CPM, CPMSP Cascade Header Kits

Installation, Commissioning and Maintenance Instructions

This manual provides detailed instructions for the installation, commissioning, and maintenance of Lochinvar CPM and CPMSP cascade header kits.

The CPM and CPMSP cascade systems are designed for use with Lochinvar's high-efficiency condensing boilers. This guide should be read in conjunction with the Installation (ICM) manual for the specific CPM or CPM SP boiler model.

For the ICM manual, please visit www.lochinvar.ltd.uk.

1. Introduction

This Installation manual should be read in conjunction with the installation (ICM) manual for either the CPM gas-condensing boiler or the CPM SP cascade system boiler. If you do not have a copy of the ICM, it can be downloaded at www.lochinvar.ltd.uk.

Figure 1: A typical cascade configuration showing two Lochinvar CPM boilers connected via a frame and hydraulic piping.

This Cascade manual is for use with the CPM and CPM SP wall-hung high-efficiency condensing boilers manufactured by Lochinvar Limited. These boilers are available, in order of ascending output, as CPM 58, CPM 77, CPM 96, CPM 116, CPM 144, CPM 175, and CPM SP Range.

The CPM 58-116 boilers can be supplied in one cascade set, as can the CPM 144-175 boilers; due to their size difference, they cannot be mixed. Lochinvar Limited can supply standard cascade systems with mounting frame, piping, and low-loss headers for up to four boilers.

All CPM boilers are equipped as standard with an internal cascade manager for up to twelve boilers. No extra controllers are necessary; you only connect a 2-wire cable between all boilers.

The low-loss header can be fitted on the right-hand side as well as on the left-hand side without altering the pipework. The gas connection can be fitted on one or both sides, independently from the side chosen for the low-loss header. To commission the cascade installation, it is necessary to set a number of parameters on the boilers, see the boiler ICM.

2. Main Dimensions

Figure 2.1: Technical drawings illustrating the main dimensions of cascade setups, including frame width (L1), hydraulic group width (L2), width with low velocity header (L3), gas connection (A), header connection (B), and various heights (H1, H2, H3) and diameters (D1, D2, D3).

2.1 Cascade dimensions

The picture shows connecting sets for CPM boilers – for CPM SP boilers the connecting sets are different.

2.2 Cascade Dimensions (use in conjunction with 2.1)

CPM 58-116 and CPMSPCPM 144-175
2 boilers3 boilers4 boilers2 boilers3 boilers4 boilers
L1 (frame)101515201980101515201980
L2 (standards)114016302084112516302090
L3 (total)135819142393140819402465
L4 (open header)190265290265290355
H1 (gas)787789791766766768
H2 (open header)766766768144165168
H3 (open header)436487440487440440
D1 (Connection)RP 1½"DN 65 PN6 (2½")DN 80 PN6 (3")DN 65 PN6 (2½")DN 80 PN6 (3")DN 96 PN6 (4")
D2 (Connection)R 1½"DN 65 PN6 (2½")DN 80 PN6 (3")DN 65 PN6 (2½")DN 80 PN6 (3")DN 96 PN6 (4")
D3 (gas)R 1¼"R 1½"R 2"R 2"R 2"DN 80 (3")
A (gas)271283283338338338
B (headers)283283283283283283

3. Explanation of Parts and Groups

Each cascade set consists of the following parts and groups:

  1. Two to four CPM/CPM SP boilers.
  2. The frame group (with locking plates) as determined by the number of boilers.
  3. Connecting groups to connect the boilers to the hydraulic groups (one group for each boiler, each group consists of one gas, one flow, and one return connecting set).
  4. Hydraulic group, comprising one gas, one flow, and one return header with all fixing and connecting parts.
  5. Low-loss header or hydraulic separation plate heat exchanger (plate would be supplied loose).

Figure 3.1: An illustration showing the main components of a cascade system: CPM/CPM SP boilers, a frame group, hydraulic group, connecting sets, and a low velocity header. It notes that return connecting sets differ for CPM and CPM SP boilers.

4. Frame Groups

Figure 4.1: Diagrams illustrating different frame group configurations for 1, 2, 3, and 4 boilers.

4.1 Cascade frame groups for 1, 2, 3, and 4 boilers

4.2 Frame group parts (use in conjunction with 4.1)

Item NumberDescription2 Boiler mounting frame Quantity3 Boiler mounting frame Quantity4 Boiler mounting frame Quantity
1standard223
2upper beam112
3mid/lower beam224
4locking plate234
5lock bolt M8 x 35234
6seal plug 70mm x 50mm223
7seal plug 50mm x 50mm446
8bolt M8 x 70121218
9nut M8121218
10washer M8141522
11adjusting bolt standard M16 x 80446

5. Mounting the Boilers on the Frame

All lines/piping must be mounted free of tension. The weight of all the components must be supported separately from the boiler so there is no force on the connections. This might influence the mounting position of the boiler.

Before mounting the boiler on the frame, ensure that the frame is level in both directions. If necessary, adjust with the adjusting bolts on the lower side of the frame (see drawing).

After mounting the boiler on the frame, ensure that the boiler is level. If necessary, adjust with the adjusting bolts on the lower rear side of the back panel. (See drawing).

When the adjusting bolts are not sufficient, it may be necessary to fill behind the bolts to get the boiler level. The levelling margin is between boiler hanging level and hanging backwards a little.

The boiler should not lean forward in the mounted position.

Lock the suspension bracket with the locking strip to prevent the boiler from falling off the bracket (See drawing).

Figure 5.1: Diagrams showing how to mount boilers on the frame, including details on locking mechanisms and leveling using adjusting bolts.

5.1 Mounting details

6. Mounting the Connecting Sets

First, connect the connecting sets hand-tight to the boiler connections. In a cascade set-up, do NOT use the T-pieces delivered with the boilers.

The shortest connecting set should be connected to the gas connection on the boiler.

Make sure to connect the flow connecting set (middle length) to the boiler flow connection (left-side connection) and the return connecting set (longest) to the boiler return connection (right-side connection).

The open connection in the flow connecting set is meant for a pressure relief valve, and the one in the return connecting set is to be used for an 8-litre expansion vessel as per BS6644. A kit is available as an ancillary option.

For the CPM SP116 boiler, the return connecting set differs due to the external pump.

Figure 6.1: Illustrations of the different connecting sets (gas, flow, return) and their connections to the boilers. It also shows a specific setup for CPM SP boilers with an external pump.

6.1 Connecting sets

Description2 boilers Quantity Required3 boilers Quantity Required4 boilers Quantity Required
Connecting set gas "234
Flow connecting set 1"234
Return connecting set CPM 1"234
Return connecting set CPM SP 1"234
Connection size relief valve and bleed valve: both Rp 1"234
Description2 boilers Quantity Required3 boilers Quantity Required4 boilers Quantity Required
Connecting set gas 1"234
Flow connecting set 1¼"234
Return connecting set 1¼”234
Connection size relief valve and bleed valve: both Rp 1"234

7. Mounting the Hydraulic Group

Connect the gas header to the gas connecting sets. Connect the flow header to the flow connecting sets. Connect the return header to the return connecting sets. Mount all headers with the clamps to the frame.

All lines/piping must be mounted free of tension. The weight of all the components must be supported separately from the boiler so there is no force on the connections. This might influence the mounting position of the boiler.

When all parts are mounted in the right place and are free of tension, fasten all couplings and fasten the clamps.

Figure 7: A diagram showing the assembly of the hydraulic group, with color-coded pipes for gas (yellow), flow (red), and return (blue).

7.1 Hydraulic group for 2 boilers CPM 58–116 and/or CPM SP

Figure 7.1: An exploded view of the hydraulic group for 2 boilers, detailing components like gas header, flow header, return header, clamps, seal caps, couplings, gaskets, and bolts.

Item NumberDescriptionHydraulic group for 2 Boilers Quantity
1gas header1
2flow header1
3return header1
4clamp gas header2
5clamp flow/return header4
6seal cap gas header1
7seal cap flow/return header2
8coupling (2-parts)2
9gasket for coupling2
10bolt + nut + washer24

7.2 Hydraulic groups for 3 and 4 boilers CPM 58–116 and/or CPM SP

Figure 7.2: An exploded view of the hydraulic group for 3 and 4 boilers, similar to the 2-boiler version but with different quantities of parts.

Item NumberDescriptionHydraulic group for 3 Boilers QuantityHydraulic group for 4 Boilers Quantity
1gas header11
2flow header11
3return header11
4clamp gas header23
5clamp flow/return header46
6seal cap gas header11
7seal cap flow/return header22
8coupling (2-parts)44
9gasket for coupling1616
10bolt + nut + washer2436

7.3 Hydraulic groups for 2 and 3 boilers CPM 144–175

Figure 7.3: An exploded view of the hydraulic group for 2 and 3 boilers of the CPM 144-175 series.

Item NumberDescriptionHydraulic group for 2 Boilers QuantityHydraulic group for 3 Boilers Quantity
1gas header11
2flow header11
3return header11
4clamp gas header23
5clamp flow/return header46
6seal cap gas header11
7seal cap flow/return header22
8coupling (2-parts)44
9gasket for coupling1616
10bolt + nut + washer2436

7.4 Hydraulic group for 4 boilers CPM 144–175

Figure 7.4: An exploded view of the hydraulic group for 4 boilers of the CPM 144-175 series.

Item NumberDescriptionHydraulic group for 4 Boilers Quantity
1gas header1
2flow header1
3return header1
4clamp gas header2
5clamp flow/return header4
6seal cap gas header1
7seal cap flow/return header2
8coupling (2-parts)4
9gasket for coupling16
10bolt + nut + washer24

8. Low Velocity Headers

The low velocity header can be mounted on the right-hand or the left-hand side of the flow and return headers, whatever is the best place to connect the headers to the heating installation. The supplied caps or flanges must block the opposite end of the flow and return headers.

Figure 8.1 & 8.2: Diagrams illustrating the low velocity headers, showing their dimensions (D, H1, H2, L) and connection points.

9. Plate Separators

For systems where water quality cannot be guaranteed, it may be better to install a plate separator instead of a low velocity header. This will isolate the boilers hydraulically from the dirty system. A suitable plate is available as an option from Lochinvar; these are sized based on the number of boilers required.

See section 6.15 in CPM/CPM-SP Installation Manual for important information regarding the use of a plate separator.

Low velocity headers for boilers 58 – 116
Low velocity groupDrawing2 boilers: E00.000.1643 boilers: E00.000.1654 boilers: E00.000.166
Venting valve ½" 1Fig. 8.1E04.015.066Fig. 8.2 E04.015.066Fig. 8.2 E04.015.066
Drain valve ½"E04.008.025E04.008.025E04.008.025
DR 1½"DN 65 PN6 (2½")DN 80 PN6 (3")
H1 (boiler-side)330330330
H2 (installation-side)436487440
L190265290
Low velocity groupDrawing2 boilers E00.000.1653 boilers E00.000.1664 boilers E00.000.167
Venting valve ½" 1Fig. 8.2E04.015.066Fig. 8.2 E04.015.066Fig. 8.2 E04.015.066
Drain valve ½"E04.008.025E04.008.025E04.008.025
DDN 65 PN6 (2½")DN 80 PN6 (3")DN 96 PN6 (4")
H1 (boiler side)330330330
H2 (installation side)487440439
L265290355

1: Lochinvar standard supply a manual venting valve that can be mounted on top of the low loss header to manually bleed the air from the low loss header. Instead of the ½" manual bleed valve, an automatic air vent can be installed, up to 1" max.

10. Flue Gas and Air Supply

10.1 Individual or Common Flue Systems

Lochinvar Limited CPM/CPM SP cascade-sets can be equipped with individual or common flue systems. Using separate venting material is always preferred above common venting. Only when separate venting cannot be used, should a common vent system be used.

When chosen for an individual flue system, each boiler has its individual flue gas outlet and air supply lines to the outside of the building. This may be executed in parallel or concentric flue gas and air supply pipes. When chosen for a common flue system, this must be executed in parallel flue gas and air supply pipes.

10.2 Individual Flue Systems

Individual flue systems can be chosen as mentioned in the CPM instruction manual. The flue system should comply with the chapter “Flue gas and air supply system” of the CPM/CPM SP manual. For each boiler, the combined resistance of the individual flue gas and air inlet pipe can be calculated and checked with the maximum for the gas-side resistance. Resistance table and example calculations are given in the same aforementioned chapter of the CPM manual.

10.3 Common Flue Systems

Common flue systems must be designed according to: EN 13384-2 “Chimney – Thermal and fluid dynamic calculation methods – Part 2: Chimneys serving more than one heating appliance.”

For common flue gas systems, the parameter P5DB has to be adjusted to prevent recirculation of flue gases.

Lochinvar can supply a common flue cascade system for up to 4no CPM58-116 boilers; see CPM ICM manual for details available at www.lochinvar.ltd.uk.

11. Installation

Follow the instructions given within the ICM manual for either the CPM or CPM SP; these are available from Lochinvar Limited at www.lochinvar.ltd.uk.

12. Cascade Control

12.1 Output Control

The total cascade set-up will act as one single big boiler, switching on and off boilers, depending on the total load necessary to adjust and keep the flow temperature at the calculated value. When the heat demand rises, more boilers are switched on, and when heat demand falls, one or more boilers will be switched off. The boiler that was switched on last will be switched off first (see table below).

12.2 Boiler Sequence

To distribute operating hours equally over all boilers, the working sequence of the boilers will change every two hours.

HourSwitching ON sequenceSwitching OFF sequence
XMaster - Slave 1 - Slave 2 - Slave 3 - Slave 4 - Slave 5 - Slave 6 - Slave 7Slave 7 - Slave 6 - Slave 5 - Slave 4 - Slave 3 - Slave 2 - Slave 1 - Master
X+1Master - Slave 1 - Slave 2 - Slave 3 - Slave 4 - Slave 5 - Slave 6Slave 6 - Slave 5 - Slave 4 - Slave 3 - Slave 2 - Slave 1 - Master - Slave 7
X+2Master - Slave 1 - Slave 2 - Slave 3 - Slave 4 - Slave 5Slave 5 - Slave 4 - Slave 3 - Slave 2 - Slave 1 - Master - Slave 7 - Slave 6
X+3Slave 5 - Slave 6 - Slave 7 - Master - Slave 1 - Slave 2 - Slave 3 - Slave 4Slave 4 - Slave 3 - Slave 2 - Slave 1 - Master - Slave 7 - Slave 6 - Slave 5

Table 1: Boiler sequence example of an eight boiler cascade. In this table, a total of eight boilers (one master, seven slaves) is mentioned as an example; in practice, the maximum number in a cascade, without extra (external) control, is twelve boilers.

13. Options

To complete your cascade set-up / heating installation, you can choose from the following options:

Room Temperature Controllers

1RC OpenTherm with ambient sensorModulatingS04.016.355
2RC OpenTherm with remote ambient sensorModulatingS04.016.358
3Clock thermostatOn / OffE04.016.308
4RCH E-bus with ambient sensor (for EBC)ModulatingS04.016.357
5RCH E-bus with remote ambient sensor (for EBC)ModulatingS04.016.361

Plate Separators

6Plate separator for CPM SP232 PackageLOKG-250L
7Plate separator for CPM SP348 PackageLOKG-400L
8Plate separator for CPM SP464 PackageLOKG-450L

Sensors

9Outside air temperature sensor12kOhm@25°CE04.016.306
10External flow temperature sensor low velocity header10kOhm@25°CE04.016.304
11External ambient sensor for RC and RCH5kOhm@25°CE04.016.359
12External flow temperature sensor heating circuit (zone)5kOhm@25°CE04.016.363

Heating circuit controller

13EBC 2-zone E-bus controllerE04.016.319
14Wall-mounted case with terminal board for EBCE04.000.103
15IF OpenTherm / E-bus interfaceE04.016.362

Parameter programming

16Interface cable and software to programme the boilerS04.016.586

Table 2: Accessories and parts.

Figure 3: A few examples of accessories, showing RC OpenTherm room temperature controller (1 and 2), RCH E-bus room temperature controller for EBC (4 and 5), EBC 2-zone E-bus controller (10) mounted in a wall-mounted case with terminal board (11), and a wall-mounted case with terminal board for EBC (11).

Notes

This section is reserved for additional notes.

Models: CPM58, CPM77, CPM96, CPM116, CPMSP116, CPM144, CPM175, CPM Series Cascade Header Kits, CPM Series, Cascade Header Kits, Header Kits

File Info : application/pdf, 24 Pages, 2.28MB

PDF preview unavailable. Download the PDF instead.

Installation-commissioning-and-maintenance-instructions cascade-header-kit

References

GPL Ghostscript 9.55.0

Related Documents

Preview Lochinvar CPM Boiler Range Flue Guide
Comprehensive guide for Lochinvar CPM boiler flue system installation, covering concentric, twin-pipe, and conventional types. Includes terminal locations, risk assessments, and sizing calculations based on BS5440-1 and IGEM/UP/10 standards.
Preview Lochinvar CPM Series Boiler Replacement Parts List
Comprehensive replacement parts list for Lochinvar CPM Series boilers, including models CPM58, CPM77, CPM96, CPM116, CPM144, and CPM175. Features part numbers, descriptions, and item comments.
Preview Lochinvar FTXL High-Efficiency Fire Tube Condensing Boilers
Explore the Lochinvar FTXL series of high-efficiency condensing fire tube boilers, offering up to 98% thermal efficiency, 10:1 turndown ratio, and advanced SMART SYSTEM control with CON-X-US remote connectivity. Learn about variable flow technology, smooth modulating combustion, and installation benefits.
Preview Lochinvar CREST High-Efficiency Commercial Boilers | 750,000 - 6.0 Million BTU/hr
Explore the Lochinvar CREST series of high-efficiency commercial boilers, featuring up to 96.2% thermal efficiency, 25:1 turndown, CONXUS remote connectivity, and advanced fire-tube technology for optimal performance and cost savings.
Preview Lochinvar SOLUTION High-Efficiency Heating Boiler Installation & Service Manual
Detailed installation and service manual for Lochinvar SOLUTION high-efficiency heating boilers (45,000-260,000 Btu/hr). Covers safety, installation, operation, maintenance, and troubleshooting for qualified technicians.
Preview Lochinvar FTXL Fire Tube Boiler Installation & Operation Manual
Comprehensive guide for the installation and operation of Lochinvar FTXL Fire Tube Boilers, covering models 400, 500, 600, 725, and 850. Includes safety precautions, technical specifications, and maintenance procedures.
Preview Lochinvar FTXL Series Fire Tube Boilers: Product Specifications and Data Sheet
Detailed product specifications for Lochinvar's FTXL series fire tube boilers, covering water, gas, electrical, dimensions, and maintenance clearance requirements. Includes model numbers FTX400 through FTX1000.
Preview Lochinvar Knight XL High Efficiency Commercial Boilers
Discover the Lochinvar Knight XL, a series of high-efficiency commercial boilers offering advanced features like Smart Touch control and Con-X-US remote connectivity. Learn about their thermal efficiency, turndown ratio, and specifications.