LightGrid Node Outdoor Wireless Control System

Installation Guide CTRL044

STOP BEFORE YOU BEGIN

Read these instructions completely and carefully.

FCC Statements

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

To satisfy FCC/ISED RF exposure requirements a separation distance of 20 cm or more must be maintained between the antenna of this device and persons during operation. Operation at closer than 20 cm is not permitted.

CAN ICES-5 (B)/NMB-3(B)

This device complies with Industry Canada license-exempt RSS standards. Operation is subject to the following two conditions:

  • This device may not cause harmful interference, and
  • This device must accept any interference received, including interference that may cause undesired operation.

This device complies with Industry Canada license-exempt RSS standards. Its operation is subject to the following two conditions: This device must not cause interference, and This device must accept any interference, including interference that may cause undesired operation.

To comply with FCC/ISED RF exposure limits, a separation distance of at least 20 cm must be maintained between the antenna of this device and any person during operation. Operating this device closer than 20 cm is not permitted.

WARNING

RISK OF ELECTRIC SHOCK

Disconnect power before servicing or installing product.

RISK OF INJURY OR DAMAGE

Unit will fall if not installed properly. Follow installation instructions. Install in accordance with National Electric Code and local codes.

CAUTION

RISK OF INJURY

Wear safety glasses and gloves during installation and servicing.

Before Installation

  • Carefully unpack unit. Inspect for defects before installing.
  • Check electrical parameters. Ensure that the fixture operating wattage is below 1000W, and the voltage at the pole is within the allowed range of the Controller (range is listed on the sticker on the bottom of the controller). Using controller outside these parameters will void its warranty.
  • Verify that power to the luminaire is ON 24/7 constant power. The LightGrid mesh will not operate properly when operating on switched power from a master timer or photocell.
  • Confirm that the controller is the correct network ID for the system it is intended to join. This will be on the sticker on the bottom of the node, labeled as Net A, Net B, Net C ... this must match the other controllers in the area or the node will not join the network.
  • Install the gateways first. The startup and formation of the network is faster and smoother process when the Gateways are installed before starting to install Controllers.
  • Plan an installation route. Generally it is best to install controllers nearest to the gateways first, and then proceed outwards.

How to Install the LightGrid 2.x Controller

(The GESEM65-3 module is pictured below, however the instructions are applicable across the entire Select TXT™ Gen3 family of modules.)

  1. Check nearby poles. At the pole to be installed, confirm there is either a Gateway or another active LightGrid Controller within 1000Ft. This is important, to make sure the node has a connection path for communications and is within its RF range limits.
  2. Ensure Cellular Service is Accessible: Prior to installing cellular nodes verify with LightGrid support team that cellular service is available at the location, providing latitude and longitude coordinates.
  3. Plug in the node: Orient controller so large blade aligns with large slot in receptacle. Plug in, then twist clockwise until it is fully locked in place.

    Description: Controller plugged into receptacle, aligning large blade with large slot.

  4. Confirm the fixture dims during the first 60 seconds. When the controller is first plugged in, it will turn the luminaire ON and will then dim the luminaire. Before leaving the pole, you must visually confirm that you see the brightness of the luminaire drop, in order to confirm that dimming is working properly. Note: applies only to dimmable fixtures with an ANSI 5 Pin or 7 Pin socket. Fixtures with a standard 3 Pin socket will not be dimmable.
  5. Orient the Controller towards North: Lift up on the controller, which will also lift the receptacle with it. While lifting, rotate the controller and socket until the word North on the top of the controller is directed toward true North. Then lower the assembly back into place.

    Description: Controller rotated to align 'North' marking towards true North.

  6. Make sure red and yellow indicator LEDs are blinking. This confirms the controller is looking for a network to join.

    Description: Blinking red and yellow indicator LEDs confirm the controller is searching for a network.

Description: The GE current LightGrid Node is a compact, cylindrical device designed for outdoor wireless control.

Troubleshooting

SymptomSolution
The luminaire is not turning ON.Check that the pole has power. The relay inside the Controller is Normally Closed, so the luminaire will always turn ON when the controller is first plugged in.
I did not see the dimming sequence in the first 60 seconds.Unplug the controller, and try plugging it in again. If you still do not see the sequence, check that the dimming wires of the fixture (Grey & Violet) are properly connected to the dimming wires of the ANSI socket. If you confirm the wiring is connected and the controller still does not dim the luminaire, try another new controller.

Questions

Models: CTRL044, LightGrid Node Outdoor Wireless Control System, CTRL044 LightGrid Node Outdoor Wireless Control System, Outdoor Wireless Control System, Wireless Control System, Control System

File Info : application/pdf, 3 Pages, 285.10KB

PDF preview unavailable. Download the PDF instead.

CTRL044-LightGrid-Mesh-Cellular-Node-Installation-Guide

References

Adobe PDF Library 15.0

Related Documents

Preview LightGrid Gateway Installation Guide: Outdoor Wireless Control System Setup
Installation guide for the GE current LightGrid Gateway Outdoor Wireless Control System, covering setup, mounting, and connection procedures. Includes FCC and ISED compliance information.
Preview Evolve™ LED Roadway Light Installation Guide
Comprehensive installation guide for the GE current Evolve™ LED Roadway Light series (ERLC, ERL1, ERLH, ERL2), detailing mounting, wiring, handling, cleaning, and technical specifications. Includes safety warnings and regulatory compliance information.
Preview Arize® Life² LED Lighting System Installation Guide | GE current
Comprehensive installation guide for the GE current Arize® Life² LED Lighting System, covering safety, setup, wiring, and troubleshooting for horticultural and indoor lighting applications.
Preview Lumination LOP Series LED Suspended Luminaires - Product Specifications and Data
Detailed specifications, ordering information, dimensions, and photometric data for the GE current Lumination LOP Series LED suspended linear luminaires. Features TriGain® technology and Daintree wireless controls.
Preview Albeo ABV3-Series LED Luminaire Installation Guide | GE Current
Official installation guide for the GE Current Albeo ABV3-Series Modular High & Low Bay LED Luminaire. Includes safety warnings, electrical requirements, wiring instructions, and troubleshooting.
Preview Albeo LED Round High Bay IP65 Luminaire PRC Series Installation Guide
Installation guide for the Albeo LED Round High Bay IP65 Luminaire, PRC Series (Model ALB091). Provides essential safety warnings, installation instructions, wiring diagrams, and optional component guidance.
Preview GE Current Arize Element L1000 LED Grow Light: Specifications & Features
Discover the GE Current Arize Element L1000, an industrial-scale LED horticulture lighting system designed for efficient growth. Features high efficacy, precise light distribution, multiple spectrum options, and durable construction assembled in the USA. Learn about specifications, spectrums, and accessories.
Preview Daintree WMZ10 Wireless People Counting Sensor Installation Guide
Comprehensive installation guide for the Daintree WMZ10 Wireless People Counting Sensor by GE Current. Covers setup, wiring, mounting, compliance, and technical specifications for intelligent building environments.