THE POSSIBILITIES AND LIMITATIONS OF ANCHOR SITE TESTING

Don't guess. Test. But interpret it correctly.

If you have the following questions, you will find the answers in this document:

ABSTRACT

On-site testing is one important element of the inspection of anchoring or post-installed rebar activities where:

Fig. 1 Hilti test execution and evaluation framework based on base material and anchor type, purpose and type of on-site test. This framework visually represents the relationship between base material (Masonry standard/non-standard, Concrete standard/non-standard, Other unknown), anchor type (Chemical, Mechanical, Plastic), purpose (Resistance determination, Setting quality validation), type of test (Pull-out (destructive), Proof-load (non-destructive)), and evaluation method (referencing British Standards like BS 8539 and EOTA TR documents).

However, if the interpretation of on-site testing results is not done correctly, this assessment could compromise the stability of the structure, put human life at risk and/or lead to considerable economic consequences.

The statements above are explained and justified on the following pages.

GENERAL BACKGROUND

Hilti anchor and post-installed rebar systems carrying an approval, installed according to the manufacturer's installation instructions and in base materials within the scope of the approval do not require on-site testing for performance verification. Generally speaking, you will encounter just three situations when on-site testing should be performed:

Non-destructive loading (proof loading) is done by applying tension loads. The load level is selected sufficiently high to provide assurance of correct installation or to determine targeted design resistance values but not so high as to result in damage (e.g. in the form of yielding or permanent slip) to a correctly installed anchor. Proof loads should be maintained long enough to enable a determination of no anchor or rebar movement. Given this objective, it should be clear that proof loads are set as a percentage of the tested tension capacity of the anchor or rebar, not the design tension load.

Note that, depending on the embedment to diameter ratio and the steel grade, this load might or might not subject the anchor to yield level stresses. Where lower yield steels are used, it should be verified that the proof loads do not exceed 80% of the nominal yield stress of the steel anchor components.

If proof load is used to verify proper installation, proof loading equipment may have load reactions close to the anchor but with sufficient clearance so any movement would be visible. If proof load is used to determine design resistance values, proof loading equipment may have load reactions far away from the anchor to determine the base material strength. Hilti provides a complete on-site testing service with the latest equipment, including a detailed test report and an evaluation report.

Destructive loading is also done by applying tension loads. The load level is selected sufficiently high to result in damage (e.g. in the form of yielding or base material failure).

However, on-site testing with one or multiple products independent of the reason can never:

Although no universal standard exists in Europe for conducting on-site testing, this type of assessment has been in use as an adjunct to anchor installation quality control and for the determination of design resistance for many decades. Therefore, Hilti investigated the existing national and European standards to provide a consistent and global on-site testing service that is state of the art.

Fig. 2 Hilti proposal for test execution and evaluation method based on base material and anchor type, purpose and type of on-site test. This diagram details test execution and evaluation methods, referencing specific standards like BS 8539 Annex B.2.3.1, B.2.3.2, and BS 8539 9.3 + Annex B.3.

HOW MANY ANCHORS / POST-INSTALLED REBARS SHOULD BE TESTED?

There is no universal rule regarding the percentage of anchors or rebars that should be tested, nor is there any existing statistical basis for the percentages usually specified. Therefore, Hilti investigated again the existing national and European standards to provide a proposal for the number of tests that should be done. However, the numbers as given in Fig. 3 should be seen as an indication only as the requirements for the proof load program may vary significantly from case to case. Clearly, the number of anchors to be proof loaded for example is dictated by structural safety as well as practical considerations and reason for testing. For example, while it is typical on a large job to require that anywhere from 2.5 to 20 percent of the installed anchors of a given type and size be proof loaded, this requirement must be adjusted where, say, only four large anchors in a baseplate are to be verified. In such a case, it is not unreasonable to require that all four anchors be proof loaded, particularly if the consequences of failure are significant.

For highly redundant applications and less critical applications such as rebar doweling for shotcrete applications or slab on grade doweling, proof loading of a minimum random sampling of 5% of the anchors may suffice. Ultimately, the Engineer of Record should determine the sampling rates.

Hilti Engineers are available to advise you, but the decision remains with the Engineer of Record.

Fig. 3 Number of tests to be performed according to evaluation method, purpose and reason (type). This table outlines the number of test anchors required for different purposes (Resistance determination, Setting quality validation), types of tests (Pull-out, Proof-load), methods (BS 8539 standards), and sample sizes (e.g., nTest = ≥ 5, nTest = 5, nTest ≥ 2.5% OR nTest ≥ 5%, Min. 3 fastenings). It also specifies anchor types and base materials.

LET'S GO ON-SITE AND DISCUSS A FEW SCENARIOS

Scenario A

(a1) Anchors approved for masonry installed in a non-standard masonry brick

(a2) Anchor or a post-installed rebar approved for concrete to be installed in concrete where the concrete strength class is not known.

Is that the right scenario for Hilti on-site testing?

The answer is a clear "yes"

Why?

No technical data for the design of the anchor is available or the technical data for the specific fastening solution is incomplete. This is based on the fact that as mentioned above – the base material is not sufficiently well known and not covered adequately by an approval but it's within the category (similarity) and therefore comparable with the base material of the approval.

Why is the "similarity" of the base material so important?

We know very well the influencing parameter on the concrete cone failure load of anchors anchored in normal weight concrete or masonry. The main parameters for concrete cone failure are embedment depth (hef) and concrete compressive strength (fc). However, we have no indication how an anchor performs in a base material like ice or butter. Even if the on-site testing would give us “results” we are still not able to design, because we do not know the decisive parameters on the failure load, consequently the base material should be similar to the one in the scope of the approval.

Necessary information or questions which should be stated for Scenario A:

If the answer is "no", damage from testing can be accepted and destructive on-site tests may be conducted to determine the resistance of the fastening solution. It is important to note that in such a case a simplified or statistical evaluation can be performed. In that case we may need fewer tests.

If the answer is "yes", damage from testing cannot be accepted. You need to rely on non-destructive on-site tests to determine the resistance of the fastening solution. A higher number of tests is required when only a simplified evaluation is possible.

Jobsite experience:

The mechanical properties of a base material, especially masonry, are not always what you would expect. Some weaker-looking bricks will deliver the tension values you expect, while others that you'd expect to manage higher tension loads, fall short.

In one specific case, Hilti assisted a team on-site who estimated that the capacity of an anchor installed in a brick wall would be at least the minimum of our allowable load. He estimated right, but the design still has to be changed.

The injectable adhesive bonded effectively with the brick – no remarks there. As we performed on-site testing with the allowable load as unconfined test (wide support) the brick was pulled right out of the masonry wall. The masonry mortar, which was like fine-grained powder, was to blame. So, the Engineer chose to re-assess his design thanks to this sobering demonstration.

Scenario B

(b1) Approved anchor or rebar system is to be installed in known and approved base material. The designer included proof load requirements on the general notes sheet of the structural drawing set.

Is that the right scenario for Hilti on-site testing?

The answer is a clear "yes"

Why?

A scenario where on-site testing is included (proof load) in their structural drawing serves as one piece of the big picture of quality assurance. Injection adhesive systems (such as epoxy mortar) have special requirements to ensure that the adhesive is correctly mixed and dispensed. These usually include dispensing a small quantity of adhesive from the mixing nozzle prior to injecting it into the hole. The objective of adhesive injection is to avoid entrained air. For long holes and holes drilled horizontally or overhead, special equipment such as extension tubes, stoppers and end caps may be specified to achieve a void-free injection. Therefore, proper installation techniques are needed for concrete anchors to perform as expected.

This, in general, can also be achieved if:

Therefore, non-destructive on-site testing (proof loading) may be performed to validate the installation quality of the installed fasteners according to Fig.1 and Fig. 2.

Necessary information or questions which should be stated:

Scenario C

First of all, this is the wrong scenario for on-site testing even if it happens quite often

(c1) Anchor or post-installed rebar performance of different products are compared on the jobsite via on-site testing by means of comparing the measured load values of the individual products.

Is that the right scenario for Hilti on-site testing?

The answer is a clear "No". Taking the wrong conclusions from on-site testing could compromise the stability of the structure, putting human life at risk and/or lead to considerable economic consequences.

Why?

Now we have to dig a little bit deeper.

Fundamentally, all types of safety-relevant anchors should be designed in such a way, that they are resistant and durable under service loads and provide an adequate margin of safety against failure. Therefore, in the European Union, United States and other countries, approval processes exist to provide an independent assessment. Approvals are based on tests intended to verify the suitability of a system and to determine the admissible service conditions.

Suitability tests are designed to verify the effectiveness of the anchor under unfavorable application conditions. These tests are generally conducted in concrete with a strength at the lower and upper end of the usual field of application. Tests in cracked and uncracked concrete specimens may be chosen, depending on the intended use of the anchor. The effects of installation variances are checked insofar as they are relevant. Factors investigated and covered in the approval documents may include:

These tests may account for the influence of sustained and repetitive loads acting on the anchorage itself as well as the component in which the anchor is placed. Suitability tests also consider circumstances which may occur while installing the anchor and during service life. In summary, we can say a product sensitive to these circumstances may have comparable test loads during on-site testing compared to a non-sensitive product. However, if all circumstances would be tested (involving hundreds of tests, as carried out during the approval process) the differences could be significant or it could even happen that such a product would never get an approval.

Another buzzword for scenario C is "long term behavior" and we should remember that the expected life-time of an anchor or rebar is at least 50 years.

The long-term behavior of anchors or post-installed rebars is also checked within the approval process with the most relevant tests named below.

This behavior can also never be checked by a “simple on-site test” and value comparison.

Therefore, the wrong conclusion of Scenario C may lead to reaching a critical displacement value of the anchor or post-installed rebar during the working life by means of pullout failure.

Let's have a deeper look into the crack movement test mentioned above. It may seem surprising, but this test is the decisive one for most anchoring products. Products showing highest load values in a pullout test may fail in the crack movement test.

Without going into detail on the exact procedure, the tests are conducted as follows:

After installing the anchors in cracked concrete, the anchors are under sustained load based on the characteristic load evaluated in a short-term test/pullout test. While the anchors are loaded under tension, cracks are opened between 0.1 mm and 0.3 mm 1000 times and the displacement of the anchor under tension is measured. During these tests the measured displacement should be below the constant value of 3 mm.

Fig. 4 Test results of crack movement test (a) and reasonable explanation for the crack movement test (b). Figure 4a is a graph plotting measured displacement against the number of crack openings (log scale) for three different products, indicating which meet a 3mm displacement limit. Figure 4b illustrates the load acting on a beam as a function of crack width, showing the effect of permanent load (g) and variable load (p) on crack opening and closure.

This behavior of the anchors can never be checked by on-site testing. However, this is included in the basic characteristic bond strength values provided in the relevant approval document.

In the words of an experienced engineer:

"Testing is easy if you know what you're doing. It doesn't have to take a lot of time if you use Hilti's on-site testing service. And it can give you peace of mind knowing you are not guessing. How do you know when you're guessing? You maybe think about your design when you get home. You dream about a certain connection. Something's not quite right but you're not sure exactly what it is".

"Don't guess. Test. But interpret it correctly. And get peace of mind!"

Models: Anchor Site Testing, Anchor Site, Testing

File Info : application/pdf, 12 Pages, 554.99KB

PDF preview unavailable. Download the PDF instead.

Thailand EXT OST expert article V1.1 Microsoft Word for Microsoft 365

Related Documents

Preview Hilti Concrete-to-Concrete Connections Handbook
A comprehensive guide to concrete-to-concrete connections using post-installed systems, covering applications, design methods, regulatory frameworks, and Hilti solutions. Includes detailed explanations of lap splices, end anchorages, and shear-friction applications.
Preview Hilti 预订平台用户指南与常见问题解答
一份关于 Hilti 全新预订平台的详细用户指南和常见问题解答,涵盖注册、预订、测试流程及报告获取,旨在提升客户服务效率。
Preview Hilti HUS4 Bonded Screw Fastener: A New Anchoring Technology
A whitepaper for planners and structural engineers detailing the Hilti HUS4 bonded screw fastener with Hilti HUS4-MAX capsule, a novel anchoring technology combining mechanical and chemical fastening benefits.
Preview HILTI Anchor Fastening Technology Manual
Comprehensive guide to HILTI anchor fastening systems, covering design, applications, technical specifications, and safety for mechanical, adhesive, and rail anchoring solutions.
Preview Hilti HIT-HY 270: Adhesive Anchoring System for Masonry
Discover the Hilti HIT-HY 270, a versatile adhesive anchoring system for secure fastenings in hollow and solid masonry. This guide covers installation, safety, and product specifications.
Preview Hilti HIT-HY 170: Universal Adhesive Anchoring System
Discover the Hilti HIT-HY 170, a high-performance universal adhesive anchoring system designed for reliable and versatile fixing in concrete and various masonry types. Learn about its applications, safety, and technical specifications.
Preview Hilti HIT-HY 200 Injectable Mortar: Technical Data & Submission Guide for Post-Installed Rebar
Comprehensive technical specifications, test reports, and application guidelines for Hilti HIT-HY 200 Injectable Mortar, a high-performance adhesive anchor for post-installed rebar in concrete.
Preview Hilti KB-TZ2 Wedge Anchor Installation and Specifications
Guide for installing the Hilti KB-TZ2 wedge anchor (1/2" x 3"). Details installation steps, required tools, and technical specifications for concrete and CMU applications.