Honeywell STG800 SmartLine Gauge Pressure Transmitter

Technical Information

Specification: 34-ST-03-83, September 2025

Introduction

Part of the SmartLine® family of products, the STG800 and STG80L are high performance gauge pressure transmitters featuring piezoresistive sensor technology combining pressure sensing with on-chip temperature compensation capabilities, providing high accuracy, stability, and performance over a wide range of application pressures and temperatures. The SmartLine family is also fully tested and compliant with Experion® PKS, providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications.

Best in Class Features

Communications/Output Options

All transmitters are available with the above listed communications protocols.

Span & Range Limits

Model URL psi (bar) LRL psi (bar) Min Span psi (bar)
STG830/STG83L 50 (3.5) -14.7 (-1.0) 0.5 (0.035)
STG840/STG84L 500 (35) -14.7 (-1.0) 5 (0.35)
STG870/STG87L 3000 (210) -14.7 (-1.0) 30 (2.1)
STG88L 6000 (420) -14.7 (-1.0) 60 (4.2)
STG89L 10000 (690) -14.7 (-1.0) 100 (6.9)

Figure 1 - STG800 Gauge Pressure Transmitters

Figure 1 - STG800 Gauge Pressure Transmitters feature field-proven piezoresistive sensor technology

Two Honeywell STG800 SmartLine Gauge Pressure Transmitters are depicted. These devices are designed for industrial pressure measurement and feature a display screen and robust construction. The image highlights the core technology: field-proven piezoresistive sensor technology.

Description

The SmartLine family of gauge pressure, differential pressure, and absolute pressure transmitters is designed around a high performance piezo-resistive sensor. This one sensor integrates multiple sensors, linking process pressure measurement with on-board static pressure (DP Models) and temperature compensation measurements, resulting in the best total performance available. This level of performance allows the ST 800 to replace virtually any competitive transmitter available today.

Unique Indication/Display Options

The ST 800 modular design accommodates a standard alphanumeric LCD display or a unique advanced graphics LCD display with many unparalleled features.

Standard LCD Display Features

Advanced Graphics LCD Display Features

Diagnostics

SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events, minimizing unplanned shutdowns and providing lower overall operational costs.

Configuration Tools

Integral Three Button Configuration Option

Suitable for all electrical and environmental requirements, SmartLine offers the ability to configure the transmitter and display via three externally accessible buttons when either display option is selected. Zero/span capabilities are also optionally available via these buttons with or without selection of a display option.

Handheld Configuration

SmartLine transmitters feature two-way communication and configuration capability between the operator and the transmitter. All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any standards-compliant handheld configuration device, such as the Honeywell Versatilis Configurator.

Personal Computer Configuration

On a personal computer or laptop, Honeywell Field Device Manager (FDM) Software and FDM Express can be used for managing HART & Fieldbus device configurations.

System Integration

Modular Design

To help contain maintenance & inventory costs, all ST 800 transmitters are modular in design, supporting the user's ability to replace meter bodies, add indicators, or change electronic modules without affecting overall performance or approval body certifications. Each meter body is uniquely characterized to provide in-tolerance performance over a wide range of application variations in temperature and pressure. Due to the Honeywell advanced interface, electronic modules may be swapped with any electronics module without losing in-tolerance performance characteristics.

Modular Features

* Field replaceable in all electrical environments (including IS) except flameproof without violating agency approvals.

With no performance effects, Honeywell's unique modularity results in lower inventory needs and lower overall operating costs.

Plugged Impulse Line Detection

STG800 models are offered with a PILD option which provides indication of a plugged impulse line or process connection. When used in conjunction with an advanced display, a non-critical diagnostic indication appears on the integral display. For units without an integral display, an indication can be seen via the host or handheld device when HART Protocol is utilized.

Dual/Triple Calibration

STG800 models are optionally offered with multiple calibrations. In lieu of a standard factory calibration, units can be supplied with 1, 2, or 3 customer-specified calibrations. These calibrations are stored in the meter body and provide users with factory-calibrated performance at up to three different calibrated ranges. This increases application flexibility without requiring any costly recalibration or additional inventory.

Performance Specifications

Reference Accuracy (conformance to +/-3 Sigma)

Model URL LRL Min Span Maximum Turndown Ratio Stability (% URL/ Yr for 15 years) Reference Accuracy¹ ² (% Span) Std / Opt.
STG830 50 psi (3.5 bar) -14.7 psi (-1.0 bar) 0.5 psi (.035 bar) 100:1 0.010 0.0375 / 0.025
STG83L 50 psi (3.5 bar) -14.7 psi (-1.0 bar) 0.5 psi (.035 bar)
STG840 500 psi (35 bar) -14.7 psi (-1.0 bar) 5 psi (.35 bar)
STG84L 500 psi (35 bar) -14.7 psi (-1.0 bar) 5 psi (.35 bar)
STG870 3000 psi (210 bar) -14.7 psi (-1.0 bar) 30 psi (2.1 bar) 0.055 / 0.04
STG87L 3000 psi (210 bar) -14.7 psi (-1.0 bar) 30 psi (2.1 bar)
STG88L 6000 psi (420 bar) -14.7 psi (-1.0 bar) 60 psi (4.2 bar)
STG89L 10000 psi (690 bar) -14.7 psi (-1.0 bar) 100 psi (6.9 bar)

Zero and span may be set anywhere within the listed (URL/LRL) range limits.

Accuracy at Specified Span and Temperature (Conformance to +/-3 Sigma)

Model URL Reference Turndown Accuracy¹ ² (% of Span) Combined Zero & Span Temperature Effect (% Span/28°C (50°F))
A B C (see URL units) D E
Standard Accuracy
STG830 50 psi (3.5 bar) 33.3:1 0.005 0.0325 1.5 (0.105) 0.030 0.003
STG83L 50 psi (3.5 bar) 16.7:1 0.005 0.0325 3 (0.21) 0.030 0.006
STG840 500 psi (35 bar) 35:1 0.005 0.0325 14.5 (1.0) 0.025 0.004
STG84L 500 psi (35 bar) 35:1 0.005 0.0200 14.5 (1.0) 0.025 0.007
STG870 3000 psi (210 bar) 10:1 0.015 0.0400 300 (21) 0.025 0.005
STG87L 3000 psi (210 bar) 10:1 0.015 0.0400 300 (21) 0.025 0.005
STG88L 6000 psi (420 bar) 12:1 0.015 0.0400 500 (35) 0.010 0.010
STG89L 10000 psi (690 bar) 10:1 0.015 0.0250 1000 (69) 0.010 0.010
High Accuracy Option
STG830 50 psi (3.5 bar) 33.3:1 0.005 0.0325 1.5 (0.105) 0.030 0.003
STG83L 50 psi (3.5 bar) 16.7:1 0.005 0.0325 3 (0.21) 0.030 0.006
STG840 500 psi (35 bar) 35:1 0.005 0.0325 14.5 (1.0) 0.025 0.004
STG84L 500 psi (35 bar) 35:1 0.005 0.0200 14.5 (1.0) 0.025 0.007
STG870 3000 psi (210 bar) 10:1 0.015 0.0400 300 (21) 0.025 0.005
STG87L 3000 psi (210 bar) 10:1 0.015 0.0400 300 (21) 0.025 0.005
STG88L 6000 psi (420 bar) 12:1 0.015 0.0400 500 (35) 0.010 0.010
STG89L 10000 psi (690 bar) 10:1 0.015 0.0250 1000 (69) 0.010 0.010

Turn Down Effect: ±[A+B] if Span ≥ C; ±[A+B(Span)] if Span < C

Temp Effect: ±[D+E(URL/Span)]

Total Performance

Total Performance Calculation: = ±√(Accuracy)² + (Temperature Effect)²

Total Performance Examples (for comparison): Standard accuracy 5:1 Turndown, ±50°F (28°C) shift

Typical Calibration Frequency

Calibration verification is recommended every four (4) years.

Notes:

Operating Conditions – All Models

Parameter Reference Condition Rated Condition Operative Limits Transportation and Storage
°C °F °C °F °C °F °C °F
Ambient Temperature¹ 25±1 77±2 -40 to 85 -40 to 185 -40 to 85 -40 to 185 -55 to 120 -67 to 248
Meter Body Temperature² 25±1 77±2 -40 to 110¹ -40 to 230¹ -40 to 125 -40 to 257 -55 to 120 -67 to 248
Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100
Vac. Region – Min. Pressure mmHg absolute Atmospheric 25 2 (short term)³ 1 (short term)³
inH₂O absolute Atmospheric 13
Supply Voltage Load Resistance
HART: 10.8 to 42.4 VDC at terminals (IS versions limited to 30 VDC), 0 to 1,440 ohms
DE: 15 to 49.3VDC at terminals (IS versions limited to 30VDC), 0 to 1,200 ohms (as shown in Figure 2)
FOUNDATION Fieldbus: 9.0 to 32.0 VDC at terminals, steady state current: 17.6mA, software download current: 27.4mA
Maximum Allowable Working Pressure (MAWP)⁴
(Maximum allowable working pressure is the maximum pressure allowed for the normal transmitter operation. MAWP depends on Approval agencies and transmitter material of construction. MAWP are same as URL for gauge and absolute pressure transmitters)
STG830: 50 psi (3.5 bar) STG83L: 50 psi (3.5 bar)
STG840: 500 psi (35 bar) STG84L: 500 psi (35 bar)
STG870: 3000 psi (210 bar) STG87L: 3000 psi (210 bar)
STG88L: 6000 psi (420 bar) STG89L: 10000 psi (690 bar)
Over pressure
These are the pressure limits the transmitters can withstand without damage
STG830: 75 psi (5.25 bar) STG83L: 75 psi (5.25 bar)
STG840: 1500 psi (103 bar) STG84L: 1500 psi (103 bar)
STG870: 4500 psi (310 bar) STG87L: 4500 psi (310 bar)
STG88L: 9000 psi (620 bar) STG89L: 15000 psi (1035 bar)

¹ LCD Display operating temperature -20°C to +70°C. Storage temperature -30°C to 80°C.

² Silicone 704 minimum temperature rating is 0°C (32°F). CTFE minimum temperature rating is -40°C (-40°F). NEOBEE M-20 minimum temperature rating is -15°C (5°F). NEOBEE® is a registered trademark of Stepan Company.

³ Short term equals 2 hours at 70°C (158°F).

⁴ Consult factory for MAWP of ST 800 transmitters with CRN approval.

Figure 2 - Supply voltage and loop resistance chart & calculations

Figure 2 - Supply voltage and loop resistance chart & calculations

This figure illustrates the relationship between operating voltage (VDC) and loop resistance (ohms) for HART and DE communication protocols. It includes formulas for calculating maximum loop resistance (RLmax) for both protocols, based on supply voltage. A minimum of 250 ohms loop resistance is required to support a field communicator.

Performance Under Rated Conditions – All Models

Parameter Description
Analog Output Two-wire, 4 to 20 mA (HART & DE Transmitters only)
Digital Communications: Honeywell DE, HART protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant. All transmitters, irrespective of protocol, have polarity insensitive connection.
HART & DE Output Failure Modes
(NAMUR for DE Units requires selecting display and configuration buttons or factory configuration)
Normal Limits: Honeywell Standard: 3.8–20.8 mA; NAMUR NE 43 Compliance: 3.8–20.5 mA
Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA
Supply Voltage Effect 0.005% span per volt
Transmitter Turn on Time (includes power up & test algorithms) HART or DE: 2.5 seconds; Foundation Fieldbus: host dependent
Response Time (delay + time constant) DE/HART Protocol: 80ms; FOUNDATION Fieldbus: 150ms (Host Dependent)
Damping Time Constant HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default Value: 0.5 seconds
DE: Discrete values 0, 0.16, 0.32, 0.48, 1, 2, 4, 8, 16, 32 seconds. Default Value: 0.48 seconds
Vibration Effect Less than +/- 0.1% of URL w/o damping. Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz: 0.21 displacement/3g max acceleration)
Electromagnetic Compatibility Complies with EMC directive 2004/108/EC per IEC 61326-3-1 (HART/ DE Units) IEC 61326-1 (FF Units)
Lightning Protection Option Leakage Current: 10uA max @ 42.4VDC 93C
Impulse rating: 8/20us: 5000A (>10 strikes) 10000A (1 strike min.)
10/1000us: 200A (> 300 strikes)

Materials Specifications

(See model selection guide for availability/restrictions with various models)

Parameter Description
Barrier Diaphragms Material STG800: 316L SS, Hastelloy® C-276², Monel® 400³, Tantalum, Gold-plated 316L SS, Gold-plated Hastelloy® C-276, Gold-plated Monel® 400
STG80L: 316L SS, Hastelloy C-276
Process Head Material STG800: Carbon Steel (Zinc Plated), 316 SS⁴, Hastelloy® C-276⁶, Monel® 400⁷
STG80L: 316L SS, Hastelloy C-276⁶
Vent/Drain Valves & Plugs ¹ STG800:316 SS⁴, Hastelloy C-276², Monel 400⁷
STG80L: N/A
Head Gaskets STG800: Glass-filled PTFE standard. Viton® and graphite are optional. STG80L: N/A
Meter Body Bolting STG800: Carbon Steel (Zinc plated) standard. Options include 316 SS, NACE A286 SS bolts and nuts or NACE A286 SS bolts and 304 SS nuts STG80L: N/A
Mounting Bracket Carbon Steel (Zinc-plated) or 304 SS or 316SS angle bracket or Carbon Steel or 304SS or 316SS flat bracket available with 2" pipe bracket. See Figure 3.
Fill Fluid Silicone 200, CTFE, NEOBEE M-20 or Silicone 704
Electronic Housing Pure Polyester Powder Coated Low Copper (<0.4%) – Aluminum. Meets Type 4X / IP66 / IP67. All stainless-steel housing is optional. Cover O ring material: Silicone.
Process Connections STG800: ½-inch NPT female, DIN 19213 (standard)
STG80L: ½-inch NPT female, ½-inch NPT male, 9/16-18 high-pressure Cone and Thread female⁸, DIN19213 (except STG89L), G ½-B Male threaded
Wiring Accepts up to 16 AWG (1.5 mm diameter).
Dimensions See Figure 4 and 5
Net Weight STG800: 8.3 pounds (3.8 Kg). STG80L: 3.6 pounds (1.6 Kg) with Aluminum Housing

¹ Vent/Drains are sealed with Teflon®

² Hastelloy® C-276 or UNS N10276.

³ Monel® 400 or UNS N04400.

⁴ Supplied as 316 SS or as Grade CF8M, the casting equivalent of 316 SS.

⁵ Carbon Steel heads are zinc-plated and not recommended for water service due to hydrogen migration. For that service, use 316 stainless steel wetted Process Heads.

⁶ Hastelloy® C-276 or UNS N10276. Supplied as indicated or as Grade CW12MW, the casting equivalent of Hastelloy® C-276.

⁷ Monel® 400 or UNS N04400. Supplied as indicated or as Grade M30C, the casting equivalent of Monel® 400.

⁸ 9/16 Aminco.

Communications Protocol & Diagnostics

HART Protocol

Version: HART 7

Foundation Fieldbus (FF)

Available Function Blocks

Block Type Quantity Execution Time
Resource 1 n/a
Transducer 1 n/a
Diagnostic 1 n/a
Analog Input 1* 30 ms
PID w/Autotune 1 45 ms
Integrator 1 30 ms
Signal Char (SC) 1 30 ms
LCD Display 1 n/a
Flow Block 1 30 ms
Input Selector 1 30 ms
Arithmetic 1 30 ms

* AI block may have two (2) additional instantiations.

All available function blocks adhere to FOUNDATION Fieldbus standards. PID blocks support ideal & robust PID algorithms with full implementation of Auto-tuning.

Link Active Scheduler

Transmitters can perform as a backup Link Active Scheduler and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus.

Number of Devices/Segment: Entity IS model: 6 devices/segment

Schedule Entries: 18 maximum schedule entries

Number of VCR's: 24 max

Compliance Testing: Tested according to ITK 6.0.1

Software Download: Utilizes Class-3 of the Common Software Download procedure as per FF-883 which allows the field devices of any manufacturer to receive software upgrades from any host.

Honeywell Digitally Enhanced (DE)

DE is a Honeywell proprietary protocol which provides digital communications between Honeywell DE enabled field devices and Hosts.

Standard Diagnostics

ST 800 top-level diagnostics are reported as either critical or non-critical and are readable via the DD/DTM/FDI tools or integral display. All critical diagnostics will appear on the Advanced and Standard integral displays, and some non-critical diagnostics will also appear on the Advanced integral display. Some of the diagnostics are listed below.

Critical Diagnostics

Non-Critical Diagnostics

Refer to the product user manual for comprehensive list of diagnostics and details.

Other Certification Options

Materials

Hazardous Area Certifications

MSG CODE AGENCY TYPE OF PROTECTION COMM. OPTION ELECTRICAL PARAMETERS AMBIENT TEMP (Ta)
A FM Approvals™ USA Explosionproof:
Class I, Division 1, Groups A, B, C, D;
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T6..T5
Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb
Class II, Zone 21, AEx tb IIIC T95° Db
All Note 1 T5: -50 °C to 85°C
T6: -50 °C to 65°C
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G: T4
Class I, Zone 0, AEx ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART Note 2a -50 °C to 70°C
Nonincendive:
Class I, Division 2, Groups A, B, C, D locations, T4
Class I, Zone 2, AEx nA IIC T4 Gc
4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50 °C to 85°C
Enclosure: Type 4X/ IP66/ IP67 All All -
STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM Class 3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013; ANSI/UL 60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL 60079-26: 2017; ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/IEC 60529: 2004
B Canadian Standards Association (CSA) USA and Canada Explosion Proof:
Class I, Division 1, Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1, T6..T5
Class I Zone 1 AEx db IIC T6..T5 Ga/Gb
Ex db IIC T6..T5 Ga/Gb
Zone 22 AEx tb IIIC T95° Db
Ex tb IIIC T95° Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C, D;
Class II, Division 1, Groups E, F, G;
Class III, Division 1, T4
Class I Zone 0, AEx ia IIC T4 Ga
Class I Zone 2, AEx ic IIC T4 Gc
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga;
Ex ic IIC T4 Gc
4-20 mA / DE/ HART Note 2 -50°C TO 70°C
Foundation Fieldbus Note 2 -50°C TO 70°C
Nonincendive:
Class I, Division 2, Groups A, B, C, D;
Class II, Division 2, Groups F, G;
Class III, Division 2, T4
Class I Zone 2 AEx nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50°C to 85°C
STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966; CSA C22.2 No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA C22.2 No. 213-M1987; CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-C22.2 No. 60079-1:11; CSA-C22.2 No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-C22.2 No. 60079-31:12; ISA 12.12.01-2010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA 60079-15: 2009; ISA 60079-26: 2008; ISA-60079-27:2007 (12.02.04)-2006 (R2011); UL 913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011
C ATEX Flameproof: SIRA 12ATEX2233X
II 1/2 G Ex db IIC T6..T5 Ga/Gb
II 2 D Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe: SIRA 12ATEX2233X
II 1 G Ex ia IIC T4 Ga
II 2 D Ex ia IIIC T125°C Db
FISCO Field Device (Only for FF Option)
II 1 G Ex ia IIC T4 Ga
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety: SIRA 12ATEX4234X
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe: SIRA 12ATEX4234X
II 3 G Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
II 3 G Ex ic IIC T4 Gc
Enclosure: IP66/ IP67
4-20 mA / DE/ HART/ Foundation Fieldbus
All
Note 2
All
-50°C TO 85°C
-
STANDARDS: EN 60079-0: 2018; EN 60079-1: 2014; EN 60079-7: 2015+A1:2018; EN 60079-11: 2012; EN 60079-26: 2015; EN 60079-31: 2014
C UKEX Flameproof: CSAE 22UKEX1021X
II 1/2 G Ex db IIC T6..T5 Ga/Gb
II 2 D Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe: CSAE 22UKEX1021X
II 1 G Ex ia IIC T4 Ga
II 2 D Ex ia IIIC T125°C Db
FISCO Field Device (Only for FF Option)
II 1 G Ex ia IIC T4 Ga
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety: CSAE 22UKEX1008X
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe: CSAE 22UKEX1008X
II 3 G Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
II 3 G Ex ic IIC T4 Gc
4-20 mA / DE/ HART/ Foundation Fieldbus Note 2 -50°C TO 85°C
STANDARDS: EN 60079-0: 2018; EN 60079-1: 2014; EN 60079-7: 2015+A1:2018; EN 60079-11: 2012; EN 60079-26: 2015; EN 60079-31: 2014
D IECEx World Flameproof: IECEx SIR 12.0100X
Ex db IIC T6..T5 Ga/Gb
Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe: IECEx SIR 12.0100X
Ex ia IIC T4 Ga
Ex ia IIIC T125°C Db
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety: IECEX SIR 12.0100X
Ex ec IIC T4 Gc
4-20 mA / DE/ HART/ Foundation Fieldbus Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe: IECEX SIR 12.0100X
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ic IIC T4 Gc
Enclosure: IP66/ IP67
4-20 mA / DE/ HART/ Foundation Fieldbus
All
Note 2
All
-50°C TO 85°C
-
STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014; IEC 60079-7: 2017; IEC 60079-11: 2011; IEC 60079-26: 2014; IEC 60079-31: 2013
E SAEX South Africa Flameproof:
Ex d IIC T6...T5 Ga/Gb
Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Ex ia IIC Ga T4
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety:
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/ HART/
Foundation Fieldbus
Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe:
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ic IIC T4 Gc
Enclosure: IP66/ IP67
4-20 mA / DE/ HART/
Foundation Fieldbus
All
Note 2
All
-50°C TO 85°C
-
F INMETRO Brazil Flameproof:
Ex db IIC T6..T5 Ga/Gb
Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2a
Note 2b
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety:
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/ HART/
Foundation Fieldbus
Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe:
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ic IIC T4 Gc
Enclosure : IP 66/67
4-20 mA / DE/ HART/
Foundation Fieldbus
All
Note 2
All
-50°C TO 85°C
-
G NEPSI CHINA Flameproof:
Ex db IIC T6..T5 Ga/Gb
Ex tb IIIC T 95°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Increase Safety:
II 3 G Ex ec IIC T4 Gc
4-20 mA / DE/ HART/
Foundation Fieldbus
Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe:
Ex ic IIC T4 Gc
FISCO Field Device (Only for FF Option)
Ex ic IIC T4 Gc
Enclosure : IP 66/67
4-20 mA / DE/ HART/
Foundation Fieldbus
All
Note 2
All
-50°C TO 85°C
-
H KOSHA Korea Flameproof :
Ex d IIC T4, T5, T6
Ex tD A21 IP66/IP67 T95°C...T120 °C
All Note 1 T4: -50°C TO 85°C
T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Ex ia IIC T4
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
Ta= -50 °C to 70°C
Ta= -50 °C to 70°C
Enclosure: IP66/ IP67 All All -
Flameproof:
Ga/Gb Ex d IIC T6..T5
Ex tb IIIC Db T 85°C
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
I EAC Russia, Belarus and Kazakhstan Intrinsically Safe:
Ga Ex ia IIC T4 X
FISCO Field Device (Only for FF Option)
Ga Ex ia IIC T4 X
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Zone 2, Non Sparking:
2 Ex nA IIC T4 Gc X
4-20 mA / DE/HART/
Foundation Fieldbus
Note 1 -50°C TO 85°C
Zone 2, Intrinsically Safe:
Ga Ex ic IIC T4 X
FISCO Field Device (Only for FF Option)
2 Ex ic IIC T4 Gc X
4-20 mA / DE/HART/
Foundation Fieldbus
Note 2 -50°C TO 85°C
Enclosure : IP 66/67 All All -
J CCoE INDIA Flameproof:
Ex d IIC T6..T5 Ga/Gb
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
Ex ia IIC T4 Ga; Ex ic IIC T4 Gc
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Non Sparking
Ex nA IIC T4 Gc
4-20 mA / DE/
HART/
Foundation Fieldbus
Note 1 -50°C TO 85°C
Enclosure: IP66/ IP67 All All -
K UATR UKRAINE Flameproof:
II 1/2 G Ex db IIC T6..T5 Ga/Gb
II 2 D Ex tb IIIC T95°C...T120°C Db
All Note 1 T5: -50°C TO 85°C
T6: -50°C TO 65°C
Intrinsically Safe:
II 1 G Ex ia IIC T4 Ga
FISCO Field Device (Only for FF Option)
II 1 G Ex ia IIC T4 Ga
4-20 mA / DE/ HART
Foundation Fieldbus
Note 2
Note 2
-50°C TO 70°C
-50°C TO 70°C
Enclosure: IP66/ IP67 All All -

Notes & Approval Certifications

Notes

  1. Operating Parameters:
    Voltage = 11 to 42 VDC
    = 9 to 32 V (FF)
    Current = 4-20 mA Normal
    = 30 mA (FF)
  2. Intrinsically Safe Entity Parameters

a. Analog/DE/HART Entity Values:

ParameterValueCiLiPi
Vmax = Ui = 30VImax = Ii = 105mA4.2nF984 uH0.9W
Transmitter with Terminal Block revision E or Later
Vmax = Ui = 30VImax= Ii = 225mA4.2nF00.9W

Note: Transmitter with Terminal Block revision E or later. The revision is on the label that is on the module. There will be two lines of text on the label: First is the Module Part #: 50049839-001 or 50049839-002. Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION.

b. Foundation Fieldbus Entity Values

ParameterValueCiLiPi
Vmax = Ui = 30VImax = Ii = 180mA0nF984 uH1W
Transmitter with Terminal Block revision F or Later
Vmax = Ui = 30VImax = Ii = 225mA0nF01 W

FISCO Field Device

ParameterValueCiLiPi
Vmax = Ui = 17.5VImax = Ii = 380 mA0nF05.32 W

Note: Transmitter with Terminal Block revision F or later. The revision is on the label that is on the module. There will be two lines of text on the label: First is the Module Part #: 50049839-003 or 50049839-004. Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION.

Approval Certifications

This certificate defines the certifications covered for the ST 800 Pressure Transmitter family of products, including the SMV 800 Smart Multivariable Transmitter. It represents the compilation of the five certificates Honeywell currently has covering the certification of these products into marine applications.

For ST 800 Smart Pressure Transmitter and SMV800 Smart Multivarible Transmitter

Marine Certificates

SIL 2/3 Certification

IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.

MEASUREMENT INSTRUMENTS DIRECTIVE (MID) 2004/22/EC

Certificate Issued by NMI Certin B.V.

Mechanical Class: M3

Electromagnetic Environment: E3

Ambient Temperature Range: -25 °C to + 55 °C

UnitCustom Calibration
STD8200 to 1000 mBar
STD8300 to 7 Bar
STA84L0 to 35 Bar A
STG84L0 to 35 Bar
STD8700 to 100 Bar
STA87L0 to 100 Bar A
STG87L0 to 100 Bar

Dimensional Drawings

Figure 3 - Typical mounting configuration of dual head and inline designs

Figure 3 - Typical mounting configuration of dual head and inline designs for reference

Diagrams illustrating various mounting configurations for the STG800 transmitters, showing both dual head and inline designs attached to piping systems.

Figure 4 - Typical mounting dimensions of STG840 & STG870

Figure 4 - Typical mounting dimensions of STG840 & STG870 for reference

Dimensional drawings for the STG840 and STG870 models in a dual head design. The drawings provide detailed measurements in millimeters and inches for various components and orientations, including conduit connections, vent/drain ports, and overall dimensions with and without optional displays.

Figure 5 - Typical mounting dimensions of STG84L, STG87L, STG88L, & STG89L

Figure 5 - Typical mounting dimensions of STG84L, STG87L, STG88L, & STG89L for reference

Dimensional drawings for the STG84L, STG87L, STG88L, and STG89L models in an inline design. The drawings provide detailed measurements in millimeters and inches for various components and orientations, including conduit connections, pressure connections, vent/drain ports, and overall dimensions with and without optional displays.

Model Selection Guide

Model Selection Guides are subject to change and are inserted into the specifications as guidance only.

Model STG800 Gauge Pressure Transmitters

Model Selection Guide: 34-ST-16-83 | Issue: 34

Instructions: Make selections from all Tables using column below the proper arrow. Asterisk indicates availability. Letter (a) refers to restrictions highlighted in the restrictions table. Tables delimited with dashes. List Price: Price equals the sum of prices for all selections made.

Key Number Table

KEY NUMBER URL/Max Span LRL Min Span Units Selection Availability
Gauge Dual Head50 (3.5)-14.7 (-1.0)0.5 (.035)psi (bar)STG830
500 (35)-14.7 (-1.0)5 (.35)psi (bar)STG840
3000 (210)-14.7 (-1.0)30 (2.1)psi (bar)STG870
Gauge In-Line50 (3.5)-14.7 (-1.0)0.5 (.035)psi (bar)STG83L
500 (35)-14.7 (-1.0)5 (.35)psi (bar)STG84L
3000 (210)-14.7 (-1.0)30(2.1)psi (bar)STG87L
6000 (420)-14.7 (-1.0)60 (4.2)psi (bar)STG88L
10000 (690)-14.7 (-1.0)100 (6.9)psi (bar)STG89L

TABLE I: METER BODY SELECTIONS

Process Head/Reference Head Material¹ᵇBarrier Diaphragm Material
a. Process Head & Diaphragm Materials316L SS316L SSABCD12
Hastelloy C - 276Hastelloy C - 276
Monel 400®Monel 400®
Plated Carbon Steel / Plated Carbon SteelTantalum
316 Stainless Steel /316 Stainless Steel¹ᶜGold Plated 316L SS
Gold Plated Hastelloy C-276
Gold Plated Monel 400
Hastelloy C-276316L SS
Hastelloy C-276 / 316 Stainless SteelHastelloy C - 276
Monel 400 / 316 Stainless SteelMonel 400
b. Fill FluidSilicone Oil 200Tantalum345678
Fluorinated Oil CTFEGold Plated Hastelloy C-276
Silicone Oil 704Gold Plated Monel 400
NEOBEE® M-20Hastelloy C-276
Gold Plated Monel 400
c. Process ConnectionSize/TypeMaterial
9/16-18 high pressure Cone & Thread (female)¹ᵈSame as Process HeadAGHDBN
1/2" NPT (female)Same as Process Head ¹ᵃ0CSNKM
1/2" NPT (male)Same as Process HeadD
DIN 19213 (1/4" female NPT)Same as Process HeadB
G ½ B Threaded FittingSame as Process Head
d. Bolt/Nuts MaterialsM20
NoneCarbon Steel
316 SS316 SS
Grade 660 (NACE A286) with NACE 304 SS NutsGrade 660 (NACE A286) Bolts & Nuts
Monel K500Monel K500
Super DuplexSuper Duplex
B7M
e. Vent/Drain Type/LocationHead TypeVent TypeLocationVent Material
NoneNoneNoneNone0
Single EndedStandard VentSideMatches Head Material¹1
Single EndedCenter VentSideStainless Steel Only2t
Dual EndedStandard VentEndMatches Head Material¹3t
Dual EndedCenter VentEndStainless Steel only4
Dual EndedStd Vent/PlugSide/EndMatches Head Material¹5
None6
f. Gasket MaterialsTeflon® or PTFE (Glass Filled)OABC
Viton
Graphite

¹ Except Carbon Steel Heads shall use 316SS Vent/Drain & Plugs and or 1/2" adapters

¹ᵃ STG830,840,870 supplied via 1/2" flange adapter same material as process head except carbon steel shall use 316 SS

¹ᵇ Reference head available with Dual Head Gage models only. In-Line Gage models are supplied with Process Head only.

¹ᶜ When selected for In-Line Gage models the Process Head / Bonnet is supplied in Dual Certified SS316/316L

¹ᵈ 9/16" Aminco

TABLE II: METER BODY & CONNECTION ORIENTATION

Head/Connect Orientation
StandardHigh Side Left, Low Side Right² / Std Head Orientation
ReversedLow Side Left, High Side Right² / Std Head Orientation
90/StandardHigh Side Left, Low Side Right² / 90° Head Rotation

TABLE III: AGENCY APPROVALS

Approvals
No Approvals Required0
<FM> Explosion proof, Intrinsically Safe, Non-incendive, & DustproofA
CSA Explosion proof, Intrinsically Safe, Non-incendive, & DustproofB
ATEX Explosion proof, Intrinsically Safe & Non-incendiveC
IECEx Explosion proof, Intrinsically Safe & Non-incendiveD
SAEx Explosion proof, Intrinsically Safe & Non-incendiveE
INMETRO Explosion proof, Intrinsically Safe & Non-incendiveF
NEPSI Explosion proof, Intrinsically Safe & Non-incendiveG
KOSHA Explosion proof, Intrinsically Safe & Non-incendiveH
EAC Customs Union (Russia, Belarus, Kazakhstan)Ex Approval, Flame proof, Intrinsically SafeI
CCoE Explosion proof, Intrinsically Safe & Non-incendiveJ
UATR Flameproof, Intrinsically Safe & DustproofK

TABLE IV: TRANSMITTER ELECTRONICS SELECTIONS

a. Electronic Housing Material & Connection TypeMaterialConnectionLightning Protection
Polyester Powder Coated Aluminum1/2 NPTNoneA
Polyester Powder Coated AluminumM20NoneB
Polyester Powder Coated Aluminum1/2 NPTYesC
Polyester Powder Coated AluminumM20YesD
Dual Certified SS 316/316L (CF8M/CF3M)1/2 NPTNoneE
Dual Certified SS 316/316L (CF8M/CF3M)M20NoneF
Dual Certified SS 316/316L (CF8M/CF3M)1/2 NPTYesG
Dual Certified SS 316/316L (CF8M/CF3M)M20YesH
b. Output/ ProtocolAnalog OutputDigital Protocol
4-20mA dcHART Protocol0
4-20mA dcDE ProtocolA
Foundation Fieldbusu
c. Customer Interface SelectionsIndicatorExt Zero, Span & Config ButtonsLanguages
NoneNoneNone0
NoneYes (Zero/Span Only)NoneA
AdvancedNoneEN, GR, FR, IT, SP, RU, TUD
AdvancedYesEN, GR, FR, IT, SP, RU, TUE
AdvancedNoneEN, CH, JPH
AdvancedYesEN, CH, JPJ
Standard (w/internal Zero, Span & Conf Buttons)NoneEN, RUS
Standard (w/internal Zero, Span & Conf Buttons)YesEN, RUT

TABLE V: CONFIGURATION SELECTIONS

a. Application SoftwareDiagnostics
Standard DiagnosticsAdvanced Diagnostics (Above with Plugged Impulse Detection PILD)1__
2
b. Output Limit, Failsafe & Write Protect SettingsHigh & Low Output Limits³
DisabledHigh> 21.0mAdcHoneywell Std (3.8 - 20.8 mAdc)1_
EnabledLow< 3.6mAdcHoneywell Std (3.8 - 20.8 mAdc)2_
DisabledHigh> 21.0mAdcHoneywell Std (3.8 - 20.8 mAdc)3
EnabledLow< 3.6mAdcHoneywell Std (3.8 - 20.8 mAdc)4
EnabledN/AFieldbus or Profibus5_
DisabledN/AFieldbus or Profibus6
c. General Configuration
Factory StandardS
Custom Configuration (Unit Data Required from customer)C

² Left side/Right side as viewed from the customer connection perspective

³ NAMUR Output Limits are configurable by customer

TABLE VI: CALIBRATION & ACCURACY SELECTIONS

AccuracyCalibrated RangeCalibration Qty
StandardFactory StandardSingle CalibrationA
StandardCustom (Unit Data Required)Single CalibrationB
StandardCustom (Unit Data Required)Dual CalibrationC
StandardCustom (Unit Data Required)Triple CalibrationD
High AccuracyFactory StandardSingle CalibrationE
High AccuracyCustom (Unit Data Required)Single CalibrationF
High AccuracyCustom (Unit Data Required)Dual CalibrationG
High AccuracyCustom (Unit Data Required)Triple CalibrationH

TABLE VII: ACCESSORY SELECTIONS

a. Mounting BracketBracket TypeMaterial
NoneNone0
Angle BracketCarbon Steel1
Angle Bracket304 SS2
Angle Bracket316 SS3
Marine Approved BracketCarbon Steel8
Marine Approved Bracket (In-Line)Carbon Steel9
Marine Approved Bracket304 SS4
Marine Approved Bracket (In-Line)304 SSA
Flat BracketCarbon Steel5
Flat Bracket304 SS6
Flat Bracket316 SS7
b. Customer TagCustomer Tag Type
No customer tag*
One Wired Stainless Steel Tag (Up to 4 lines 26 char/line)2
Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line)
c. Unassembled Conduit Plugs & Adapters
No Conduit Plugs or Adapters Required
1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit AdapterA0
1/2 NPT 316 SS Certified Conduit PlugA2
M20 316 SS Certified Conduit PlugA6
Minifast® 4 pin (1/2 NPT) (not suitable for X-Proof applications)A7
Minifast® 4 pin (M20) (not suitable for X-Proof applications)A8

TABLE VIII: OTHER Certifications & Options: (String in sequence comma delimited (XX, XX, XX,....)

No additional options00******
Low Temperature Rating (-50 deg C min. ambient operative temperature limit)LTwwwwww
NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts onlyFG*c*c*c
NACE MR0175; MR0103; ISO15156 (FC33339) Process wetted and non-wetted partsF7*c*c*c
Marine (DNV, ABS, BV, KR, LR)MTdddddd
EN10204 Type 3.1 Material Traceability (FC33341)FX******
MID Approved Transmitter - Contact Tech Support for specific MID approved rangesMD******
Certificate of Conformance (F3391)F3******
Calibration Test Report & Certificate of Conformance (F3399)F1******
Certificate of Origin (F0195)F5******
FMEDA (SIL 2/3) Certification (FC33337)FEjjjjjj
Over-Pressure Leak Test Certificate (1.5X MAWP) (F3392) for Transmitter OnlyTP******
Cert Clean for O2 or CL2 service per ASTM G93OXeeeeee
PMI Certification¹PM******
Extended Warranty Additional 1 year for Transmitter Only01******
Extended Warranty Additional 2 years for Transmitter Only02******
Extended Warranty Additional 3 years for Transmitter Only03******
Extended Warranty Additional 4 years for Transmitter Only04******
Extended Warranty Additional 15 years for Transmitter Only15******

¹The PM option is available on all Smartline Pressure Transmitter process wetted parts such as process heads, flanges, bushings and vent plugs except plated carbon steel process heads and flanges. PM option information is also available on diaphragms except Gold plated and STG and STA in-line construction pressure transmitters.

TABLE IX: Factory Identification

FactoryManufacturing Specials
Factory Identification0000******

Field Installable Accessory Kits

Note P - For part number pricing please refer to WEB Channel

Product Manuals

All product documentation is available at www.honeywellprocess.com.

Sales and Service

For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor, contact one of the offices below.

ASIA PACIFIC

Honeywell Process Solutions,
Phone: + 800 12026455 or +44 (0) 1202645583
(TAC) hfs-tac-support@honeywell.com

Australia

Honeywell Limited
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36
Toll Free Fax:
1300-36-04-70

China - PRC - Shanghai

Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826

Singapore

Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033

South Korea

Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015

EMEA

Honeywell Process Solutions,
Phone: + 800 12026455 or +44 (0) 1202645583
Email: (Sales) FP-Sales-Apps@Honeywell.com
or (TAC)
hfs-tac-support@honeywell.com

Web
Knowledge Base search engine http://bit.ly/2N5Vldi

AMERICAS

Honeywell Process Solutions,
Phone: (TAC) (800) 423-9883 or (215) 641-3610
(Sales) 1-800-343-0228
Email: (Sales) FP-Sales-Apps@Honeywell.com
or (TAC)
hfs-tac-support@honeywell.com

Web
Knowledge Base search engine http://bit.ly/2N5Vldi

Specifications are subject to change without notice.

For more information

To learn more about SmartLine Transmitters, visit www.process.honeywell.com
Or contact your Honeywell Account Manager

Process Solutions

Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042

Honeywell Control Systems Ltd

Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB

Shanghai City Centre, 100 Jungi Road

Shanghai, China 20061

www.process.honeywell.com

34-ST-03-83
September 2025
©2025 Honeywell International Inc.

PDF preview unavailable. Download the PDF instead.

hon-ia-stg800-smartline-gauge-pressure-technical-specification-34-st-03-83-sep-2025 Honeywell Internatinal Inc. Adobe PDF Library 20.5.73

Related Documents

Preview Honeywell STA700 SmartLine Absolute Pressure Transmitters Technical Specification
Detailed technical specifications for Honeywell's STA700 SmartLine Absolute Pressure Transmitters, covering features, performance, operating conditions, materials, and hazardous area certifications.
Preview Honeywell STA700 SmartLine Absolute Pressure Transmitter Technical Specification
Detailed technical specifications for the Honeywell STA700 SmartLine Absolute Pressure Transmitter, covering features, performance, operating conditions, and hazardous area certifications for industrial applications.
Preview Honeywell ST 700 SmartLine Pressure Transmitters User's Manual
This comprehensive user's manual provides detailed instructions for the Honeywell ST 700 SmartLine pressure transmitters, covering installation, configuration, operation, maintenance, and troubleshooting for industrial process applications.
Preview Honeywell ST 3000 Smart Transmitter: Specification and Model Selection Guide
A comprehensive guide detailing the specifications, features, operating conditions, performance data, physical characteristics, approval bodies, options, and model selection process for the Honeywell ST 3000 Series 100 Differential Pressure Transmitters.
Preview Honeywell ST 800/ST 700 SmartLine 压力变送器快速安装指南
获取 Honeywell ST 800 和 ST 700 SmartLine 压力变送器的详细快速安装说明和步骤。本指南涵盖安装、接线、配置和安全认证,帮助用户高效部署这些高性能压力变送器。
Preview ST 800 & ST 700 SmartLine Transmitter Safety Manual
This safety manual provides essential information for the Honeywell ST 800 and ST 700 SmartLine Transmitters with HART® Communications Options. It covers requirements, safety functions, design considerations, installation, operation, maintenance, and security guidelines.
Preview Honeywell SLG700 Level Transmitter: Replacing GWR Sensor Electronics
Instruction sheet detailing the process for replacing GWR Sensor Electronics in Honeywell SLG700 Level Transmitters, including safety precautions, required tools, and step-by-step assembly instructions.
Preview Honeywell FEMA Smart SN Electronic Pressure Transmitter Product Data
Comprehensive product data for the Honeywell FEMA Smart SN series of electronic pressure transmitters, detailing features, technical specifications, mounting, electrical connections, and operational parameters.