipment14000Clock Format
9010Indoor Sensor Used for Dehumidification Control14010Daylight Saving Time
9020Humidity Sensor Displayed on the Home Screen14020Indoor Temperature Display Offset
9040Terminals Wired to Dehumidification Equipment14020Indoor Humidity Display Offset
9050A/C with Low Speed Fan Setup15000-15020Dealer name, phone, email, website, message
9050Hot Gas Bypass Setup
9070Dehumidification - Overcooling Limit
9080Dehumidification Control
9090Dehumidification Minimum On Time
9100High Humidity Comfort Reset Setting
9120System Modes Allowing Dehumidification

Wiring Guides

EIM wiring guide – conventional systems

Typical wiring of a conventional system with up to 3-stage heat and 2-stage cool with one transformer.

Diagram Description: "A wiring diagram illustrates the connections between the Equipment Interface Module (EIM), the thermostat, and a furnace transformer for a conventional HVAC system. It shows terminals for power, heat stages (W, W2, W3), cooling stages (Y, Y2), fan (G), and optional sensors (S1, S2)."

EIM wiring guide – heat pump systems

Typical wiring of a heat pump system with up to four-stage heat and two-stage cool with one transformer.

Diagram Description: "A wiring diagram illustrates the connections between the Equipment Interface Module (EIM), the thermostat, and an air handler transformer for a heat pump system. It shows terminals for O/B (changeover valve), AUX1/AUX2 (backup heat), Y/Y2 (compressor stages), G (fan), and optional sensors (S1, S2)."

EIM wiring guide – geothermal radiant heat

Typical wiring for geothermal radiant heat, geothermal forced-air, and backup heat with one transformer. See page 19 for operation.

Diagram Description: "A wiring diagram illustrates the connections between the Equipment Interface Module (EIM), the thermostat, and an air handler transformer for a geothermal radiant heat system. It shows terminals for O/B, AUX1/AUX2 (backup heat), Y/Y2 (compressor stages), G (fan), and specific terminals U1, U2, U3 for geothermal radiant heat. Optional jumper connection is shown."

Thermostat wiring guides – Prestige THX9321

Typical wiring of a 3-heat / 2-cool heat pump system with one transformer

Diagram Description: "Wiring diagram for a Prestige THX9321 thermostat in a 3-heat/2-cool heat pump system with one transformer, showing connections for O/B, AUX/E, Y, Y2, G, L/A, K, and C terminals."

Typical wiring of a 2-heat / 2-cool conventional system with one transformer

Diagram Description: "Wiring diagram for a Prestige THX9321 thermostat in a 2-heat/2-cool conventional system with one transformer, showing connections for W, W2, Y, Y2, G, A, K, and C terminals."

Typical wiring of a 3-heat / 2-cool heat pump system with two transformers (example - oil forced air backup heat)

Diagram Description: "Wiring diagram for a Prestige THX9321 thermostat in a 3-heat/2-cool heat pump system with two transformers (one for air handler, one for backup heat), showing connections for O/B, AUX/E, Y, Y2, G, L/A, K, and C terminals."

Typical wiring for geothermal radiant heat, geothermal forced-air and backup heat with one transformer

Diagram Description: "Wiring diagram for a Prestige THX9321 thermostat for geothermal radiant heat, forced-air, and backup heat with one transformer, showing connections for O/B, AUX/E, Y, Y2, G, L/A, K, and C terminals, plus specific connections for GEOTHERMAL RADIANT HEAT STAGE 1."

Prestige THX9321 or EIM: Using U terminals to control heating or cooling

Powering U terminals with system transformer (THX9321 shown)

Diagram Description: "Wiring diagram showing U terminals (U1, U2) connected to a system transformer for controlling heating or cooling stages (HEAT STAGE 3 or COOL STAGE 3/4) on a THX9321 thermostat."

Powering U terminals with separate heating transformer (THX9321 shown)

Diagram Description: "Wiring diagram showing U terminals (U1, U2) connected to a separate heating transformer for controlling heating or cooling stages (HEAT STAGE 3) on a THX9321 thermostat."

Dry Contact Alerts

⚠️ EQUIPMENT DAMAGE HAZARD. Do not apply power to S1 or S2 terminals.

The dry contact device must be rated for low voltage.

If you are not using the S1 and S2 terminals on the EIM, you can connect them to a dry contact device to display an alert. Dry contact alerts include Full Drain Pan, Dirty Filter, Water Leak, System Shutdown, Service Needed, Fan Failure, and Custom Alert (ISU 6000).

Diagram Description: "Diagram shows the EIM S1 and S2 terminals connected to either a single dry contact device or multiple dry contact devices in parallel."

You can connect multiple Dry Contact devices in parallel to the S1 or S2 terminals.

Wiring guide – IAQ equipment (EIM or thermostat)

"U" terminals can be used for humidification, dehumidification, or ventilation.

With power supply

Typical hookup of powered humidifier.

Diagram Description: "Wiring diagram for a powered humidifier connected to U terminals (U1, U2, U3) and a 24 VAC transformer."

Typical hookup of powered ventilation.

Diagram Description: "Wiring diagram for a powered ventilator connected to U terminals (U1, U2, U3) and a 24 VAC transformer."

Typical hookup of powered dehumidifier (whole house dehumidifier).

Diagram Description: "Wiring diagram for a powered dehumidifier connected to U terminals (U1, U2, U3) and a 24 VAC transformer."

Without power supply

Typical hookup of non-powered humidifier.

Diagram Description: "Wiring diagram for a non-powered humidifier connected to U terminals (U1, U2, U3), a 24 VAC transformer, and includes a field-installed jumper between R and U1."

Typical hookup of non-powered ventilation.

Diagram Description: "Wiring diagram for a non-powered ventilator connected to U terminals (U1, U2, U3), a 24 VAC transformer, and includes a field-installed jumper between R and U1."

Typical hookup of variable speed blower for dehumidification in low speed.

Diagram Description: "Wiring diagram for a variable speed blower for dehumidification connected to U terminals (U1, U2, U3), a 24 VAC transformer, and includes a field-installed jumper between R and U1. Shows a DEHUMIDIFICATION WITH LOW SPEED FAN label."

KEY

Economizer Module wiring guides

Typical wiring of a W7220 Economizer Module for a heat pump system, using a Prestige THX9321 thermostat or Equipment Interface Module.

Diagram Description: "Wiring diagram for a W7220 Economizer Module connected to a rooftop unit and a thermostat/EIM for a heat pump system. Shows connections for O/B, N, Y1, Y2, AUX, AUX 2, G, and SD-O/B, OCC, E-GND, AUX, Y2I, Y2O, Y1I, Y1O, C, R terminals on the module."

Typical wiring of a W7220 Economizer Module for a conventional system, using a Prestige THX9321 thermostat or Equipment Interface Module.

Diagram Description: "Wiring diagram for a W7220 Economizer Module connected to a rooftop unit and a thermostat/EIM for a conventional system. Shows connections for N, Y1, Y2, W1, W2, G, and SD-O/B, OCC, E-GND, AUX, Y2I, Y2O, Y1I, Y1O, C, R terminals on the module."

Typical wiring of a W7213/W7214 Economizer Module for a heat pump system, using a Prestige THX9321 thermostat or Equipment Interface Module.

Diagram Description: "Wiring diagram for a W7213/W7214 Economizer Module connected to a rooftop unit and a thermostat/EIM for a heat pump system. Shows connections for O or B, N, 3, 4, 1, 2 & 5, TR1, TR, and module terminals."

Typical wiring of a W7212 Economizer Module for a conventional heating system, using a Prestige THX9321 thermostat or Equipment Interface Module.

Diagram Description: "Wiring diagram for a W7212 Economizer Module connected to a rooftop unit and a thermostat/EIM for a conventional heating system. Shows connections for N, Y1, Y2, W1, W2, G, and module terminals."

Operation Modes

Economizer and TOD operation (ISU 2220)

Commercial use only

The Economizer can greatly reduce energy costs if configured properly. In some climates, the cooling system may run hundreds of hours when it may not be required to maintain indoor comfort. In some conditions, ventilation with outdoor air can achieve the same level of comfort at lower cost. Tables below explain how the Economizer feature maintains comfort while minimizing costs.

Economizer Operation (A-L/A terminal)
Thermostat Mode Equipment Operation A-L/A terminal: Economizer
OccupiedHeat/Cool/Fan runningON
Occupied temporarilyHeat/Cool/Fan running
OccupiedHeat/Cool/Fan NOT runningOFF
Occupied temporarilyHeat/Cool/Fan NOT running
Pre-occupancy purgeFan runningON
UnoccupiedCooling system running
Unoccupied temporarilyCooling system running
StandbyCooling system running
UnoccupiedCooling system NOT runningOFF
Unoccupied temporarilyCooling system NOT running
StandbyCooling system NOT running
Non-programmableFan runningON
Non-programmableFan NOT running
TOD Operation (A-L/A terminal)
Thermostat Mode A-L/A terminal: TOD
OccupiedON
Occupied temporarily
Temperature overridesOFF
Unoccupied
Unoccupied temporarily
Standby
Non-programmable

Advanced Features

Heat pump with outdoor temperature lockouts

Outdoor temperature lockouts are optional. See Installer Setup options (ISU 3120).

Backup heat allowed to run with heat pump

Diagram Description: "A chart illustrates heat pump operation with backup heat lockout and compressor lockout based on outdoor temperature thresholds."

* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat Upstage Timer expires. Heat pump stays ON when backup heat turns on.

Backup heat NOT allowed to run with heat pump

Diagram Description: "A chart illustrates heat pump operation without backup heat lockout and compressor lockout based on outdoor temperature thresholds."

* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat Upstage Timer expires. Heat pump turns OFF when backup heat turns on.

Heat pump and backup heat operation

Backup Heat Type Backup Heat Operation Backup Heat Fan Operation
Electric forced airAllowed to run with heat pumpThermostat controls fan
Gas or oil forced airNOT allowed to run with heat pumpEquipment controls fan
Hot water radiant heatAllowed to run with heat pump[n/a]
Hot water fan coilSelectable in installer setupThermostat controls fan
OtherSelectable in installer setupSelectable in installer setup

Geothermal Radiant Heat

The thermostat can be set up to control Geothermal Radiant Heat, Geothermal Forced Air Heat, and Backup Heat, all from one thermostat. The thermostat stages the equipment starting with the Geothermal Radiant Heat, followed by Geothermal Forced Air Heat, and then Backup Heat as needed to maintain the desired temperature. The thermostat allows you to set differential temperature settings between each stage if you want the equipment to stage a certain way (see ISU 3030 to ISU 3090).

When the Backup Heat is fossil fuel, the Geothermal Forced Air Heat turns off when the Backup Heat turns on. Geothermal Radiant Heat stays on when the fossil fuel Backup Heat turns on.

When the Backup Heat is electric, Geothermal Radiant Heat and Geothermal Forced Air Heat stay on when the electric Backup Heat turns on.

To turn off Radiant Heat during the shoulder seasons, install an outdoor reset control and connect to the Radiant Heat or switch the thermostat to Emergency Heat mode.

Basic and Advanced Temperature Control Options (ISU 3010)

Basic Options: The Installer Setup displays basic temperature control options which include Backup Heat Differential, Backup Heat Upstage Timer, and Outdoor Temperature Lockouts. Note: Outdoor Temperature Lockouts only apply to Heat Pump applications.

Advanced Options: The Installer Setup displays both Basic and Advanced Options. Advanced temperature control options include Finish With High Cool Stage, Finish With High Heat Stage, Temperature Differential settings between all stages, and Cycle Rate settings per stage.

Finish With High Heat or Cool Stage: When a multi-stage heating or cooling system is used, this feature keeps the high stage of the heating or cooling equipment running until the desired setpoint is reached. Recommended setting for Geothermal Heat Pumps to allow the loop to rest.

Backup heat differential and upstage timer

A backup heat differential and backup heat upstage timer can be set on any system that has more than one type of heating equipment. See installer setup options (ISU 3070-3110).

Normal operation

When the Backup Heat Differential is set to Comfort, the thermostat uses backup heat as needed to keep the indoor temperature within 1° F (0.5° C) of the setpoint.

When the Backup Heat Differential is set to 2° F or higher, backup heat is not used unless the indoor temperature drops to the Backup Heat Differential setting or the Backup Heat Upstage Timer expires, whichever occurs first. The upstage timer starts when the highest stage of the previous equipment type turns on.

Manual temperature change

When the Backup Heat Differential is set to Comfort, the thermostat uses backup heat as needed to keep the indoor temperature within 1° F (0.5° C) of the setpoint.

When the Backup Heat Differential is set to 2° F or higher, if the primary heat is making progress as expected, backup heat will not be used to reach the new setpoint. Set to a higher number to use less backup heat (a greater difference between the current indoor temperature and the new setpoint is required to turn on backup heat). See notes below.

Programmed recovery

If the primary heat is making progress as expected, backup heat will not be used to reach the setpoint of the next program period. Backup heat is always restricted during a programmed recovery when the Adaptive Intelligent Recovery feature is used. See note below.

During a programmed recovery (or when the temperature setpoint is changed by the user), the thermostat waits to turn on the backup heat depending on system performance, load conditions, and how many degrees the temperature setpoint is changed. Backup heat will be used ONLY when the temperature is not rising quickly enough to reach the setpoint in a reasonable time.

If the backup heat was used in the last 2 hours because the primary heat was not able to maintain the setpoint, the thermostat may turn on the backup heat earlier when the user raises the setpoint. This does NOT apply to heat pumps with fossil fuel backup heat.

Humidification

The thermostat reads the indoor humidity level and allows the user to set a humidification setting with or without window protection. The thermostat can be set up to control a humidifier in any system mode (Heat, Off, Cool [ISU 8060]). A discharge air sensor is required to humidify in the cool mode.

Humidification Control Options: (ISU 8070)

Residential dehumidification

The thermostat reads the indoor humidity level and allows the user to set a dehumidification setting. The thermostat controls the humidity level using the cooling system or a whole house dehumidifier.

Dehumidification Equipment Options: (ISU 9000)

When set for A/C with Low Speed Fan or A/C with High Speed Fan, an overcooling limit can be set from 0° to 3° F (ISU 9070). The thermostat uses the cooling system to reduce humidity by lowering the temperature up to 3° F below the current cool setpoint until the desired humidity level is reached. If set for A/C with Low Speed Fan, configure U1, U2, or U3 as normally open or normally closed (ISU 9050) and wire the terminal to the Low Speed Fan terminal on the equipment. For example, if the U1, U2, or U3 terminal is normally closed, it will open when the thermostat calls for dehumidification.

Note: The thermostat will not lower the fan speed when the second stage of cooling is on.

The Whole House Dehumidifier option requires a dedicated unit for dehumidification. The thermostat can be set up to control dehumidification in all modes (Heat, Off, Cool [ISU 9120]).

If humidification and dehumidification are set up to operate in the same system mode (Heat, Cool, Off), and you are sensing humidity from one location, the thermostat will automatically enforce a 15% deadband between the humidification and dehumidification settings. The thermostat will automatically switch between humidification and dehumidification to maintain the desired humidity level.

If humidification and dehumidification are set up to operate in the same system mode (Heat, Cool, Off), and you are sensing humidity from two different locations using a remote wireless indoor sensor (for example, main level and crawl space), the thermostat will allow humidification and dehumidification to operate at the same time, and there is no deadband between humidification and dehumidification settings.

Commercial dehumidification

The thermostat reads the indoor humidity level and allows the user to set a dehumidification setting. The thermostat controls the humidity level using the cooling system or a dehumidifier.

Dehumidification Equipment Options: (ISU 9000)

When set for A/C with Low Speed Fan, A/C with High Speed Fan, or Hot Gas Bypass, there are six methods of dehumidification control: (ISU 9080) See descriptions of each, below.

  1. Basic: This option uses the cooling system to reach the desired humidity level. Minimum On Time, High Humidity Comfort Reset, and Reheat are not used with this method. This setting is commonly used if your dehumidification equipment is Hot Gas Bypass.
  2. Minimum On Time (ISU 9090): This option ensures that the compressor runs long enough to effectively reduce humidity when the cooling equipment is cycled on. The compressor will run for the minimum "on time" you set until the desired humidity level is reached.
  3. High Humidity Comfort Reset (ISU 9100): This option uses the cooling system to lower the temperature up to 5° F below the current cool setpoint until the desired humidity is reached. The high humidity comfort range is from 1° to 5° F.
  4. High Humidity Comfort Reset with Minimum On Time (ISU 9090 and 9100): This method uses both options above to reduce humidity while maintaining a comfortable temperature.
  5. Reheat (ISU 9080): This option allows heating to run during dehumidification to help maintain a comfortable temperature. If only cooling stage 1 is used, during the "off" cycle, both cooling and heating run at the same time as needed to dehumidify without overcooling. This option cannot be used in the Heat mode. This option is effective only if using a system with the A-Coil located before the heating coil (heat exchanger).
  6. Reheat with Minimum On Time (ISU 9080 and 9090): This method uses both Reheat and Minimum On Time options above to reach the desired humidity level.

The Dehumidifier option requires a dedicated unit for dehumidification. The thermostat can be set up to control dehumidification in all modes (Heat, Off, Cool [ISU 9120]).

Hot Gas Bypass: During a call for dehumidification, the cooling capacity will be used to remove more latent heat than sensible heat. The operation of Hot Gas Bypass varies by equipment. For more details, contact the equipment manufacturer.

Reheat: Reheat can be used on heat pump applications that have a forced air backup heat source (gas, oil, or electric). The thermostat will turn on the first stage of forced air backup heat during Reheat.

Southern Dehumidification Away Mode

Southern Dehumidification Away Mode protects the home when unoccupied for long periods of time during hot and humid weather by maintaining the desired humidity and temperature settings. Southern Dehumidification Away Mode options: (ISU 9180 to 9200)

You can control humidity with a dehumidifier or a cooling system. If a cooling system is used, humidity is controlled by cooling indoor air to the Low Limit Temperature Setting. When the desired humidity level is reached, the system will maintain the Southern Dehumidification Away Mode temperature setting.

Ventilation

The thermostat can be set for the following ventilation types: (ISU 10000)

Ventilation Control Methods (ISU 10050)

Ventilation can be set up to meet ASHRAE or Percent On Time settings. To meet these settings, the thermostat will ventilate during calls for heat, cool, and fan. If the required ventilation has not been achieved for ASHRAE or Percent On Time, the thermostat will force the ventilation equipment on.

System Components & Operation

Indoor sensor operation

Diagram Description: "Screenshots show the thermostat interface for selecting sensors for Temperature Control, Humidification Control, and Dehumidification Control."

Temperature control

The thermostat can be set to respond to its internal temperature sensor, or to an optional remote indoor sensor. If multiple sensors are used, the thermostat will respond to an average of temperatures detected at each sensor.

Humidification control

If optional remote indoor sensors are installed, you can choose which sensor you want to use for humidification control. You can use a different sensor for dehumidification.

Dehumidification control

If optional remote indoor sensors are installed, you can choose which sensor you want to use for dehumidification control. For example, you can use one sensor for humidification control, and another for dehumidification.

Wireless indoor sensor

Battery level indicators (when batteries are inserted)

Battery level indicators (during use)

The Wireless Indoor Sensor is compatible only with RedLINK 2.0 thermostats. The thermostat can use up to 6 optional wireless sensors.

Alerts and diagnostics

Maintain close contact with your customers by providing more comfort and efficiency with alerts and diagnostics. Alerts and reminders can notify customers when maintenance or service is needed, and display your contact information to make it easy for them to reach you. The following are only a few of many options. Check the thermostat's on-screen menus for more.

Alerts Log

Access via MENU > INSTALLER OPTIONS > DATA LOGS > ALERTS LOG.

The thermostat saves the most recent 25 alerts. It records the date, time, alert status (snoozed, dismissed, recovered), and diagnostic information to help you identify and correct problems.

User Interactions Log

Access via MENU > INSTALLER OPTIONS > DATA LOGS > USER INTERACTIONS LOG.

Check this log to find out if a problem was caused by an accidental user error. The log shows most changes made to thermostat settings, by time and date, and describes what change was made.

The thermostat records the most recent 250 changes. You can quickly search them by date and time, or by function. This feature can be turned off if necessary, so that no user interactions are recorded.

Examples:

Delta T Diagnostics

Access via MENU > INSTALLER OPTIONS > SET UP DIAGNOSTICS.

If a discharge and return air sensor is installed, the thermostat can track system performance over time. It measures this as "Delta T." This can tell you if the system is performing above or below expected standards, which would normally go unnoticed and may cause unnecessary energy use. It can also detect and warn about problems early, before heating or cooling equipment fails.

The thermostat will measure and record Delta T of the system for each stage you test. This information can be used to set the proper Delta T fault limits of the system. When the system operates outside those limits multiple times, an alert is recorded in the log. If configured to do so, the system will then display an alert to the user.

Delta T Alert Sensitivity is adjustable in the Installer Setup (ISU 13180).

Delta T diagnostics is only for non-zoned forced air systems.

Replacing System Components

To replace an Equipment Interface Module (EIM)

Follow steps below to disconnect the thermostat and RedLINK accessories. See pages 5-6 to re-link devices.

At the Thermostat

  1. Press MENU > INSTALLER OPTIONS, then enter date code when prompted (printed on back of thermostat). Or press MENU > EQUIPMENT STATUS to find the date code.
  2. Scroll down to select WIRELESS DEVICE MANAGER.
  3. Press REMOVE DEVICE, then select THIS THERMOSTAT to remove.

At the Portable Comfort Control

  1. Press and hold the blank space (or arrow if present) in the lower right hand corner of the screen until the display changes.
  2. Press REMOVE, then YES to disconnect from the old EIM.

Diagram Description: "A diagram of the Portable Comfort Control screen highlights the area to press and hold to initiate disconnection."

At the Indoor Sensor, RedLINK Internet Gateway, Entry/Exit Remote, Vent Boost Remote, or TrueSTEAM Wireless Adapter

Press and hold the CONNECT button on the RedLINK accessory until the status light glows amber (hold for about 10 seconds). This will disconnect the device from the old EIM or thermostat.

To replace a thermostat

At the EIM (Skip this step if no EIM is used)

Press and hold the CONNECT button on the EIM until the status light glows amber (hold for about 10 seconds). This will disconnect ALL devices from the EIM.

At the Portable Comfort Control

  1. Press and hold the blank space (or arrow if present) in the lower right hand corner of the screen until the display changes.
  2. Press REMOVE, then YES to disconnect from the old thermostat.

At the Indoor Sensor, RedLINK Internet Gateway, Entry/Exit Remote, Vent Boost Remote, or TrueSTEAM Wireless Adapter

Press and hold the CONNECT button on the RedLINK accessory until the status light glows amber (hold for about 10 seconds). This will disconnect the device from the old thermostat.

To remove accessories from an EIM or thermostat

At the Thermostat

  1. Press MENU > INSTALLER OPTIONS, then enter date code when prompted (print on back of thermostat). Or press MENU > EQUIPMENT STATUS to find the date code.
  2. Scroll down to select WIRELESS DEVICE MANAGER.
  3. Press REMOVE DEVICE, then select the device you want to remove.

OR: At the EIM

Press and hold the CONNECT button on the EIM until the status light glows amber (hold for about 10 seconds). This will disconnect ALL devices from the EIM.

If the THX9321 thermostat is set up without an EIM, all thermostat settings must be reset before it can be used with an EIM. Press MENU > INSTALLER OPTIONS, scroll down to select ADVANCED OPTIONS, then press RESTORE FACTORY DEFAULTS.

Specifications & Replacement Parts

Operating Ambient Temperature

Operating Relative Humidity

Physical Dimensions (height, width, depth)

Electrical Ratings

Terminal Voltage (50/60 Hz) Max. Current Rating
W - O/B18 to 30 VAC1.00A
W - O/B (EIM only)18 to 30 VAC and 750 mVDC1.00A
Y (cooling)18 to 30 VAC1.00A
G (fan)18 to 30 VAC0.50A
W2 - Aux 1 (heating)18 to 30 VAC0.60A
Y2 (cooling)18 to 30 VAC0.60A
W3 - Aux 218 to 30 VAC1.00A
A-L/A (Output)18 to 30 VAC1.00A
U1, U130 VAC max.0.50A
U2, U230 VAC max.0.50A
U3, U330 VAC max.0.50A

Accessories & Replacement Parts

Item Part Number
Equipment Interface ModuleTHM5421R1013
RedLINK Internet GatewayTHM6000R1002
Wireless Entry/Exit RemoteREM1000R1003
Wireless Vent and Filter Boost RemoteHVC20A1000
Portable Comfort ControlREM5000R1001
Occupancy Sensor for Remote SetbackWSK-24
Wireless Outdoor SensorC7089R1013
Wireless Indoor SensorC7189R1004
Wired Outdoor Sensor 10k ohm NTCC7089U1006
Wired Wall-mount Indoor Sensor 10k ohm NTCC7189U1005
Wired Flush-mount Indoor Sensor 20k ohm NTCC7772A1004, C7772A1012
Wired Wall-mount Indoor Sensor 20k ohm NTCTR21
Wired Wall-mount Indoor Sensor 10k ohm NTCTR21-A
Discharge or Return Air Sensor 10k ohm NTCC7735A1000
Discharge or Return Air Sensor 20k ohm NTCC7041
Discharge or Return Air Sensor 20k ohm NTCC7770A1006
Cover Plate (covers marks left by old thermostats)50028399-001
Battery Pack (For demo use only)THP1000A1007
Wire Saver ModuleTHP9045A1023

Regulatory Information

FCC Compliance Statement (Part 15.19) (USA only)

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

FCC Warning (Part 15.21) (USA only)

Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

FCC Interference Statement (Part 15.105 (b)) (USA only)

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.

If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

Equipment interface module, thermostats and outdoor sensor

To comply with FCC and Industry Canada RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for these transmitters must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.

Portable Comfort Control

This portable transmitter with its antenna complies with FCC and Industry Canada RF exposure limits for general population/uncontrolled exposure. This device must not be co-located or operating in conjunction with any other antenna or transmitter.

Section 7.1.2 of RSS-GEN

Under Industry Canada regulations, this radio transmitter may only operate using an antenna of type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.

Section 7.1.3 of RSS-GEN

Operation is subject to the following two conditions:

  1. this device may not cause interference, and
  2. this device must accept any interference, including interference that may cause undesired operation of the device.

Need Help?

For assistance please visit http://customer.resideo.com or call toll-free: 1-800-468-1502

Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
https://customer.resideo.com

©2021 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International, Inc. This product is manufactured by Resideo Technologies, Inc. and its affiliates.

Models: THX9321 Prestige IAQ 2.0 with EIM, THX9321, Prestige IAQ 2.0 with EIM

File Info : application/pdf, 28 Pages, 1.26MB

PDF preview unavailable. Download the PDF instead.

69-2490

Related Documents

Preview Honeywell Home THM5421R1021 Equipment Interface Module Installation Guide
This installation guide provides detailed instructions for installing the Honeywell Home THM5421R1021 Equipment Interface Module, compatible with Prestige IAQ, VisionPRO 8000, and Wireless FocusPRO thermostats.
Preview Honeywell Home Prestige Touch Screen Thermostat User Guide
Comprehensive user guide for the Honeywell Home Prestige Touch Screen Thermostat, detailing features, programming, settings, troubleshooting, and warranty information for residential and commercial use. Learn how to optimize your home comfort and energy savings.
Preview Honeywell Home THM6000R7001 RedLINK Internet Gateway Installation Guide
Comprehensive installation instructions and specifications for the Honeywell Home THM6000R7001 RedLINK Internet Gateway, detailing setup, LED behavior, and regulatory compliance for remote thermostat access.
Preview Honeywell Home DR90A3000/DR120A3000 Professional Installation Guide
A comprehensive guide for the professional installation of the Honeywell Home DR90A3000 and DR120A3000 whole-house dehumidifiers. This document outlines included components, required tools, optional controls, and detailed installation steps for optimal performance and integration with HVAC systems.
Preview Honeywell Home T10 & T10+ Pro Smart Thermostat with RedLINK® 3.0 - Installation Guide
Explore the advanced features and installation process for the Honeywell Home T10 and T10+ Pro Smart Thermostats. This guide covers smart scheduling, RedLINK® 3.0 integration, Apple® HomeKit™ compatibility, and energy-saving capabilities for optimized home climate control.
Preview Honeywell Home Indoor Air Quality Solutions Guide
A comprehensive guide to Honeywell Home indoor air quality (IAQ) solutions, covering air filtration, humidification, dehumidification, and ventilation systems from Resideo, designed to improve home comfort and health.
Preview Honeywell Home T10 & T10+ Pro Smart Thermostat Professional Install Guide
Professional installation guide for Honeywell Home T10 and T10+ Pro Smart Thermostats with RedLINK 3.0. Covers mounting, wiring, system compatibility, sensor setup, Apple HomeKit integration, and troubleshooting. Essential resource for HVAC technicians and installers.
Preview Honeywell Home RedLINK Zoning Options Guide
A comprehensive guide to Honeywell Home RedLINK zoning solutions, detailing system configurations, compatible thermostats, and wiring diagrams for various HVAC systems.