TROX Circular Silencer CAK
Installation Manual
GB/en
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn, Germany
Germany
+49 (0) 2845 202-0
+49 (0) 2845 202-265
E-mail: trox@trox.de
www.troxtechnik.com
Product Overview
The CAK type is particularly suitable for ventilation systems with chemically contaminated extract air, e.g., from fume cupboards.
1 Casing of the silencer
2 Spigot
Important Notes
Safety
Correct Use
Circular silencers are used to reduce noise in the circular ducts of ventilation and air conditioning systems within closed rooms.
For the reduction of air-regenerated noise of air terminal units and mechanical self-powered controllers, etc.
Do not use circular silencers in extract air systems in commercial kitchens unless the extract air has been cleaned as much as possible with high-efficiency aerosol separators; see VDI 2052.
Incorrect Use
WARNING! Danger of injury or risk of damage to property due to incorrect use
Incorrect use of the circular silencer can lead to dangerous situations.
Never use the circular silencer:
- outdoors without sufficient protection against the effects of weather
- in process air systems
Modifying the unit or using replacement parts that have not been approved by TROX is not permitted.
Staff
Qualification
The work described in this manual has to be carried out by individuals with the qualification, training, knowledge and experience described below:
Specialized personnel
Specialised personnel are personnel, who due to their specialized training, skills, and experience, as well as knowledge of the applicable standards and regulations, are capable of executing the tasks assigned to them, and of recognizing possible hazards and avoiding them on their own.
Personal protective equipment
Personal protective equipment is equipment that protects the user against health or safety risks at work.
Transport, Storage and Packaging
Personal protective equipment must be worn for various types of work; the protective equipment required is listed in this manual together with the description of each type of work.
Description of Personal Protective Equipment
Industrial Safety Helmet
Industrial safety helmets protect the head from falling objects, suspended loads, and the effects of striking the head against stationary objects.
Protective Gloves
Protective gloves protect hands from friction, abrasions, punctures, deep cuts, and direct contact with hot surfaces.
Safety Shoes
Safety shoes protect the feet against crushing, falling parts, and from slipping on slippery ground.
Repair and Replacement Parts
Only qualified personnel must repair the products, and they have to use genuine replacement parts.
Transport, Storage and Packaging
Delivery Check
Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, contact the shipping company and your supplier immediately.
Transport on Site
Please note:
- Be careful when unloading or moving the product, and pay attention to the symbols and information on the packaging.
- If possible, take the product in its transport packaging up to the installation location.
- Use only lifting and transport gear designed for the required load.
- Always secure the load against tipping and falling.
- Do not move bulky items just by yourself. Get help to prevent injuries and damage.
Storage
Please note:
- Store the product only in its original packaging
- Protect the product from the effects of weather
- Protect the product from humidity, dust and contamination
- Storage temperature: 0 °C to 100 °C.
- Relative humidity: 80 % max., no condensation
Packaging
Properly dispose of packaging material.
Installation
General Installation Information
Personnel
- Specialized personnel
Protective Equipment
- Protective gloves
- Industrial safety helmet
- Safety shoes
CAUTION! Danger of injury from sharp edges, sharp corners and thin plastic parts!
Sharp edges and sharp corners may cause cuts or grazes.
- Be careful when carrying out any work.
- Wear protective gloves, safety shoes and a hard hat.
Please note:
- Horizontal or vertical installation orientation.
- Duct connection on both sides.
- Installation in ducts outside closed rooms requires sufficient protection against the effects of weather.
- Length (L) refers to the airflow direction.
- Installation material is not part of the supply package unless stated otherwise.
- Airflow direction freely selectable.
- Torsion-free installation.
Installation Information for Circular Silencer
General Installation Information
- When designing and constructing ventilation and air conditioning systems, take into account the requirements of VDI 6022, in particular:
- Hygienic, clean installation of all components and their air distribution surfaces
- Inspection and cleaning options by planning inspection/cleaning openings in the ducting system
- Avoidance of leaks
- Affix the circular silencer proficiently and only to load-bearing components.
- Load suspension systems only with the weight of the circular silencer. Adjacent components and connecting ducts must be supported separately.
- Only use approved and sufficiently dimensioned suspensions for fixing. Secure screw connections against self-loosening, e.g., by locking them. Fixing material is not included in the supply package.
1 Fixing to pipe clamps
2 Fixing to suspension element
When installing the circular silencer, choose a load-bearing structure that will support the entire weight of the circular silencer construction.
The weight of the circular silencer must not be supported by the spigots or flanges alone.
- Tension-free assembly
- Structure-borne sound transmission must be avoided by taking suitable measures.
- Installation in ducts outside closed rooms requires sufficient protection against the effects of weather
- Take standard DIN EN 12236 into consideration (suspensions and supports for air ducts)
Assembly to Control Components
Circular silencers without splitters can be used for the reduction of air-regenerated noise of air terminal units and mechanical self-powered controllers. Installation can be carried out without a minimum distance to the control component.
Connecting the Air Duct
When connecting the ducting, the customer must ensure that the connection points are installed as air-tight as possible in order to avoid negative influences from leakages such as air volume deviations, power consumption, etc. Unless otherwise stated, the connecting material is not included in the supply package.
1 Duct
2 Circular silencers
3 Pipe clamp
4 Suspension, e.g. with threaded rod
Technical Data
Before Connecting the Ducting:
- Check the inside of the unit for damage and loose parts.
- Remove any contamination from the ducting.
Leakage Classes
In order to be able to achieve the required tightness of the duct system, it is necessary that suitable sound attenuators and duct components have been selected. In addition, the following should be observed:
- Proper and expert assembly
- Provide seals
- Establish the cable fastening (suspension/support)
Circular Duct – Plastic
Plastic spigot
- Installation on ducting in accordance with DIN 8077.
- With clamp connectors.
Plastic spigot
- Installation on ducting in accordance with DIN 8077.
- By plastic welding.
Technical Data
General Data
Item | Value |
---|---|
Nominal sizes | 125 - 400 mm |
Operating pressure | 1000 Pa max. |
Airflow velocity | < 20 m/s |
Item | Value |
---|---|
Air temperature | 0 °C to 100 °C |
Relative humidity | < 80%, no condensation |
Casing leakage according to | Class D EN 15727 |
Materials of circular silencer | PPs (flame-retardant polypropylene) |
Dimensions and Weights CAK
Dimensions
nominal size | ØD [mm] | ØD3 [mm] |
---|---|---|
125 | 125 | 225 |
160 | 160 | 250 |
200 | 200 | 280 |
250 | 250 | 355 |
315 | 315 | 415 |
400 | 400 | 500 |
Lengths
Nominal length | L [mm] | L1 [mm] |
---|---|---|
500 | 595 | 495 |
1000 | 1095 | 995 |
1500 | 1595 | 1495 |
Weights
nominal size | 500 [kg] | 1000 [kg] | 1500 [kg] |
---|---|---|---|
125 | 2.2 | 4.1 | 5.9 |
160 | 2.6 | 4.7 | 6.8 |
200 | 3.2 | 5.8 | 8.5 |
250 | 4.3 | 7.6 | 10.9 |
315 | 4.6 | 8.6 | 12.5 |
400 | 5.2 | 9.3 | 13.4 |
Dimensions and Weights CAK/.../VF2
Dimensions
nominal size | ØD [mm] | ØD3 [mm] | ØD1 [mm] | ØD2 [mm] | T [mm] | n |
---|---|---|---|---|---|---|
125 | 125 | 225 | 165 | 185 | 8 | 8 |
160 | 160 | 250 | 200 | 230 | 8 | 8 |
200 | 200 | 280 | 240 | 270 | 8 | 8 |
250 | 250 | 355 | 290 | 320 | 8 | 12 |
315 | 315 | 415 | 350 | 395 | 10 | 12 |
400 | 400 | 500 | 445 | 475 | 10 | 16 |
Lengths
Nominal length | L [mm] | L1 [mm] |
---|---|---|
500 | 595 | 495 |
1000 | 1095 | 995 |
1500 | 1595 | 1495 |
Weights
nominal size | 500 [kg] | 1000 [kg] | 1500 [kg] |
---|---|---|---|
125 | 2.5 | 4.4 | 6.2 |
160 | 3.0 | 5.1 | 7.2 |
200 | 3.6 | 6.2 | 8.9 |
250 | 4.9 | 8.2 | 11.5 |
315 | 5.3 | 9.3 | 13.7 |
400 | 6.8 | 10.9 | 15.0 |
Commissioning
Commissioning and Operation
Personnel
- Specialized personnel
Before you start commissioning:
- Check proper installation of the circular silencers.
- Ensure that all sound attenuators are clean and free from residues and foreign matter.
Commissioning
Code of good practice for commissioning
Commissioning is governed by the standard "DIN EN 12599 Testing and measuring procedures for the transfer of installed ventilation and air conditioning systems", and, if applicable, contractually agreed services between HVAC contractors, system owners and installation engineers. The standard describes the essential commissioning steps of the completeness check, function check, function measurement as well as report generation and handover.
Operation
Once commissioning has been completed, the circular silencer will operate in a self-powered manner and require no intervention from the system owner. Depending on the area of application of the circular silencer, test specifications and intervals may have to be observed.
Maintenance
System Owner's Responsibility
WARNING! Only authorised specialist personnel are allowed to perform the described maintenance measures.
The system owner is responsible for maintenance. The system owner is responsible for creating a maintenance plan, for defining the maintenance goals, and for the functional reliability of the equipment. The legal regulations must be observed during maintenance, e.g. the system owner is responsible for hygienic operation in accordance with VDI 6022.
Maintenance
The circular silencers are low-maintenance in terms of wear, but they must be included in the regular cleaning of the ventilation system. Regular care and maintenance ensure long service life of the circular silencer.
Inspection Measures
- Remove contamination that affects the function of the circular silencer.
- Check all screws for firm seating and retighten them, if necessary.
- Document the maintenance work.
Repair
Repair work is only allowed to be carried out by specialist personnel or by the manufacturer. Only genuine replacement parts must be used.
Disposal
ENVIRONMENT! Risk of harm to the environment due to incorrect disposal of goods and packaging!
Incorrect disposal can harm the environment.
- Be sure to comply with the relevant national guidelines and regulations.
- If you are not sure how to dispose of anything in an environmentally friendly manner, contact your local authorities or a specialist disposal company.
Note: The sound attenuator has to be disassembled for disposal. If no take back (disposal) agreement with TROX GmbH is in place, we recommend disposing of the various materials as described below:
1 Casing, inner duct and spigot
2 Absorption material
No. | Part | Material/waste disposal code | Disposal |
---|---|---|---|
1 | Casing, inner duct and spigot | Plastic EAK 170203 | According to EAK |
2 | Absorption material | Mineral wool EWC European Waste Catalogue | According to EAK 170604 |
File Info : application/pdf, 9 Pages, 340.78KB
DocumentDocumentReferences
AH XSL Formatter V7.2 MR3 for Windows (x64) : 7.2.4.55390 (2022-01-31T09:48 09) Antenna House PDF Output Library 7.2.1732Related Documents
![]() |
TROX CAK Circular Silencer Installation and Maintenance Manual Comprehensive guide for the TROX CAK circular silencer, covering product overview, installation, transport, storage, commissioning, technical data, maintenance, and disposal. Designed for ventilation and air conditioning systems. |
![]() |
TROX Circular Silencer CF: Installation, Technical Data, and Maintenance Manual Comprehensive guide for the TROX Circular Silencer CF, covering installation, operation, technical specifications, dimensions, weights, commissioning, maintenance, and disposal. Includes safety warnings and correct usage guidelines. |
![]() |
TROX VSD50-1-LT Slot Diffuser - Product Overview Detailed information on the TROX VSD50-1-LT, a space-saving slot diffuser with integrated sound attenuation for lightweight partition walls. Features include supply and extract air configurations and technical specifications. |
![]() |
TROX TR2 Ventilation Grille - Technical Data Sheet Detailed technical specifications, dimensions, variants, and performance data for the TROX TR2 ventilation grille, designed for supply and extract air in comfort and industrial zones. |
![]() |
TROX FBK Round Plastic Air Diffusers for Floor Installation - Technical Data and Specifications Detailed technical specifications, features, installation guide, and performance data for TROX FBK round plastic air diffusers designed for installation in raised floors. Includes airflow options, materials, and dimensions. |
![]() |
TROX X-CUBE X2 / X-CUBE X2 compact Air Handling Unit Operating Instructions Official operating instructions for the TROX X-CUBE X2 and X-CUBE X2 compact air handling units, detailing safety procedures, functional descriptions, software operation, maintenance schedules, and troubleshooting guides. |
![]() |
TROX X-CUBE X2 / X-CUBE X2 compact Air Handling Unit: Transport and Installation Manual This comprehensive manual from TROX provides essential guidance for the safe transport, installation, setup, assembly, and initial commissioning of the X-CUBE X2 and X-CUBE X2 compact air handling units. |
![]() |
Trox TS Secondary Silencer Product Data Sheet Product data sheet for the Trox TS secondary silencer, designed for noise reduction in air terminal units. Details specifications, dimensions, materials, and order information for HVAC systems. |