Introduction
Part of the SmartLine® family of products, the STG800 and STG80L are high performance gauge pressure transmitters featuring piezoresistive sensor technology combining pressure sensing with on-chip temperature compensation capabilities, providing high accuracy, stability, and performance over a wide range of application pressures and temperatures. The SmartLine family is also fully tested and compliant with Experion® PKS, providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications.
Best in Class Features
- Accuracies up to 0.0375% of span standard & 0.025% of span optional.
- Stability up to 0.015% of URL per year for 15 years.
- Automatic temperature compensation.
- Rangeability up to 100:1.
- Response times as fast as 80ms.
- Multiple local display capabilities.
- External zero, span, & configuration capability.
- Polarity insensitive electrical connections.
- Comprehensive on-board diagnostic capabilities.
- Integral Dual Seal design for highest safety based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.1.
- Full compliance to SIL 2/3 requirements.
- Modular design characteristics.
- Available with an additional 15-year warranty.
- Plugged Impulse Line Detection Option.
- Supports NAMUR NE-107 Extended Diagnostics (FF).
- Dual/Triple Calibration Option (HART & Fieldbus Only).
Communications/Output Options
- 4-20mA
- Honeywell Digitally Enhanced (DE)
- HART® (version 7.0)
- FOUNDATION™ Fieldbus
All transmitters are available with the above listed communications protocols.
Span & Range Limits
Model | URL psi (bar) | LRL psi (bar) | Min Span psi (bar) |
---|---|---|---|
STG830/STG83L | 50 (3.5) | -14.7 (-1.0) | 0.5 (0.035) |
STG840/STG84L | 500 (35) | -14.7 (-1.0) | 5 (0.35) |
STG870/STG87L | 3000 (210) | -14.7 (-1.0) | 30 (2.1) |
STG88L | 6000 (420) | -14.7 (-1.0) | 60 (4.2) |
STG89L | 10000 (690) | -14.7 (-1.0) | 100 (6.9) |
Figure 1 - STG800 Gauge Pressure Transmitters
Figure 1 - STG800 Gauge Pressure Transmitters feature field-proven piezoresistive sensor technology
Two Honeywell STG800 SmartLine Gauge Pressure Transmitters are depicted. These devices are designed for industrial pressure measurement and feature a display screen and robust construction. The image highlights the core technology: field-proven piezoresistive sensor technology.
Description
The SmartLine family of gauge pressure, differential pressure, and absolute pressure transmitters is designed around a high performance piezo-resistive sensor. This one sensor integrates multiple sensors, linking process pressure measurement with on-board static pressure (DP Models) and temperature compensation measurements, resulting in the best total performance available. This level of performance allows the ST 800 to replace virtually any competitive transmitter available today.
Unique Indication/Display Options
The ST 800 modular design accommodates a standard alphanumeric LCD display or a unique advanced graphics LCD display with many unparalleled features.
Standard LCD Display Features
- Modular (may be added or removed in the field).
- Supports HART protocol variant.
- 0, 90, 180, & 270 degree position adjustments.
- Four configurable screens.
- Standard and custom measurement units available.
- Display calculated flow (square root) value in addition to analog output signal.
- 2 Lines 6 digits PV (9.95H x 4.20W mm) 8 Characters.
- Write protect Indication.
- Built-in Basic Device Configuration through Internal or External Buttons – Range/Engineering Unit/Loop Test /Loop Calibration/Zero /Span Setting.
- Multiple language capabilities (EN, RU).
Advanced Graphics LCD Display Features
- Modular (may be added or removed in the field).
- 0, 90, 180, & 270-degree position adjustments.
- Standard and custom measurement units available.
- Up to eight display screens with 3 formats are possible.
- Large PV with Bar Graph or PV with Trend Graph.
- Configurable screen rotation timing (1 to 30 sec).
- Display calculated flow (square root) value in addition to analog output signal.
- Unique "Health Watch" indication provides instant visibility of diagnostics.
- Multiple language capability (EN, DE, FR, IT, ES, RU, TR, CN, & JP).
Diagnostics
SmartLine transmitters all offer digitally accessible diagnostics which aid in providing advanced warning of possible failure events, minimizing unplanned shutdowns and providing lower overall operational costs.
Configuration Tools
Integral Three Button Configuration Option
Suitable for all electrical and environmental requirements, SmartLine offers the ability to configure the transmitter and display via three externally accessible buttons when either display option is selected. Zero/span capabilities are also optionally available via these buttons with or without selection of a display option.
Handheld Configuration
SmartLine transmitters feature two-way communication and configuration capability between the operator and the transmitter. All Honeywell transmitters are designed and tested for compliance with the offered communication protocols and are designed to operate with any standards-compliant handheld configuration device, such as the Honeywell Versatilis Configurator.
Personal Computer Configuration
On a personal computer or laptop, Honeywell Field Device Manager (FDM) Software and FDM Express can be used for managing HART & Fieldbus device configurations.
System Integration
- SmartLine communications protocols all meet the most current published standards for HART/DE/Fieldbus.
- Integration with Honeywell's Experion PKS offers the following unique advantages:
- Transmitter messaging.
- Maintenance mode indication.
- Tamper reporting.
- FDM Plant Area Views with Health summaries.
- All ST 800 units are Experion tested to provide the highest level of compatibility assurance.
Modular Design
To help contain maintenance & inventory costs, all ST 800 transmitters are modular in design, supporting the user's ability to replace meter bodies, add indicators, or change electronic modules without affecting overall performance or approval body certifications. Each meter body is uniquely characterized to provide in-tolerance performance over a wide range of application variations in temperature and pressure. Due to the Honeywell advanced interface, electronic modules may be swapped with any electronics module without losing in-tolerance performance characteristics.
Modular Features
- Meter body replacement
- Exchange/replace electronics/comms modules*
- Add or remove integral indicators*
- Add or remove lightning protection (terminal connection)*
* Field replaceable in all electrical environments (including IS) except flameproof without violating agency approvals.
With no performance effects, Honeywell's unique modularity results in lower inventory needs and lower overall operating costs.
Plugged Impulse Line Detection
STG800 models are offered with a PILD option which provides indication of a plugged impulse line or process connection. When used in conjunction with an advanced display, a non-critical diagnostic indication appears on the integral display. For units without an integral display, an indication can be seen via the host or handheld device when HART Protocol is utilized.
Dual/Triple Calibration
STG800 models are optionally offered with multiple calibrations. In lieu of a standard factory calibration, units can be supplied with 1, 2, or 3 customer-specified calibrations. These calibrations are stored in the meter body and provide users with factory-calibrated performance at up to three different calibrated ranges. This increases application flexibility without requiring any costly recalibration or additional inventory.
Performance Specifications
Reference Accuracy (conformance to +/-3 Sigma)
Model | URL | LRL | Min Span | Maximum Turndown Ratio | Stability (% URL/ Yr for 15 years) | Reference Accuracy¹ ² (% Span) Std / Opt. |
---|---|---|---|---|---|---|
STG830 | 50 psi (3.5 bar) | -14.7 psi (-1.0 bar) | 0.5 psi (.035 bar) | 100:1 | 0.010 | 0.0375 / 0.025 |
STG83L | 50 psi (3.5 bar) | -14.7 psi (-1.0 bar) | 0.5 psi (.035 bar) | |||
STG840 | 500 psi (35 bar) | -14.7 psi (-1.0 bar) | 5 psi (.35 bar) | |||
STG84L | 500 psi (35 bar) | -14.7 psi (-1.0 bar) | 5 psi (.35 bar) | |||
STG870 | 3000 psi (210 bar) | -14.7 psi (-1.0 bar) | 30 psi (2.1 bar) | 0.055 / 0.04 | ||
STG87L | 3000 psi (210 bar) | -14.7 psi (-1.0 bar) | 30 psi (2.1 bar) | |||
STG88L | 6000 psi (420 bar) | -14.7 psi (-1.0 bar) | 60 psi (4.2 bar) | |||
STG89L | 10000 psi (690 bar) | -14.7 psi (-1.0 bar) | 100 psi (6.9 bar) |
Zero and span may be set anywhere within the listed (URL/LRL) range limits.
Accuracy at Specified Span and Temperature (Conformance to +/-3 Sigma)
Model | URL | Reference Turndown | Accuracy¹ ² (% of Span) | Combined Zero & Span Temperature Effect (% Span/28°C (50°F)) | ||||
---|---|---|---|---|---|---|---|---|
A | B | C (see URL units) | D | E | ||||
Standard Accuracy | ||||||||
STG830 | 50 psi (3.5 bar) | 33.3:1 | 0.005 | 0.0325 | 1.5 (0.105) | 0.030 | 0.003 | |
STG83L | 50 psi (3.5 bar) | 16.7:1 | 0.005 | 0.0325 | 3 (0.21) | 0.030 | 0.006 | |
STG840 | 500 psi (35 bar) | 35:1 | 0.005 | 0.0325 | 14.5 (1.0) | 0.025 | 0.004 | |
STG84L | 500 psi (35 bar) | 35:1 | 0.005 | 0.0200 | 14.5 (1.0) | 0.025 | 0.007 | |
STG870 | 3000 psi (210 bar) | 10:1 | 0.015 | 0.0400 | 300 (21) | 0.025 | 0.005 | |
STG87L | 3000 psi (210 bar) | 10:1 | 0.015 | 0.0400 | 300 (21) | 0.025 | 0.005 | |
STG88L | 6000 psi (420 bar) | 12:1 | 0.015 | 0.0400 | 500 (35) | 0.010 | 0.010 | |
STG89L | 10000 psi (690 bar) | 10:1 | 0.015 | 0.0250 | 1000 (69) | 0.010 | 0.010 | |
High Accuracy Option | ||||||||
STG830 | 50 psi (3.5 bar) | 33.3:1 | 0.005 | 0.0325 | 1.5 (0.105) | 0.030 | 0.003 | |
STG83L | 50 psi (3.5 bar) | 16.7:1 | 0.005 | 0.0325 | 3 (0.21) | 0.030 | 0.006 | |
STG840 | 500 psi (35 bar) | 35:1 | 0.005 | 0.0325 | 14.5 (1.0) | 0.025 | 0.004 | |
STG84L | 500 psi (35 bar) | 35:1 | 0.005 | 0.0200 | 14.5 (1.0) | 0.025 | 0.007 | |
STG870 | 3000 psi (210 bar) | 10:1 | 0.015 | 0.0400 | 300 (21) | 0.025 | 0.005 | |
STG87L | 3000 psi (210 bar) | 10:1 | 0.015 | 0.0400 | 300 (21) | 0.025 | 0.005 | |
STG88L | 6000 psi (420 bar) | 12:1 | 0.015 | 0.0400 | 500 (35) | 0.010 | 0.010 | |
STG89L | 10000 psi (690 bar) | 10:1 | 0.015 | 0.0250 | 1000 (69) | 0.010 | 0.010 |
Turn Down Effect: ±[A+B] if Span ≥ C; ±[A+B(Span)] if Span < C
Temp Effect: ±[D+E(URL/Span)]
Total Performance
Total Performance Calculation: = ±√(Accuracy)² + (Temperature Effect)²
Total Performance Examples (for comparison): Standard accuracy 5:1 Turndown, ±50°F (28°C) shift
- STG830 @ 10 psi: 0.059% of span
- STG83L @ 10 psi: 0.071% of span
- STG88L @ 1200 psi: 0.084% of span
- STG840 @ 100 psi: 0.059% of span
- STG84L @ 100 psi: 0.071% of span
- STG89L @ 2000 psi: 0.093% of span
- STG870 @ 600 psi: 0.063% of span
- STG87L @ 600 psi: 0.084% of span
Typical Calibration Frequency
Calibration verification is recommended every four (4) years.
Notes:
- Terminal Based Accuracy - Includes combined effects of linearity, hysteresis, and repeatability. Analog output adds 0.005% of span.
- For zero based spans and reference conditions of: 25°C (77°F) for LRV>= 0 psia, 10 to 55% RH, and 316 Stainless Steel barrier diaphragm.
Operating Conditions – All Models
Parameter | Reference Condition | Rated Condition | Operative Limits | Transportation and Storage | ||||
---|---|---|---|---|---|---|---|---|
°C | °F | °C | °F | °C | °F | °C | °F | |
Ambient Temperature¹ | 25±1 | 77±2 | -40 to 85 | -40 to 185 | -40 to 85 | -40 to 185 | -55 to 120 | -67 to 248 |
Meter Body Temperature² | 25±1 | 77±2 | -40 to 110¹ | -40 to 230¹ | -40 to 125 | -40 to 257 | -55 to 120 | -67 to 248 |
Humidity | %RH | 10 to 55 | 0 to 100 | 0 to 100 | 0 to 100 | |||
Vac. Region – Min. Pressure | mmHg absolute | Atmospheric | 25 | 2 (short term)³ | 1 (short term)³ | |||
inH₂O absolute | Atmospheric | 13 | ||||||
Supply Voltage Load Resistance | ||||||||
HART: 10.8 to 42.4 VDC at terminals (IS versions limited to 30 VDC), 0 to 1,440 ohms DE: 15 to 49.3VDC at terminals (IS versions limited to 30VDC), 0 to 1,200 ohms (as shown in Figure 2) FOUNDATION Fieldbus: 9.0 to 32.0 VDC at terminals, steady state current: 17.6mA, software download current: 27.4mA |
||||||||
Maximum Allowable Working Pressure (MAWP)⁴ (Maximum allowable working pressure is the maximum pressure allowed for the normal transmitter operation. MAWP depends on Approval agencies and transmitter material of construction. MAWP are same as URL for gauge and absolute pressure transmitters) |
STG830: 50 psi (3.5 bar) | STG83L: 50 psi (3.5 bar) | ||||||
STG840: 500 psi (35 bar) | STG84L: 500 psi (35 bar) | |||||||
STG870: 3000 psi (210 bar) | STG87L: 3000 psi (210 bar) | |||||||
STG88L: 6000 psi (420 bar) | STG89L: 10000 psi (690 bar) | |||||||
Over pressure These are the pressure limits the transmitters can withstand without damage |
STG830: 75 psi (5.25 bar) | STG83L: 75 psi (5.25 bar) | ||||||
STG840: 1500 psi (103 bar) | STG84L: 1500 psi (103 bar) | |||||||
STG870: 4500 psi (310 bar) | STG87L: 4500 psi (310 bar) | |||||||
STG88L: 9000 psi (620 bar) | STG89L: 15000 psi (1035 bar) |
¹ LCD Display operating temperature -20°C to +70°C. Storage temperature -30°C to 80°C.
² Silicone 704 minimum temperature rating is 0°C (32°F). CTFE minimum temperature rating is -40°C (-40°F). NEOBEE M-20 minimum temperature rating is -15°C (5°F). NEOBEE® is a registered trademark of Stepan Company.
³ Short term equals 2 hours at 70°C (158°F).
⁴ Consult factory for MAWP of ST 800 transmitters with CRN approval.
Figure 2 - Supply voltage and loop resistance chart & calculations
Figure 2 - Supply voltage and loop resistance chart & calculations
This figure illustrates the relationship between operating voltage (VDC) and loop resistance (ohms) for HART and DE communication protocols. It includes formulas for calculating maximum loop resistance (RLmax) for both protocols, based on supply voltage. A minimum of 250 ohms loop resistance is required to support a field communicator.
Performance Under Rated Conditions – All Models
Parameter | Description |
---|---|
Analog Output | Two-wire, 4 to 20 mA (HART & DE Transmitters only) |
Digital Communications: | Honeywell DE, HART protocol or FOUNDATION Fieldbus ITK 6.0.1 compliant. All transmitters, irrespective of protocol, have polarity insensitive connection. |
HART & DE Output Failure Modes (NAMUR for DE Units requires selecting display and configuration buttons or factory configuration) |
Normal Limits: Honeywell Standard: 3.8–20.8 mA; NAMUR NE 43 Compliance: 3.8–20.5 mA |
Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA | |
Supply Voltage Effect | 0.005% span per volt |
Transmitter Turn on Time (includes power up & test algorithms) | HART or DE: 2.5 seconds; Foundation Fieldbus: host dependent |
Response Time (delay + time constant) | DE/HART Protocol: 80ms; FOUNDATION Fieldbus: 150ms (Host Dependent) |
Damping Time Constant | HART: Adjustable from 0 to 32 seconds in 0.1 increments. Default Value: 0.5 seconds DE: Discrete values 0, 0.16, 0.32, 0.48, 1, 2, 4, 8, 16, 32 seconds. Default Value: 0.48 seconds |
Vibration Effect | Less than +/- 0.1% of URL w/o damping. Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz: 0.21 displacement/3g max acceleration) |
Electromagnetic Compatibility | Complies with EMC directive 2004/108/EC per IEC 61326-3-1 (HART/ DE Units) IEC 61326-1 (FF Units) |
Lightning Protection Option | Leakage Current: 10uA max @ 42.4VDC 93C Impulse rating: 8/20us: 5000A (>10 strikes) 10000A (1 strike min.) 10/1000us: 200A (> 300 strikes) |
Materials Specifications
(See model selection guide for availability/restrictions with various models)
Parameter | Description |
---|---|
Barrier Diaphragms Material | STG800: 316L SS, Hastelloy® C-276², Monel® 400³, Tantalum, Gold-plated 316L SS, Gold-plated Hastelloy® C-276, Gold-plated Monel® 400 STG80L: 316L SS, Hastelloy C-276 |
Process Head Material | STG800: Carbon Steel (Zinc Plated), 316 SS⁴, Hastelloy® C-276⁶, Monel® 400⁷ STG80L: 316L SS, Hastelloy C-276⁶ |
Vent/Drain Valves & Plugs ¹ | STG800:316 SS⁴, Hastelloy C-276², Monel 400⁷ STG80L: N/A |
Head Gaskets | STG800: Glass-filled PTFE standard. Viton® and graphite are optional. STG80L: N/A |
Meter Body Bolting | STG800: Carbon Steel (Zinc plated) standard. Options include 316 SS, NACE A286 SS bolts and nuts or NACE A286 SS bolts and 304 SS nuts STG80L: N/A |
Mounting Bracket | Carbon Steel (Zinc-plated) or 304 SS or 316SS angle bracket or Carbon Steel or 304SS or 316SS flat bracket available with 2" pipe bracket. See Figure 3. |
Fill Fluid | Silicone 200, CTFE, NEOBEE M-20 or Silicone 704 |
Electronic Housing | Pure Polyester Powder Coated Low Copper (<0.4%) – Aluminum. Meets Type 4X / IP66 / IP67. All stainless-steel housing is optional. Cover O ring material: Silicone. |
Process Connections | STG800: ½-inch NPT female, DIN 19213 (standard) STG80L: ½-inch NPT female, ½-inch NPT male, 9/16-18 high-pressure Cone and Thread female⁸, DIN19213 (except STG89L), G ½-B Male threaded |
Wiring | Accepts up to 16 AWG (1.5 mm diameter). |
Dimensions | See Figure 4 and 5 |
Net Weight | STG800: 8.3 pounds (3.8 Kg). STG80L: 3.6 pounds (1.6 Kg) with Aluminum Housing |
¹ Vent/Drains are sealed with Teflon®
² Hastelloy® C-276 or UNS N10276.
³ Monel® 400 or UNS N04400.
⁴ Supplied as 316 SS or as Grade CF8M, the casting equivalent of 316 SS.
⁵ Carbon Steel heads are zinc-plated and not recommended for water service due to hydrogen migration. For that service, use 316 stainless steel wetted Process Heads.
⁶ Hastelloy® C-276 or UNS N10276. Supplied as indicated or as Grade CW12MW, the casting equivalent of Hastelloy® C-276.
⁷ Monel® 400 or UNS N04400. Supplied as indicated or as Grade M30C, the casting equivalent of Monel® 400.
⁸ 9/16 Aminco.
Communications Protocol & Diagnostics
HART Protocol
Version: HART 7
Foundation Fieldbus (FF)
Available Function Blocks
Block Type | Quantity | Execution Time |
---|---|---|
Resource | 1 | n/a |
Transducer | 1 | n/a |
Diagnostic | 1 | n/a |
Analog Input | 1* | 30 ms |
PID w/Autotune | 1 | 45 ms |
Integrator | 1 | 30 ms |
Signal Char (SC) | 1 | 30 ms |
LCD Display | 1 | n/a |
Flow Block | 1 | 30 ms |
Input Selector | 1 | 30 ms |
Arithmetic | 1 | 30 ms |
* AI block may have two (2) additional instantiations.
All available function blocks adhere to FOUNDATION Fieldbus standards. PID blocks support ideal & robust PID algorithms with full implementation of Auto-tuning.
Link Active Scheduler
Transmitters can perform as a backup Link Active Scheduler and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus.
Number of Devices/Segment: Entity IS model: 6 devices/segment
Schedule Entries: 18 maximum schedule entries
Number of VCR's: 24 max
Compliance Testing: Tested according to ITK 6.0.1
Software Download: Utilizes Class-3 of the Common Software Download procedure as per FF-883 which allows the field devices of any manufacturer to receive software upgrades from any host.
Honeywell Digitally Enhanced (DE)
DE is a Honeywell proprietary protocol which provides digital communications between Honeywell DE enabled field devices and Hosts.
Standard Diagnostics
ST 800 top-level diagnostics are reported as either critical or non-critical and are readable via the DD/DTM/FDI tools or integral display. All critical diagnostics will appear on the Advanced and Standard integral displays, and some non-critical diagnostics will also appear on the Advanced integral display. Some of the diagnostics are listed below.
Critical Diagnostics
- Electronics Module Fault.
- Meter body Memory Corruption.
- Config Data Corruption.
- Electronics Module Diagnostics Failure.
- Meter body Critical Failure.
- Sensor Communication Timeout.
Non-Critical Diagnostics
- Electronics Module Fault.
- Display Failure.
- Electronics Module Comm Failure.
- Meter body Excess Correct.
- Sensor Over Temperature.
- Fixed Current Mode.
- PV Out of Range.
- No DAC Compensation.
- Tamper Attempt Alarm.
Refer to the product user manual for comprehensive list of diagnostics and details.
Other Certification Options
Materials
- NACE MRO175, MRO103, ISO15156
Hazardous Area Certifications
MSG CODE | AGENCY | TYPE OF PROTECTION | COMM. OPTION | ELECTRICAL PARAMETERS | AMBIENT TEMP (Ta) |
---|---|---|---|---|---|
A | FM Approvals™ USA | Explosionproof: Class I, Division 1, Groups A, B, C, D; Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T6..T5 Class I, Zone 0/1, AEx db IIC T6..T5 Ga/Gb Class II, Zone 21, AEx tb IIIC T95° Db |
All | Note 1 | T5: -50 °C to 85°C T6: -50 °C to 65°C |
Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D, E, F, G: T4 Class I, Zone 0, AEx ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART | Note 2a | -50 °C to 70°C | ||
Nonincendive: Class I, Division 2, Groups A, B, C, D locations, T4 Class I, Zone 2, AEx nA IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 1 | -50 °C to 85°C | ||
Enclosure: Type 4X/ IP66/ IP67 | All | All | - | ||
STANDARDS: FM Class 3600:2011; FM Class 3610: 2010; FM Class 3611: 2004; FM Class 3615: 2006; FM Class 3616: 2011; FM Class 3810: 2005; ANSI/ISA 60079-0: 2013; ANSI/UL 60079-1: 2015; ANSI/UL 60079-11: 2014; ANSI/ISA 60079-15: 2012; ANSI/UL 60079-26: 2017; ANSI/UL 60079-31: 2015; ANSI/NEMA 250: 2003; ANSI/IEC 60529: 2004 | |||||
B | Canadian Standards Association (CSA) USA and Canada | Explosion Proof: Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1, T6..T5 Class I Zone 1 AEx db IIC T6..T5 Ga/Gb Ex db IIC T6..T5 Ga/Gb Zone 22 AEx tb IIIC T95° Db Ex tb IIIC T95° Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1, T4 Class I Zone 0, AEx ia IIC T4 Ga Class I Zone 2, AEx ic IIC T4 Gc Ex ia IIC T4 Ga Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART | Note 2 | -50°C TO 70°C | ||
Foundation Fieldbus | Note 2 | -50°C TO 70°C | |||
Nonincendive: Class I, Division 2, Groups A, B, C, D; Class II, Division 2, Groups F, G; Class III, Division 2, T4 Class I Zone 2 AEx nA IIC T4 Gc Ex nA IIC T4 Gc Enclosure: Type 4X/ IP66/ IP67 |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 1 | -50°C to 85°C | ||
STANDARDS: CSA C22.2 No. 0-10; CSA C22.2 No. 94-M91; CSA C22.2 No. 25-1966; CSA C22.2 No. 30-M1986; CSA C22.2 No. 142-M1987; CSA C22.2 No. 157-92; CSA C22.2 No. 213-M1987; CSA-C22.2 No. 60529:05; CSA-C22.2 No. 60079-0:11; CSA-C22.2 No. 60079-1:11; CSA-C22.2 No. 60079-11:11; CSA-C22.2 No. 60079-15:12; CSA-C22.2 No. 60079-31:12; ISA 12.12.01-2010; ISA 60079-0: 2009; ISA 60079-11: 2011; ISA 60079-15: 2009; ISA 60079-26: 2008; ISA-60079-27:2007 (12.02.04)-2006 (R2011); UL 913 Ed. 6; UL 916:1998; ANSI/ISA-12.27.01-2011 | |||||
C | ATEX | Flameproof: SIRA 12ATEX2233X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: SIRA 12ATEX2233X II 1 G Ex ia IIC T4 Ga II 2 D Ex ia IIIC T125°C Db FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: SIRA 12ATEX4234X II 3 G Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: SIRA 12ATEX4234X II 3 G Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) II 3 G Ex ic IIC T4 Gc Enclosure: IP66/ IP67 |
4-20 mA / DE/ HART/ Foundation Fieldbus All |
Note 2 All |
-50°C TO 85°C - |
||
STANDARDS: EN 60079-0: 2018; EN 60079-1: 2014; EN 60079-7: 2015+A1:2018; EN 60079-11: 2012; EN 60079-26: 2015; EN 60079-31: 2014 | |||||
C | UKEX | Flameproof: CSAE 22UKEX1021X II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: CSAE 22UKEX1021X II 1 G Ex ia IIC T4 Ga II 2 D Ex ia IIIC T125°C Db FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: CSAE 22UKEX1008X II 3 G Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: CSAE 22UKEX1008X II 3 G Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) II 3 G Ex ic IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 2 | -50°C TO 85°C | ||
STANDARDS: EN 60079-0: 2018; EN 60079-1: 2014; EN 60079-7: 2015+A1:2018; EN 60079-11: 2012; EN 60079-26: 2015; EN 60079-31: 2014 | |||||
D | IECEx World | Flameproof: IECEx SIR 12.0100X Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: IECEx SIR 12.0100X Ex ia IIC T4 Ga Ex ia IIIC T125°C Db FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: IECEX SIR 12.0100X Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus | Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: IECEX SIR 12.0100X Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc Enclosure: IP66/ IP67 |
4-20 mA / DE/ HART/ Foundation Fieldbus All |
Note 2 All |
-50°C TO 85°C - |
||
STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014; IEC 60079-7: 2017; IEC 60079-11: 2011; IEC 60079-26: 2014; IEC 60079-31: 2013 | |||||
E | SAEX South Africa | Flameproof: Ex d IIC T6...T5 Ga/Gb Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Ex ia IIC Ga T4 FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus |
Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc Enclosure: IP66/ IP67 |
4-20 mA / DE/ HART/ Foundation Fieldbus All |
Note 2 All |
-50°C TO 85°C - |
||
F | INMETRO Brazil | Flameproof: Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2a Note 2b |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus |
Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc Enclosure : IP 66/67 |
4-20 mA / DE/ HART/ Foundation Fieldbus All |
Note 2 All |
-50°C TO 85°C - |
||
G | NEPSI CHINA | Flameproof: Ex db IIC T6..T5 Ga/Gb Ex tb IIIC T 95°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Zone 2, Increase Safety: II 3 G Ex ec IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus |
Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: Ex ic IIC T4 Gc FISCO Field Device (Only for FF Option) Ex ic IIC T4 Gc Enclosure : IP 66/67 |
4-20 mA / DE/ HART/ Foundation Fieldbus All |
Note 2 All |
-50°C TO 85°C - |
||
H | KOSHA Korea | Flameproof : Ex d IIC T4, T5, T6 Ex tD A21 IP66/IP67 T95°C...T120 °C |
All | Note 1 | T4: -50°C TO 85°C T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Ex ia IIC T4 |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
Ta= -50 °C to 70°C Ta= -50 °C to 70°C |
||
Enclosure: IP66/ IP67 | All | All | - | ||
Flameproof: Ga/Gb Ex d IIC T6..T5 Ex tb IIIC Db T 85°C |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
||
I | EAC Russia, Belarus and Kazakhstan | Intrinsically Safe: Ga Ex ia IIC T4 X FISCO Field Device (Only for FF Option) Ga Ex ia IIC T4 X |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
Zone 2, Non Sparking: 2 Ex nA IIC T4 Gc X |
4-20 mA / DE/HART/ Foundation Fieldbus |
Note 1 | -50°C TO 85°C | ||
Zone 2, Intrinsically Safe: Ga Ex ic IIC T4 X FISCO Field Device (Only for FF Option) 2 Ex ic IIC T4 Gc X |
4-20 mA / DE/HART/ Foundation Fieldbus |
Note 2 | -50°C TO 85°C | ||
Enclosure : IP 66/67 | All | All | - | ||
J | CCoE INDIA | Flameproof: Ex d IIC T6..T5 Ga/Gb |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) Ex ia IIC T4 Ga; Ex ic IIC T4 Gc |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Non Sparking Ex nA IIC T4 Gc |
4-20 mA / DE/ HART/ Foundation Fieldbus |
Note 1 | -50°C TO 85°C | ||
Enclosure: IP66/ IP67 | All | All | - | ||
K | UATR UKRAINE | Flameproof: II 1/2 G Ex db IIC T6..T5 Ga/Gb II 2 D Ex tb IIIC T95°C...T120°C Db |
All | Note 1 | T5: -50°C TO 85°C T6: -50°C TO 65°C |
Intrinsically Safe: II 1 G Ex ia IIC T4 Ga FISCO Field Device (Only for FF Option) II 1 G Ex ia IIC T4 Ga |
4-20 mA / DE/ HART Foundation Fieldbus |
Note 2 Note 2 |
-50°C TO 70°C -50°C TO 70°C |
||
Enclosure: IP66/ IP67 | All | All | - |
Notes & Approval Certifications
Notes
- Operating Parameters:
Voltage = 11 to 42 VDC
= 9 to 32 V (FF)
Current = 4-20 mA Normal
= 30 mA (FF) - Intrinsically Safe Entity Parameters
a. Analog/DE/HART Entity Values:
Parameter | Value | Ci | Li | Pi |
---|---|---|---|---|
Vmax = Ui = 30V | Imax = Ii = 105mA | 4.2nF | 984 uH | 0.9W |
Transmitter with Terminal Block revision E or Later | ||||
Vmax = Ui = 30V | Imax= Ii = 225mA | 4.2nF | 0 | 0.9W |
Note: Transmitter with Terminal Block revision E or later. The revision is on the label that is on the module. There will be two lines of text on the label: First is the Module Part #: 50049839-001 or 50049839-002. Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION.
b. Foundation Fieldbus Entity Values
Parameter | Value | Ci | Li | Pi |
---|---|---|---|---|
Vmax = Ui = 30V | Imax = Ii = 180mA | 0nF | 984 uH | 1W |
Transmitter with Terminal Block revision F or Later | ||||
Vmax = Ui = 30V | Imax = Ii = 225mA | 0nF | 0 | 1 W |
FISCO Field Device
Parameter | Value | Ci | Li | Pi |
---|---|---|---|---|
Vmax = Ui = 17.5V | Imax = Ii = 380 mA | 0nF | 0 | 5.32 W |
Note: Transmitter with Terminal Block revision F or later. The revision is on the label that is on the module. There will be two lines of text on the label: First is the Module Part #: 50049839-003 or 50049839-004. Second line has the supplier information, along with the REVISION: XXXXXXX-EXXXX, THE "X" is production related, THE POSITION of the "E" IS THE REVISION.
Approval Certifications
This certificate defines the certifications covered for the ST 800 Pressure Transmitter family of products, including the SMV 800 Smart Multivariable Transmitter. It represents the compilation of the five certificates Honeywell currently has covering the certification of these products into marine applications.
For ST 800 Smart Pressure Transmitter and SMV800 Smart Multivarible Transmitter
Marine Certificates
- American Bureau of Shipping (ABS) - 2009 Steel Vessel Rules 1-1-4/3.7, 4-6-2/5.15, 4-8-3/13 & 13.5, 4-8-4/27.5.1, 4-9-7/13. Certificate number: 04-HS417416-PDA
- Bureau Veritas (BV) - Product Code: 389:1H. Certificate number: 12660/B0 BV
- Det Norske Veritas (DNV) - Location Classes: Temperature D, Humidity B, Vibration A, EMC B, Enclosure C. For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316 SST bolts to be applied. Certificate number: A-11476
- Korean Register of Shipping (KR) - Certificate number: LOX17743-AE001
- Lloyd's Register (LR) - Certificate number: 02/60001(E1) & (E2)
SIL 2/3 Certification
IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use according to EXIDA and TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.
MEASUREMENT INSTRUMENTS DIRECTIVE (MID) 2004/22/EC
Certificate Issued by NMI Certin B.V.
Mechanical Class: M3
Electromagnetic Environment: E3
Ambient Temperature Range: -25 °C to + 55 °C
Unit | Custom Calibration |
---|---|
STD820 | 0 to 1000 mBar |
STD830 | 0 to 7 Bar |
STA84L | 0 to 35 Bar A |
STG84L | 0 to 35 Bar |
STD870 | 0 to 100 Bar |
STA87L | 0 to 100 Bar A |
STG87L | 0 to 100 Bar |
Dimensional Drawings
Figure 3 - Typical mounting configuration of dual head and inline designs
Figure 3 - Typical mounting configuration of dual head and inline designs for reference
Diagrams illustrating various mounting configurations for the STG800 transmitters, showing both dual head and inline designs attached to piping systems.
Figure 4 - Typical mounting dimensions of STG840 & STG870
Figure 4 - Typical mounting dimensions of STG840 & STG870 for reference
Dimensional drawings for the STG840 and STG870 models in a dual head design. The drawings provide detailed measurements in millimeters and inches for various components and orientations, including conduit connections, vent/drain ports, and overall dimensions with and without optional displays.
Figure 5 - Typical mounting dimensions of STG84L, STG87L, STG88L, & STG89L
Figure 5 - Typical mounting dimensions of STG84L, STG87L, STG88L, & STG89L for reference
Dimensional drawings for the STG84L, STG87L, STG88L, and STG89L models in an inline design. The drawings provide detailed measurements in millimeters and inches for various components and orientations, including conduit connections, pressure connections, vent/drain ports, and overall dimensions with and without optional displays.
Model Selection Guide
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Model STG800 Gauge Pressure Transmitters
Model Selection Guide: 34-ST-16-83 | Issue: 34
Instructions: Make selections from all Tables using column below the proper arrow. Asterisk indicates availability. Letter (a) refers to restrictions highlighted in the restrictions table. Tables delimited with dashes. List Price: Price equals the sum of prices for all selections made.
Key Number Table
KEY NUMBER | URL/Max Span | LRL | Min Span | Units | Selection | Availability |
---|---|---|---|---|---|---|
Gauge Dual Head | 50 (3.5) | -14.7 (-1.0) | 0.5 (.035) | psi (bar) | STG830 | |
500 (35) | -14.7 (-1.0) | 5 (.35) | psi (bar) | STG840 | ||
3000 (210) | -14.7 (-1.0) | 30 (2.1) | psi (bar) | STG870 | ||
Gauge In-Line | 50 (3.5) | -14.7 (-1.0) | 0.5 (.035) | psi (bar) | STG83L | |
500 (35) | -14.7 (-1.0) | 5 (.35) | psi (bar) | STG84L | ||
3000 (210) | -14.7 (-1.0) | 30(2.1) | psi (bar) | STG87L | ||
6000 (420) | -14.7 (-1.0) | 60 (4.2) | psi (bar) | STG88L | ||
10000 (690) | -14.7 (-1.0) | 100 (6.9) | psi (bar) | STG89L |
TABLE I: METER BODY SELECTIONS
Process Head/Reference Head Material¹ᵇ | Barrier Diaphragm Material | |||||||
---|---|---|---|---|---|---|---|---|
a. Process Head & Diaphragm Materials | 316L SS | 316L SS | A | B | C | D | 1 | 2 |
Hastelloy C - 276 | Hastelloy C - 276 | |||||||
Monel 400® | Monel 400® | |||||||
Plated Carbon Steel / Plated Carbon Steel | Tantalum | |||||||
316 Stainless Steel /316 Stainless Steel¹ᶜ | Gold Plated 316L SS | |||||||
Gold Plated Hastelloy C-276 | ||||||||
Gold Plated Monel 400 | ||||||||
Hastelloy C-276 | 316L SS | |||||||
Hastelloy C-276 / 316 Stainless Steel | Hastelloy C - 276 | |||||||
Monel 400 / 316 Stainless Steel | Monel 400 | |||||||
b. Fill Fluid | Silicone Oil 200 | Tantalum | 3 | 4 | 5 | 6 | 7 | 8 |
Fluorinated Oil CTFE | Gold Plated Hastelloy C-276 | |||||||
Silicone Oil 704 | Gold Plated Monel 400 | |||||||
NEOBEE® M-20 | Hastelloy C-276 | |||||||
Gold Plated Monel 400 | ||||||||
c. Process Connection | Size/Type | Material | ||||||
9/16-18 high pressure Cone & Thread (female)¹ᵈ | Same as Process Head | A | G | H | D | B | N | |
1/2" NPT (female) | Same as Process Head ¹ᵃ | 0 | C | S | N | K | M | |
1/2" NPT (male) | Same as Process Head | D | ||||||
DIN 19213 (1/4" female NPT) | Same as Process Head | B | ||||||
G ½ B Threaded Fitting | Same as Process Head | |||||||
d. Bolt/Nuts Materials | M20 | |||||||
None | Carbon Steel | |||||||
316 SS | 316 SS | |||||||
Grade 660 (NACE A286) with NACE 304 SS Nuts | Grade 660 (NACE A286) Bolts & Nuts | |||||||
Monel K500 | Monel K500 | |||||||
Super Duplex | Super Duplex | |||||||
B7M | ||||||||
e. Vent/Drain Type/Location | Head Type | Vent Type | Location | Vent Material | ||||
None | None | None | None | 0 | ||||
Single Ended | Standard Vent | Side | Matches Head Material¹ | 1 | ||||
Single Ended | Center Vent | Side | Stainless Steel Only | 2 | t | |||
Dual Ended | Standard Vent | End | Matches Head Material¹ | 3 | t | |||
Dual Ended | Center Vent | End | Stainless Steel only | 4 | ||||
Dual Ended | Std Vent/Plug | Side/End | Matches Head Material¹ | 5 | ||||
None | 6 | |||||||
f. Gasket Materials | Teflon® or PTFE (Glass Filled) | O | A | B | C | |||
Viton | ||||||||
Graphite |
¹ Except Carbon Steel Heads shall use 316SS Vent/Drain & Plugs and or 1/2" adapters
¹ᵃ STG830,840,870 supplied via 1/2" flange adapter same material as process head except carbon steel shall use 316 SS
¹ᵇ Reference head available with Dual Head Gage models only. In-Line Gage models are supplied with Process Head only.
¹ᶜ When selected for In-Line Gage models the Process Head / Bonnet is supplied in Dual Certified SS316/316L
¹ᵈ 9/16" Aminco
TABLE II: METER BODY & CONNECTION ORIENTATION
Head/Connect Orientation | |
---|---|
Standard | High Side Left, Low Side Right² / Std Head Orientation |
Reversed | Low Side Left, High Side Right² / Std Head Orientation |
90/Standard | High Side Left, Low Side Right² / 90° Head Rotation |
TABLE III: AGENCY APPROVALS
Approvals | |
---|---|
No Approvals Required | 0 |
<FM> Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof | A |
CSA Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof | B |
ATEX Explosion proof, Intrinsically Safe & Non-incendive | C |
IECEx Explosion proof, Intrinsically Safe & Non-incendive | D |
SAEx Explosion proof, Intrinsically Safe & Non-incendive | E |
INMETRO Explosion proof, Intrinsically Safe & Non-incendive | F |
NEPSI Explosion proof, Intrinsically Safe & Non-incendive | G |
KOSHA Explosion proof, Intrinsically Safe & Non-incendive | H |
EAC Customs Union (Russia, Belarus, Kazakhstan)Ex Approval, Flame proof, Intrinsically Safe | I |
CCoE Explosion proof, Intrinsically Safe & Non-incendive | J |
UATR Flameproof, Intrinsically Safe & Dustproof | K |
TABLE IV: TRANSMITTER ELECTRONICS SELECTIONS
a. Electronic Housing Material & Connection Type | Material | Connection | Lightning Protection | |
---|---|---|---|---|
Polyester Powder Coated Aluminum | 1/2 NPT | None | A | |
Polyester Powder Coated Aluminum | M20 | None | B | |
Polyester Powder Coated Aluminum | 1/2 NPT | Yes | C | |
Polyester Powder Coated Aluminum | M20 | Yes | D | |
Dual Certified SS 316/316L (CF8M/CF3M) | 1/2 NPT | None | E | |
Dual Certified SS 316/316L (CF8M/CF3M) | M20 | None | F | |
Dual Certified SS 316/316L (CF8M/CF3M) | 1/2 NPT | Yes | G | |
Dual Certified SS 316/316L (CF8M/CF3M) | M20 | Yes | H |
b. Output/ Protocol | Analog Output | Digital Protocol | |
---|---|---|---|
4-20mA dc | HART Protocol | 0 | |
4-20mA dc | DE Protocol | A | |
Foundation Fieldbus | u |
c. Customer Interface Selections | Indicator | Ext Zero, Span & Config Buttons | Languages | |
---|---|---|---|---|
None | None | None | 0 | |
None | Yes (Zero/Span Only) | None | A | |
Advanced | None | EN, GR, FR, IT, SP, RU, TU | D | |
Advanced | Yes | EN, GR, FR, IT, SP, RU, TU | E | |
Advanced | None | EN, CH, JP | H | |
Advanced | Yes | EN, CH, JP | J | |
Standard (w/internal Zero, Span & Conf Buttons) | None | EN, RU | S | |
Standard (w/internal Zero, Span & Conf Buttons) | Yes | EN, RU | T |
TABLE V: CONFIGURATION SELECTIONS
a. Application Software | Diagnostics | |
---|---|---|
Standard Diagnostics | Advanced Diagnostics (Above with Plugged Impulse Detection PILD) | 1__ |
2 |
b. Output Limit, Failsafe & Write Protect Settings | High & Low Output Limits³ | ||
---|---|---|---|
Disabled | High> 21.0mAdc | Honeywell Std (3.8 - 20.8 mAdc) | 1_ |
Enabled | Low< 3.6mAdc | Honeywell Std (3.8 - 20.8 mAdc) | 2_ |
Disabled | High> 21.0mAdc | Honeywell Std (3.8 - 20.8 mAdc) | 3 |
Enabled | Low< 3.6mAdc | Honeywell Std (3.8 - 20.8 mAdc) | 4 |
Enabled | N/A | Fieldbus or Profibus | 5_ |
Disabled | N/A | Fieldbus or Profibus | 6 |
c. General Configuration | |
---|---|
Factory Standard | S |
Custom Configuration (Unit Data Required from customer) | C |
² Left side/Right side as viewed from the customer connection perspective
³ NAMUR Output Limits are configurable by customer
TABLE VI: CALIBRATION & ACCURACY SELECTIONS
Accuracy | Calibrated Range | Calibration Qty | |
---|---|---|---|
Standard | Factory Standard | Single Calibration | A |
Standard | Custom (Unit Data Required) | Single Calibration | B |
Standard | Custom (Unit Data Required) | Dual Calibration | C |
Standard | Custom (Unit Data Required) | Triple Calibration | D |
High Accuracy | Factory Standard | Single Calibration | E |
High Accuracy | Custom (Unit Data Required) | Single Calibration | F |
High Accuracy | Custom (Unit Data Required) | Dual Calibration | G |
High Accuracy | Custom (Unit Data Required) | Triple Calibration | H |
TABLE VII: ACCESSORY SELECTIONS
a. Mounting Bracket | Bracket Type | Material | |
---|---|---|---|
None | None | 0 | |
Angle Bracket | Carbon Steel | 1 | |
Angle Bracket | 304 SS | 2 | |
Angle Bracket | 316 SS | 3 | |
Marine Approved Bracket | Carbon Steel | 8 | |
Marine Approved Bracket (In-Line) | Carbon Steel | 9 | |
Marine Approved Bracket | 304 SS | 4 | |
Marine Approved Bracket (In-Line) | 304 SS | A | |
Flat Bracket | Carbon Steel | 5 | |
Flat Bracket | 304 SS | 6 | |
Flat Bracket | 316 SS | 7 |
b. Customer Tag | Customer Tag Type | |
---|---|---|
No customer tag | * | |
One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) | 2 | |
Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line) |
c. Unassembled Conduit Plugs & Adapters | |
---|---|
No Conduit Plugs or Adapters Required | |
1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter | A0 |
1/2 NPT 316 SS Certified Conduit Plug | A2 |
M20 316 SS Certified Conduit Plug | A6 |
Minifast® 4 pin (1/2 NPT) (not suitable for X-Proof applications) | A7 |
Minifast® 4 pin (M20) (not suitable for X-Proof applications) | A8 |
TABLE VIII: OTHER Certifications & Options: (String in sequence comma delimited (XX, XX, XX,....)
No additional options | 00 | * | * | * | * | * | * |
Low Temperature Rating (-50 deg C min. ambient operative temperature limit) | LT | w | w | w | w | w | w |
NACE MR0175; MR0103; ISO15156 (FC33338) Process wetted parts only | FG | * | c | * | c | * | c |
NACE MR0175; MR0103; ISO15156 (FC33339) Process wetted and non-wetted parts | F7 | * | c | * | c | * | c |
Marine (DNV, ABS, BV, KR, LR) | MT | d | d | d | d | d | d |
EN10204 Type 3.1 Material Traceability (FC33341) | FX | * | * | * | * | * | * |
MID Approved Transmitter - Contact Tech Support for specific MID approved ranges | MD | * | * | * | * | * | * |
Certificate of Conformance (F3391) | F3 | * | * | * | * | * | * |
Calibration Test Report & Certificate of Conformance (F3399) | F1 | * | * | * | * | * | * |
Certificate of Origin (F0195) | F5 | * | * | * | * | * | * |
FMEDA (SIL 2/3) Certification (FC33337) | FE | j | j | j | j | j | j |
Over-Pressure Leak Test Certificate (1.5X MAWP) (F3392) for Transmitter Only | TP | * | * | * | * | * | * |
Cert Clean for O2 or CL2 service per ASTM G93 | OX | e | e | e | e | e | e |
PMI Certification¹ | PM | * | * | * | * | * | * |
Extended Warranty Additional 1 year for Transmitter Only | 01 | * | * | * | * | * | * |
Extended Warranty Additional 2 years for Transmitter Only | 02 | * | * | * | * | * | * |
Extended Warranty Additional 3 years for Transmitter Only | 03 | * | * | * | * | * | * |
Extended Warranty Additional 4 years for Transmitter Only | 04 | * | * | * | * | * | * |
Extended Warranty Additional 15 years for Transmitter Only | 15 | * | * | * | * | * | * |
¹The PM option is available on all Smartline Pressure Transmitter process wetted parts such as process heads, flanges, bushings and vent plugs except plated carbon steel process heads and flanges. PM option information is also available on diaphragms except Gold plated and STG and STA in-line construction pressure transmitters.
TABLE IX: Factory Identification
Factory | Manufacturing Specials | ||||||
---|---|---|---|---|---|---|---|
Factory Identification | 0000 | * | * | * | * | * | * |
Field Installable Accessory Kits
- Integrally Mounted Advanced Indicator Kit (compatible with all Electronic Modules)
- Standard Display Module
- Terminal Strip w/o Lightning Protection for HART or DE Modules
- Terminal Strip w/ Lightning Protection Kit for HART or DE Modules
- Terminal Strip w/o Lightning Protection FFB Module
- Terminal Strip w/ Lightning Protection Kit for FFB Module
- HART Electronics Module
- HART Electronics Module w/ connection for external configuration buttons
- DE Electronics Module
- DE Electronics Module w/ connection for external configuration buttons
- FFB Electronics Module Kit
- FFB Electronics Module w/ connection for external configuration buttons
Note P - For part number pricing please refer to WEB Channel
Product Manuals
- ST 800 SmartLine Transmitter User Manual - English
- ST 800 SmartLine Transmitter HART/DE Communications Manual - English
- ST 800 SmartLine Transmitter Safety Manual - English
- ST 800 SmartLine Transmitter Foundation Fieldbus Manual - English
- ST 800 SmartLine Transmitter Function Block Manual - English
All product documentation is available at www.honeywellprocess.com.
Sales and Service
For application assistance, current specifications, ordering, pricing, and name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
Honeywell Process Solutions,
Phone: + 800 12026455 or +44 (0) 1202645583
(TAC) hfs-tac-support@honeywell.com
Australia
Honeywell Limited
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36
Toll Free Fax:
1300-36-04-70
China - PRC - Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
EMEA
Honeywell Process Solutions,
Phone: + 800 12026455 or +44 (0) 1202645583
Email: (Sales) FP-Sales-Apps@Honeywell.com
or (TAC)
hfs-tac-support@honeywell.com
Web
Knowledge Base search engine http://bit.ly/2N5Vldi
AMERICAS
Honeywell Process Solutions,
Phone: (TAC) (800) 423-9883 or (215) 641-3610
(Sales) 1-800-343-0228
Email: (Sales) FP-Sales-Apps@Honeywell.com
or (TAC)
hfs-tac-support@honeywell.com
Web
Knowledge Base search engine http://bit.ly/2N5Vldi
Specifications are subject to change without notice.
For more information
To learn more about SmartLine Transmitters, visit www.process.honeywell.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road
Shanghai, China 20061
34-ST-03-83
September 2025
©2025 Honeywell International Inc.