INSTALLATION MANUAL
S311D-XX-L / S311D-XX-H Series
4, 6, 8, 11-digit display advanced digital totalizers - indicators
EN

SENECA s.r.l. Via Austria, 26 ­ 35127 ­ PADOVA ­ ITALY Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287 For manuals in other languages and the configuration software, visit www.seneca.it/products/s311d

MI00150-9-EN

1/9

MODULE LAYOUT


48 mm

96 mm

98 mm

Weight: 170 g; Enclosure: Self-extinguishing PC/ABS material, black.

BUTTON POSITION
4-6-8-11-DIGIT DISPLAY

A1: Alarm 1 LED A2: Alarm 2 LED
OK/MENU KEY

DOWN KEY

UP KEY

PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available at www.seneca.it/prodotti/s311d
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
2/9

TECHNICAL SPECIFICATIONS

STANDARDS

EN61000-6-4 Electromagnetic emissions, industrial environment. EN61000-6-2 Electromagnetic immunity, industrial environment. EN61010-1 Safety Install a fuse with a maximum capacity of 1 A near the module.

ENVIRONMENTAL CONDITIONS

Temperature: Humidity: Storage temperature: Protection rating:

-10 ÷ + 65°C 30% ÷ 90% non condensing. -20 + 85° IP65 (on the front with appropriate gasket)

INSULATION POWER SUPPLY

2500 Vdc between each pair of ports (including those belonging to the optional board)
S311D-XX-L: 10 ÷ 40 Vdc, 19 ÷ 28 Vac, 50 ÷ 60 Hz, max. 3 W S311D-XX-H: 85 ÷ 265 Vac, 50 ÷ 60 Hz, max. 3 W

CONNECTIONS Removable screw terminals, 3.5 mm/5.08 mm pitch

DIGITAL INPUT

Type: Reed, Npn (2 wires), npn 24 V (3 wires) or pnp 24 V (3 wires), NAMUR, Photoelectric (Astra), Hall, 24 V input, TTL, Variable reluctance. Absorbed current: max. 7 mA Vmax.: 28 Vdc Sensor power supply: 17 Vdc Frequency band: 0.00014 Hz ÷ 10 kHz Frequency resolution: < 0.05 %

ANALOGUE OUTPUT

Applied current: 0 ÷ 20 mA, max. load resistance 500 W Voltage: 0 ÷ 10 V, min. load resistance 1 kW Configurable start and end of scale Resolution: 2 mA / 1 mV Response time: 5 ms
Maximum measurement field errors: Calibration error: 0.1% Thermal coefficient: 0.01%/°K Linearity error: 0.05% EMI (electromagnetic interference): < 1%

DIGITAL OUTPUT Open Collector type, Imax: 50 mA, Vmax: 30 V

RELAY OUTPUT Capacity: 8 A / 250 Vac (available only on optional board) AUX. DIGITAL INPUT Optoinsulated, Vmin: 10 V, Vmax: 30 V (available only on optional board)

OPERATION DESCRIPTION
The measurement of the digital input frequency or the totalizer value is translated into an analogue or digital output signal. The frequency value or alternatively the totalizer value can also be viewed via the display; in the 11-digit model (4 + 7) both values can be displayed simultaneously (4 digits: frequency value, 7 digits: totalizer value). The values are also available via MODBUS-RTU protocol from the RS485 port (via optional board). Setting mode: All the parameters of the instrument can be set via the Programming Menu or RS485 (via optional board). The alarm thresholds can also be set quickly via the specific Quick Alarm Menu. The dedicated Easy Setup software for programming/ configuring the module was also developed (see www.seneca.it). Retransmission mode: The instrument accepts the following retransmission modes: Analogue output: The measurement of the frequency of the digital input is translated into an analogue output signal (current or voltage). Digital output: The output generates an impulse every time the totalization is increased or decreased. A pulse of duration  ~ 100 ms is generated. The output follows the totalizer up to the maximum value of approximately 4.7 Hz. As the counting frequency increases (up to the maximum value shown above), pulses are gradually lost until an output is obtained always at a low logic level. The output is normally high.
3/9

Alarms on frequency or totalizer measurement (optional board): Two alarms can be activated on the measurement of the frequency of the digital input signal or on the totalizer threshold values, each of which, if enabled, can be configured as follows: 1. Alarm on the minimum threshold. 2. Alarm on the maximum threshold. 3. Alarm on the minimum held threshold (does not automatically reset). 4. Alarm on the maximum held threshold (does not automatically reset). 5. Alarm on the totalizer threshold value (does not reset automatically). For each alarm it is possible to set threshold and hysteresis. For the totalizer alarm, the hysteresis is not considered. If the alarm is maximum the reset value is Threshold-Hysteresis, if it is minimum the reset value is Threshold + Hysteresis. The status of the alarms can be viewed via the two LEDs on the front panel and from the relays (if the optional board is used). The relays switch status when the alarm occurs and return to the initial state when it is reset (if held). The alarms held are reset in normal operation by pressing the UP + OK/MENU keys for a few seconds. For the totalizer alarm, the alarms are reset by pressing the UP+DOWN+ OK/MENU keys, via MODBUS or from the auxiliary digital input.
Totalizer As an alternative to measuring the frequency of the digital input signal, it is possible to view the value of the associated totalizer (saved in non-volatile memory). Both values are available simultaneously in the 11-digit indicators (4+7). The totalizer can be: Increasing: it is increased by one unit at each rising edge of the digital input. - Decreasing: it is decreased by one unit at each rising edge of the digital input. Once the maximum or minimum limit is reached, counting restarts from zero. It is also possible to set a reduction ratio by which to divide the totalizer value; the resulting value will then be displayed. Reset can also take place in the following three ways: - From auxiliary digital input (if enabled). - By pressing the three keys simultaneously (if enabled). - Via Modbus register.
Display of frequency measurement value or totalized value Three types of operation can be set (except for the 11-digit models that display both the frequency value and the totalizer value together) that define the display modes: 1. Type 0: both frequency value and totalizer value display. Pressing UP for a few seconds you access the frequency
display, pressing DOWN for a few seconds displays the totalized value. When passing to the frequency value for a few seconds the writing  appears, passing to the totalized value the writing  appears for a few seconds. 2. Type 1: frequency measurement display only. 3. Type 2: totalizer display only
Average and frequency measurement filtering The frequency value can be averaged over a settable number of samples. The average value is then filtered through the 20-level exponential filter and then shown on the display.
VLF Mode If the full scale in Hz for measuring the frequency (HI-F)  1 Hz the instrument goes to Very Low Frequency Mode (VLF) thanks to which the minimum detectable frequency value is equal to 0.00015 Hz (1 pulse every 111 minutes).
Password to access the menu It is possible to enable password protection from the Programming Menu. The Quick Alarm Menu is always free of passwords.
4/9

ELECTRICAL CONNECTIONS

POWER SUPPLY S311D-XX-L

10 ÷ 40 Vdc

1

19 ÷ 28 Vac

3.0 W

2A

S311D-XX-H

85 ÷ 265 Vac

1

3.0 W

2B

DIGITAL INPUT REED
07 08 09 10

NPN (2 WIRES) NPN 24 V (3 WIRES) PNP 24 V (3 WIRES)

07

+

08

09

- 10

+ 07 S 08
09
- 10

+ 07
08 S 09
- 10

NAMUR

+

07 08

09

- 10

VARIABLE RELUCTANCE

07

V

08

09

V > 100 mV

10

24 V INPUT

07

08

+

09

10

TTL INPUT

07

08

+

09

10

HALL
+ 07 S 08
09
- 10

PHOTOELECTRIC

Brown
07

08

White

09

Green

External R. 1K

10

The internal power supply for the sensors, equal to 17 Vdc, is available at terminals 7 (+) and 10 (-).

ANALOGUE OUTPUT

VOLTAGE

APPLIED CURRENT

EXTERNAL POWER SUPPLY

+

03 +

03

03

V

04

A

04

04

05

05

+

05

06

06

06

Active output: already powered to Passive output: not powered to be be connected to passive inputs connected to active inputs.

DIGITAL OUTPUT

I

+ I

03

R

04

-

05

+

06

I max: V / R = 50 mA

OPTIONAL BOARD CONNECTIONS

RS485

RELAY OUTPUT 1 8 A / 250 Vdc

B

21 N.C.

13

A

20 N.O.

12

GND

19 Com

11

RELAY OUTPUT 2 8 A / 250 Vdc

N.C.

16

N.O.

15

Com

14

Auxiliary input:
Totalizer reset (external power supply)

Example: Totalizer reset with power supplied entirely by the module
17

24 V
I V ext +

18 D17 D+

07 10

18

5/9

MENU PARAMETERS

DISPLAY DIGITS 4 6 8
11 (4+7)

FREQUENCY MEASUREMENT LIMITS:

MIN. LIMIT

MAX. LIMIT

-1999

9999

-199999

999999

-19999999

99999999

-1999

9999999

TOTALIZER LIMITS

MIN. LIMIT

MAX. LIMIT

0

9999

0

999999

0

99999999

0

9999999

Parameter code FUNC RE PA
type
H-f
dpn
L-d H-d dp_D FLt Au

PARAMETERS TO SET FROM THE MENU: C..n.F

Parameter name

SETTING RANGE AND DESCRIPTION

Type of instrument operation

0 = frequency and totalizer display function. 1 = only frequency measurement display function. 2 = only totalizer display function.

Enables panel totalizer reset and auxiliary digital input

0 = totalizer reset from panel and auxiliary digital input enabled. 1 = totalizer reset from panel and auxiliary digital input disabled.

Password enabling for By setting a value other than 5477, the password will be requested when

menu access

starting the menu (always 5477).

PARAMETERS TO SET FROM THE MENU: .n.P.t.

Input type
Full scale (Hz)
Position of decimal point in H-F

1= Reed 2= npn 2 wires 3= npn 24 V (3 wires) 4= pnp 24 V (3 wires) 5= NAMUR

6= Photoelectric (ASTRA) 7= HALL 8= 24 V input 9= TTL input 10= Variable reluctance

Full scale in Hz to measure frequency. It also defines the frequency value associated with the H-D parameter. Settable values The decimal point is imposed by DPN. Minimum value: 0,
Max value depending on the display: 4 / 11 (4+7) digits: 9999 (without decimal point). 6 / 8 digits: 10000 (without decimal point).

0 = no decimal point (e.g. 00009999), 1 = first digit (e.g. 0000999.9) 2 = second decimal point (e.g. 000099.99) 3 = third decimal point (e.g. 00009.999), 4 = fourth decimal digit (e.g. 0000.9999, only for 6 and 8 digit models).

PARAMETERS TO SET FROM THE MENU: s.C.a.L

Start of the scales displaying frequency
measurement

Frequency value displayed if the measured frequency is 0. Values within the limits see: TABLE1.

Full scales displaying frequency
measurement

Displayed frequency value if the measured frequency is H-f. Value within the limits see: TABLE1.

Frequency display decimal point position

0 = no decimal point (ex. 12345678), 1 = first digit (e.g. 1234567.8) ... ... N digits display-1
For 11-digit models (4+7): max number of decimal places equal to 3

Filter level

0= no filter

1 - 20

Number of samples on which to average the Selectable values: 1 -10.
frequency value

DEFAULT VALUE 0 = Instant. and
Totaliz. 0 = Enables 5477 = Password
disabled
3 = npn 24 V (3 wires)
1000 Hz
0 = Decimal point absent
0
1000
0 = Decimal point absent 3 1

6/9

PARAMETERS TO SET FROM THE MENU: A.L...anda.L.2..

Parameters related to alarm 1: accessible from menu a.L...and identified by final index 1. Parameters related to alarm 2: accessible from menu A.L...and identified by final index 2.

Parameter code Parameter name SETTING RANGE AND DESCRIPTION

et1 set2

Threshold for alarm 1. Threshold for alarm 1.

If frequency meter then frequency value shown on the display (decimal point imposed by d_Pd). Settable values between the limits of TABLE 1. If totalizer then totalizer value shown on the display. Settable values between the limits of TABLE 2.

HY1 HY2

Hysteresis for alarm 1. Hysteresis has no effect on the totalizer alarms. Hysteresis for alarm 2. Settable values between the limits of TABLE 1

tYp1 tYp2

Alarm 1 type Alarm 2 type

0 = Alarm not active 1 = Alarm on the minimum threshold 2 = Alarm on the maximum threshold 3 = Alarm on the minimum held threshold (does not automatically reset) 4 = Alarm on the maximum held threshold (does not automatically reset). 5 = Alarm on the totalizer threshold value. (does not automatically reset)

rLY1 rLY2

Relay 1: N.O. or N.C. Relay 2: N.O. or N.C.

Relay operation: 0 = relay normally open (N.O.) 1 = relay normally closed (N.C.).

L-t
H-t tYpe Addr PAr dEL baUd
CN UPDN DFL

PARAMETERS TO SET FROM THE MENU: .U.t..

Frequency display value associated with the minimum output
value
Frequency display value associated with the maximum output
value

Limits for scaling the retransmitted output see TABLE1. Decimal point imposed by dP-d.

Type of retransmitted 1= 0 ÷ 10 V

output

3= 0 ÷ 20 mA

2= 4 ÷ 20 mA 4= Totalizer digital output

PARAMETERS TO SET FROM THE MENU: b.U...

MODBUS Address Settable values: from 1 to 255.

Parity control type 0= None

1= Even

2= Odd

Delayed response time
Serial communication speed

Number of pauses of 6 characters each between the end of the Rx

message and the beginning of the Tx. Settable values: 0 ­ 255.

Serial communication speed in baud:

0= 1200

4= 14400

1= 2400

5= 19200

2= 4800

6= 38400

3= 9600

7= 57600

PARAMETERS TO SET FROM THE MENU: .Y...

Display contrast Values from 1 (minimum contrast) to 20 (maximum)

Totalizer type: Increasing or decreasing

0 = The totalizer increases by one unit at each rising edge of the digital input. 1 = The totalizer decreases by one unit at each rising edge of the digital input.

Default settings 1 = Overwrites the set parameters with the default values.

DEFAULT VALUE 500 100 10 10
0: Al 1 not active 0: Al 2 not active
0: N.O. 0: N.O.
0
1000 2 = 4 ÷ 20 mA
1 0 = None 0 = No delay
6 = 38400
10 0 = UP

7/9

PARAMETERS TO SET FROM THE MENU: t..t..

Parameter code rAt
dP_t

Parameter name

SETTING RANGE AND DESCRIPTION

Totalizer ratio

Sets a value by which to divide the totalizer. Permitted values: 1- 9999.

Decimal point position in the totalizer display

0 = no decimal point (e.g. 123456) 1 = first digit (e.g. 12345.6) 2 = second digit (e.g. 1234.56) ...... N digits display - 1
For 11-digit models (4+7): max number of decimal places equal to 6.

e.H..t

Confirming with OK/MENU you save all parameters on a flash card and, after a few moments, reset the module.

DEFAULT VALUE 1
0: No decimal point

SUMMARY OF BUTTON ACTIONS (in display mode)
Below is a summary of the actions that can be performed from the button starting from the display phase (not programming). In order for the actions to be carried out, the pressure on the buttons must last a few seconds.

Access to the programming menu.
If FunC=0 has been set, it switches to the frequency display (except 11-digit model)
Held alarm reset

Access to the Quick Alarm Menu
If FunC=0 has been set, it switches to the totalizer display (except for the 11-digit model) Totalizer reset (if this function has been enabled by setting rER=0 and reset of the alarms on the totalizer

ERROR REPORTING
Any errors are also shown directly on the display. Below are the possible warnings with their meaning. 0000: Frequency measurement value to be displayed > Hi-d value by 2.5% or if the frequency measurement value to be displayed is > maximum that can be displayed. EErr: It can signal an error of the calibration memory at startup. The operation of the instrument is blocked while ModBus communication is available (if optional board).
ORDER CODES

CODE

MODEL:

S311

4

6 DISPLAY
8

11

H POWER SUPPLY
L

O OPTIONS
T

DESCRIPTION Indicator - totalizer with universal digital input. 4 digits 6 digits 8 digits 4 + 7 digits 85 ÷ 265 Vac 10 ÷ 40 Vdc, 19 ÷ 28 Vac Optional board: RS485 Modbus port, 2 relay alarms and auxiliary digital input. Insulation: 1500 Vac between each port. Calibration and configuration service

CONTACT INFORMATION

Technical support

support@seneca.it

Product information

sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
8/9

EN: Programming menù diagram - IT: Schema menù di programmazione - ES: Esquema menù de programación - FR: Schéme de programmation - DE: ProgrammiermenÜ-Diagramm

Back to E.X.I.T.

C.O.n.F.

I.N.p.T

S.C.A.L.

A.L.1 .

A.L.2 .

O.u.t. .

B.U.S. .

S.Y.S. .

T.o.T. .

E.X.I.T

Back to C.o.n.F.

FunC
Change FUNC
IrES
Change IrES
PASS
Change PASS

tyPE
Change type
HI-F
Change HI-F
dPIn
Change DPIN

LO-d
Cange LO-d
HI-d
Change HI-d
dp_D
Change dp_d
FILt
Change FILT
FAAVHIR
Change AVI

Set1
Change SeT1
Hys1
Change HYS1
FTAyHp1R
Change tyP1
FRALHy1R
Change rLy1

Set2
Change SeT2
Hys2
Change HYS2
FTAyHp2R
Change tyP2
FRALHy2R
Change RLY2

SLeOt-2t
Change LO-t
HI-t
Change HI-t
type
Change type

ADDR
Change Addr
PAR
Change PAR
DEL
Change dEL
BAUD
Change bAUD

COnt
Change CONT
UPDN
Change UPdn
DFLT
Chande DFLT

RatI
Change rATI
dP_T
Change dp_T

0 9 9 4 0 9 9 5 0 9 9 6

0 9 9 6 0 9 8 6 0 9 9 6

0 9 9 6

0 9 9 6

- 9 9 6

Ú-1 9 9 6

- 9 9 6

: