Carrier Aquasmart 30EX(V) Chiller Datasheet
This document provides detailed specifications for the Carrier Aquasmart 30EX(V) chiller.
Product Overview
The Carrier Aquasmart 30EX(V) is a high-efficiency chiller designed for various cooling applications. It features advanced technology for optimal performance and energy savings.
Master Specifications
Model: 30EVA15226MAH---S
- Cooling Capacity: 12.00 Tons
- Total Unit Power: 13.61 KW
- Unit Voltage: 220 V
- Full Load EER (BTU/W): 10.57
- IPLV EER (BTU/W): 17.40
- Minimum Capacity: 16%
- Chiller Pressure Drop: 0.37 PSI
- Fluid Flow (GPM): 28.97
- Refrigerant: R-410A
- Refrigerant Charge: 27.1 lb
- Operating Weight: 665.8 lb
- Chassis Dimensions: 35.43 x 33.85 x 68.62 inches
Compressor Details
- Model: Scroll
- Quantity: 2
- RPM (60Hz): 3500 rpm
- Oil Charge: 1.65 (Poliol Éster)
- Recommended Oil: Copeland Ultra 22CC
- Crankcase Heater: 90 W
Electrical Information
Parameter | Value |
---|---|
Model | 30EVA15 |
Voltage (V) | 220 |
Fan Motor Quantity | 2 |
Compressor Amps (A) | 40.3 |
Maximum Compressor Amps (A) | 51.3 |
Total Compressor Power (W) | 12450 |
Maximum Compressor Power (W) | 16140 |
Fan Motor Quantity | 1 |
Full Load Amps (A) | 7.1 |
Total Fan Motor Power (W) | 1150 |
Total Unit Amps (A) | 47.4 |
Maximum Unit Amps (A) | 58.4 |
Total Unit Power (W) | 13600 |
Maximum Unit Power (W) | 17290 |
Notes:
- Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed minimum and maximum limits. Supplied voltage limit is ± 10%. Maximum allowable phase imbalance is: voltage, 2%; amps 10%.
- Check and follow all electrical and safety codes for installing, starting up, and servicing this equipment.
- Rated in accordance with AHRI Standard 550/590 at standard rating conditions.
- Maximum Unit Power (W) and Maximum Unit Amps (A) must be used for wire sizing.
System Specifications
- Cooling Capacity: 12.00 Tons
- Total Unit Power: 13.61 KW
- Unit Voltage: 220 V
- Full Load EER (BTU/W): 10.57
- IPLV EER (BTU/W): 17.40
- Minimum Capacity: 16%
- Leaving Water Temperature (°F): 44
- Entering Water Temperature (°F): 54.00
- Entering Air Temperature (°F): 95.00
- Altitude (ft): 0
Dimensions
Diagram showing the external dimensions of the chiller unit. Key dimensions include:
- Height: 1744 mm (68.66 inches)
- Width: 862 mm (33.94 inches)
- Depth: 990 mm (38.98 inches)
Coil Information:
- Face Area: 32.83 ft²
- Rows: 2
- Outside Diameter: 9.5mm / 3/8 in
- Fins per inch: 20 FPI
- Model: Al GoldFin fins and Cu tubes
Fan Information:
- Model/Quantity: Axial / 1
- RPM (60Hz): Variable between 160 - 860
- Air Flow (CFM): 1766 - 9417
- External Pressure Drop: 0 mmca
- Model/Quantity: 1 / BLDC
- Power (W): 850
Evaporator Information:
- Model: Arm plate in stainless steel
- Net Fluid Volume: 1.8 gal
- Maximum Water-Side Pressure: 145.03 psi
- Water Connections: Type Victaulic 63.5 (2 in)
IPLV - Integrated Part Load Value
AquaSmart 15TR inverter
Load | Capacity (TR) | Power (KW) | EER (Btu/h/W) | COP | KW/TR | Outside Air (°F) |
---|---|---|---|---|---|---|
100% | 12.00 | 13.56 | 10.62 | 3.11 | 1.13 | 95.00 |
75% | 9.00 | 10.11 | 14.24 | 4.17 | 0.85 | 80.00 |
50% | 6.00 | 7.44 | 19.35 | 5.67 | 0.62 | 65.00 |
25% | 3.00 | 6.90 | 20.88 | 6.12 | 0.57 | 55.00 |
- IPLV (EER): 17.30
- IPLV (COP): 5.070
- IPLV (KW/TR): 0.696
AquaSmart 15TR fixed
Load | Capacity (TR) | Power (KW) | EER (Btu/h/W) | COP | KW/TR | Outside Air (°F) |
---|---|---|---|---|---|---|
100% | 14.60 | 16.56 | 10.58 | 3.10 | 1.13 | 95.00 |
75% | 10.95 | 8.66 | 15.19 | 4.45 | 0.84 | 80.00 |
50% | 7.30 | 4.64 | 18.88 | 5.53 | 0.64 | 65.00 |
25% | 3.65 | 2.23 | 18.73 | 5.49 | 0.64 | 55.00 |
- IPLV (EER): 17.23
- IPLV (COP): 5.050
- IPLV (KW/TR): 0.713
Operational Limits
Parameter | Unit | 30EV 15 | 30EX 15 |
---|---|---|---|
Minimum flow on evaporator | gpm | 18.5 | 19.5 |
Maximum flow on evaporator | gpm | 67.3 | 80.1 |
Maximum outdoor temperature | °F | 113 | 113 |
Minimum outdoor temperature | °F | 50 | 50 |
Maximum REWT (evaporator) | °F | 95 | 95 |
Minimum REWT (evaporator) | °F | 42.8 | 42.8 |
Maximum ULWT (evaporator) | °F | 95 | 95 |
Minimum ULWT (evaporator) | °F | 41 | 41 |
Minimum temperature delta | °F | 5.4 | 5.4 |
Maximum temperature delta | °F | 18 | 18 |
Accessories and Control
- Accessories: Y filter + Victaulic connection included
- Control: Human Interface Control / No Communication Option