Cantilever Arm FCA
FUS profiles with welded base plate for direct mounting on the base material.
Product Overview
The Fischer Cantilever Arm FCA is a robust metal profile designed for mounting pipelines. It features a welded base plate for secure attachment to base materials. Visuals depict the arm installed with a refrigerant pipe clamp on a sliding element and supporting a heavy pipe on a cantilever.
Applications
- Quick and easy installation of pipelines, for example, along the wall.
- For use in dry indoor areas. (FCA standard)
- For indoor and outdoor application. (FCA hdg)
- For indoor and outdoor application and in environments with high stress to components due to corrosion. (FCA A4)
Certificates
The product is certified with R 120 and R 30 MLAR.
Advantages
- The fire inspection report in line with MLAR/EN13501 guarantees independently tested functional safety.
- The graduated range of lengths allows for ideal adaptation to the application.
- The arm's solid base plate offers a secure hold for load-bearing construction.
- The base plate's long slots, which are at 90° to one another, allow for easy alignment.
- The stamped serration/teeth in the channel provide a secure hold for sliding nuts under high shear loads, e.g., for vertical installation.
Properties
FCA and FCA hdg Series
Material: steel S235JR (material no. 1.0037) according to DIN EN 10025
Zinc plating: electro zinc-plated (FCA) or hot-dip galvanised (FCA hdg)
FCA A4 Series
Material: stainless steel A4 (material no. 1.4404)
Technical Data and Diagrams
FCA Series (Standard)
Technical drawings illustrate the dimensions and profiles for various FCA models, including FCA 21/2.0, FCA 41/2.0, FCA 41/2.5, FCA 62/2.5, FCA 21D/2.0, FCA 41D/2.0, and FCA 41D/2.5. These diagrams show the profile dimensions, length (L), base plate with slots, and overall measurements.
Item | Item no. | Fire test report | Profile | Length L [mm] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 21/2.0-200 | 537207 | 21/2.0 | 200 | 1 | |
FCA 21/2.0-300 | 537208 | 21/2.0 | 300 | 1 | |
FCA 21/2.0-450 | 537209 | 21/2.0 | 450 | 1 | |
FCA 41/2.0-300 | 559915 | 41/2.0 | 300 | 1 | |
FCA 41/2.0-450 | 559916 | 41/2.0 | 450 | 1 | |
FCA 41/2.0-600 | 559917 | 41/2.0 | 600 | 1 | |
FCA 41/2.0-750 | 559918 | 41/2.0 | 750 | 1 | |
FCA 41/2.0-1,000 | 559919 | 41/2.0 | 1,000 | 1 | |
FCA 41/2.5-300 | 077359 | Yes | 41/2.5 | 300 | 1 |
FCA 41/2.5-450 | 077361 | Yes | 41/2.5 | 450 | 1 |
FCA 41/2.5-600 | 077363 | Yes | 41/2.5 | 600 | 1 |
FCA 41/2.5-750 | 077365 | Yes | 41/2.5 | 750 | 1 |
FCA 62/2.5-1,000 | 504315 | Yes | 62/2.5 | 1,000 | 1 |
FCA 21D/2.0 - 300 | 536978 | 21D/2.0 | 300 | 1 | |
FCA 21D/2.0 - 450 | 536979 | 21D/2.0 | 450 | 1 | |
FCA 21D/2.0 - 600 | 536980 | 21D/2.0 | 600 | 1 | |
FCA 41D/2.0 - 750 | 559920 | 41D/2.0 | 750 | 1 | |
FCA 41D/2.0 - 1000 | 559921 | 41D/2.0 | 1,000 | 1 | |
FCA 41D/2.5 - 750 | 504317 | 41D/2.5 | 750 | 1 | |
FCA 41D/2.5 - 1,000 | 504319 | 41D/2.5 | 1,000 | 1 |
FCA hdg Series (Hot-dip galvanized)
Technical drawings illustrate the dimensions and profiles for FCA hdg models, including FCA 41/2.5 hdg, FCA 62/2.5 hdg, and FCA 41D/2.5 hdg. These diagrams show the profile dimensions, length (L), base plate with slots, and overall measurements.
Item | Item no. | Fire test report | Profile | Length L [mm] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 41/2.5-300 hdg | 517411 | Yes | 41/2.5 | 300 | 1 |
FCA 41/2.5-450 hdg | 517412 | Yes | 41/2.5 | 450 | 1 |
FCA 41/2.5-600 hdg | 517413 | Yes | 41/2.5 | 600 | 1 |
FCA 41/2.5-750 hdg | 517414 | Yes | 41/2.5 | 750 | 1 |
FCA 62/2.5 -1000 hdg | 538015 | Yes | 62/2.5 | 1,000 | 1 |
FCA 41D/2.5-750 hdg | 538016 | Yes | 41D/2.5 | 750 | 1 |
FCA 41D/2.5-1.000 hdg | 538017 | Yes | 41D/2.5 | 1,000 | 1 |
FCA A4 Series (Stainless Steel)
Technical drawings illustrate the dimensions and profiles for FCA A4 models, specifically FCA 41/2.5 A4. These diagrams show the profile dimensions, length (L), base plate with slots, and overall measurements.
Item | Item no. | Fire test report | Profile | Length L [mm] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 41/2.5 A4 - 300 | 505487 | Yes | 41/2.5 | 300 | 1 |
FCA 41/2.5 A4 - 450 | 505488 | Yes | 41/2.5 | 450 | 1 |
FCA 41/2.5 A4 - 600 | 505489 | Yes | 41/2.5 | 600 | 1 |
Loads
Load Case Descriptions
The load capacities are specified for three distinct load cases:
- Load Case 1: Force (F) applied at the end of the arm (length L).
- Load Case 2: Force (F) applied at the midpoint of the arm (L/2).
- Load Case 3: Uniformly distributed load (F = q x L) along the entire length (L).
Load Data (FCA Series)
Item | Item no. | Max. recommended static load case 1 Frec [kN] | Max. recommended static load case 2 Frec [kN] | Max. recommended static load case 3 Frec [kN] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 21/2.0-200 | 537207 | 1.43 | 0.72 | 1.43 | 1 |
FCA 21/2.0-300 | 537208 | 0.95 | 0.45 | 0.95 | 1 |
FCA 21/2.0-450 | 537209 | 0.65 | 0.21 | 0.65 | 1 |
FCA 41/2.0-300 | 559915 | 1.80 | 0.90 | 1.80 | 1 |
FCA 41/2.0-450 | 559916 | 1.20 | 0.60 | 1.20 | 1 |
FCA 41/2.0-600 | 559917 | 0.90 | 0.45 | 0.90 | 1 |
FCA 41/2.0-750 | 559918 | 0.72 | 0.36 | 0.72 | 1 |
FCA 41/2.0-1,000 | 559919 | 0.54 | 0.23 | 0.54 | 1 |
FCA 41/2.5-300 | 077359 | 1.80 | 0.90 | 1.80 | 1 |
FCA 41/2.5-450 | 077361 | 1.20 | 0.60 | 1.20 | 1 |
FCA 41/2.5-600 | 077363 | 0.90 | 0.45 | 0.90 | 1 |
FCA 41/2.5-750 | 077365 | 0.72 | 0.36 | 0.72 | 1 |
FCA 62/2.5-1,000 | 504315 | 1.25 | 0.62 | 1.25 | 1 |
FCA 21D/2.0 - 300 | 536978 | 1.83 | 0.92 | 1.83 | 1 |
FCA 21D/2.0 - 450 | 536979 | 1.24 | 0.62 | 1.24 | 1 |
FCA 21D/2.0 - 600 | 536980 | 0.92 | 0.46 | 0.92 | 1 |
FCA 41D/2.0 - 750 | 559920 | 2.50 | 1.25 | 2.50 | 1 |
FCA 41D/2.0 - 1000 | 559921 | 1.90 | 0.93 | 1.90 | 1 |
FCA 41D/2.5 - 750 | 504317 | 2.50 | 1.25 | 2.50 | 1 |
FCA 41D/2.5 - 1,000 | 504319 | 1.90 | 0.93 | 1.90 | 1 |
Load Data (FCA hdg Series)
Item | Item no. | Max. recommended static load case 1 Frec [kN] | Max. recommended static load case 2 Frec [kN] | Max. recommended static load case 3 Frec [kN] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 41/2.5-300 hdg | 517411 | 1.80 | 0.90 | 1.80 | 1 |
FCA 41/2.5-450 hdg | 517412 | 1.20 | 0.60 | 1.20 | 1 |
FCA 41/2.5-600 hdg | 517413 | 0.90 | 0.45 | 0.90 | 1 |
FCA 41/2.5-750 hdg | 517414 | 0.72 | 0.36 | 0.72 | 1 |
FCA 62/2.5 -1000 hdg | 538015 | 1.25 | 0.62 | 1.25 | 1 |
FCA 41D/2.5-750 hdg | 538016 | 2.50 | 1.25 | 2.50 | 1 |
FCA 41D/2.5-1.000 hdg | 538017 | 1.90 | 0.64 | 1.90 | 1 |
Load Data (FCA A4 Series)
Item | Item no. | Max. recommended static load case 1 Frec [kN] | Max. recommended static load case 2 Frec [kN] | Max. recommended static load case 3 Frec [kN] | Sales unit [pcs] |
---|---|---|---|---|---|
FCA 41/2.5 A4 - 300 | 505487 | 1.80 | 0.90 | 1.80 | 1 |
FCA 41/2.5 A4 - 450 | 505488 | 1.20 | 0.60 | 1.20 | 1 |
FCA 41/2.5 A4 - 600 | 505489 | 0.90 | 0.45 | 0.90 | 1 |
Load Curves
The document includes load curves for various FCA series, plotting Force (F) in Newtons [N] against Length (L) in millimeters [mm]. These graphs illustrate the maximum static load capacity under different load cases:
- FCA 21 / FCA 21D: Curves show capacity for Load Case 1+3 and Load Case 2.
- FCA 41 / FCA 41D: Curves show capacity for Load Case 1+3 and Load Case 2.
- FCA 62 / FCA 62/2.5: Curves show capacity for Load Case 1+3 and Load Case 2.
These curves are based on permissible steel strain (adm. = 160 N/mm²) and maximum deflection (L/150), considering the load capacity of the base plate. Fixings and screw fastenings must be calculated accordingly. The load curves are valid for all material thicknesses of the FCA brackets.