Rich Solar MPPT Solar Charge and Discharge Controller User Manual

Maximum Power Point Tracking (MPPT) Series

Models: RS-MPPT20, RS-MPPT30, RS-MPPT40

Safety Instructions

  1. As this controller deals with voltages that exceed the top limit for human safety, do not operate it before reading this manual carefully and completing safety operation training.
  2. The controller has no internal components that need maintenance or service, thus do not attempt to disassemble or repair the controller.
  3. Install the controller indoors, and avoid component exposure and water intrusion.
  4. During operation, the radiator may reach a very high temperature, therefore install the controller at a place with good ventilation conditions.
  5. It's recommended that a fuse or breaker be installed outside the controller.
  6. Before installing and wiring the controller, make sure to disconnect the photovoltaic array and the fuse or breaker close to the battery terminals.
  7. After installation, check if all connections are solid and reliable so as to avoid loose connections that may give rise to dangers caused by heat accumulation.

Warning: means the operation in question is dangerous, and you should get properly prepared before proceeding.

Note: means the operation in question may cause damage.

Tips: means advice or instruction for the operator.

Product Overview

This product can keep monitoring the solar panel's generating power and tracking the highest voltage and current values (VI) in real time, enabling the system to charge the battery in maximum power. It's designed to be used in off-grid solar photovoltaic systems to coordinate operation of the solar panel, battery and load, functioning as the core control unit in off-grid photovoltaic systems.

This product features an LCD screen which can dynamically display the operating status, operating parameters, controller logs, control parameters, etc. Users can conveniently check parameters by the keys, and modify control parameters to cater to different system requirements.

The controller utilizes standard Modbus communication protocol, making it easy for users to check and modify system parameters on their own. By providing free monitoring software, Rich Solar offers users maximum convenience to satisfy their varied needs for remote monitoring.

With comprehensive electronic fault self-detecting functions and powerful electronic protection functions built inside the controller, component damage caused by installation errors or system failures can be avoided to the greatest extent possible.

Product Features

Introduction to Maximum Power Point Tracking Technology

Maximum Power Point Tracking (MPPT) is an advanced charging technology that enables the solar panel to output more power by adjusting the electric module's operating status. Due to the nonlinearity of solar arrays, there exists a maximum energy output point (maximum power point) on their curves. Unable to continuously lock onto this point to charge the battery, conventional controllers (employing switching and PWM charging technologies) can't get the most of the power from the solar panel. But a solar charge controller featuring MPPT technology can continuously track arrays' maximum power point so as to get the maximum amount of power to charge the battery.

Take a 12V system as an example. As the solar panel's peak voltage (Vpp) is approximately 17V while the battery's voltage is around 12V, when charging with a conventional charge controller, the solar panel's voltage will stay at around 12V, failing to deliver the maximum power. However, the MPPT controller can overcome the problem by adjusting the solar panel's input voltage and current in real time, realizing a maximum input power.

Charging Stages Introduction

As one of the charging stages, MPPT can not be used alone, but has to be used together with boost charging, floating charging, equalizing charging, etc. to complete charging the battery. A complete charging process includes: fast charging, sustaining charging and floating charging. The charging curve is as shown below:

a) Fast charging

At the fast charging stage, as the battery voltage has not reached the set value of full voltage (i.e. equalizing / boost voltage) yet, the controller will perform MPPT charging on the battery with the maximum solar power. When the battery voltage reaches the preset value, constant voltage charging will begin.

b) Sustaining charging

When the battery voltage reaches the set value of sustaining voltage, the controller will switch to constant voltage charging. In this process, no MPPT charging will be performed, and meanwhile the charging current will also gradually decrease. The sustaining charging stage itself consists of two sub-stages, i.e. equalizing charging and boost charging, the two of which are not carried out in a repeated manner, with the former getting activated once every 30 days.

> Boost charging

By default, boost charging generally lasts for 2h, but users can adjust preset values of duration and boost voltage point according to the actual needs. When the duration reaches the set value, the system will then switch to floating charging.

> Equalizing charging

Warning: risk of explosion! In equalizing charging, an open lead-acid battery can produce explosive gas, therefore the battery chamber shall have good ventilation conditions.

Note: risk of equipment damage! Equalizing charging may raise the battery voltage to a level that may cause damage to sensitive DC loads. Check and make sure that allowable input voltages of all the loads in the system are greater than the set value for battery equalizing charging.

Note: risk of equipment damage! Overcharge or too much gas generated may damage battery plates and cause active material on the battery plates to scale off. Equalizing charging to an excessively high level or for too long a period may cause damage. Read carefully the actual requirements of the battery deployed in the system.

Some types of batteries benefit from regular equalizing charging which can stir the electrolyte, balance the battery voltage and finish the electrochemical reaction. Equalizing charging raises the battery voltage to a higher level than the standard supply voltage and gasify the battery electrolyte. If the controller then automatically steers the battery into equalizing charging, the charging duration is 120 mins (default). In order to avoid too much generated gas or battery overheat, equalizing charging and boost charging won't repeat in one complete charging cycle.

Note:

  1. When due to the installation environment or working loads, the system can't continuously stabilize the battery voltage to a constant level, the controller will initiate a timing process, and 3 hours after the battery voltage reaches the set value, the system will automatically switch to equalizing charging.
  2. If no calibration has been done to the controller clock, the controller will perform equalizing charging regularly according to its internal clock.

> Floating charging

When finishing the sustaining charging stage, the controller will switch to floating charging in which the controller lowers the battery voltage by diminishing the charging current and keeps the battery voltage at the set value of floating charging voltage. In the floating charging process, very light charging is carried out for the battery to maintain it at full state. At this stage, the loads can access almost all the solar power. If the loads consume more power than the solar panel could provide, the controller will not be able to keep the battery voltage at the floating charging stage. When the battery voltage drops to the set value for returning to boost charging, the system will exit floating charging and reenter into fast charging.

Installation Precautions

Wiring Specifications

Wiring and installation methods must comply with national and local electrical specifications. The wiring specifications of the battery and loads must be selected according to rated currents, and see the following table for wiring specifications:

Model Rated charging current Rated discharging current Battery wire diameter (mm²) Load wire diameter (mm²)
RS-MPPT20 20A 20A 5 mm² 5 mm²
RS-MPPT30 30A 20A 6 mm² 5 mm²
RS-MPPT40 40A 20A 10 mm² 5 mm²

Installation and Wiring

Warning: risk of explosion! Never install the controller and an open battery in the same enclosed space! Nor shall the controller be installed in an enclosed space where battery gas may accumulate.

Warning: danger of high voltage! Photovoltaic arrays may produce a very high open-circuit voltage. Open the breaker or fuse before wiring, and be very careful during the wiring process.

Note: when installing the controller, make sure that enough air flows through the controller's radiator, and leave at least 150 mm of space both above and below the controller so as to ensure natural convection for heat dissipation. If the controller is installed in an enclosed box, make sure the box delivers reliable heat dissipation effect.

Step 1: choose the installation site

Do not install the controller at a place that is subject to direct sunlight, high temperature or water intrusion, and make sure the ambient environment is well ventilated.

Step 2: first place the installation guide plate at a proper position, use a marking pen to mark the mounting points, then drill 4 mounting holes at the 4 marked points, and fit screws in.

Step 3: fix the controller

Aim the controller's fixing holes at the screws fit in Step 2 and mount the controller on.

Step 4: wire

First remove the two screws on the controller, and then begin wiring operation. In order to guarantee installation safety, Rich Solar recommends the following wiring order; however, you can choose not to follow this order and no damage will be incurred to the controller.

Connecting to external temperature sampling interface

Connecting communication cable

Connecting power cable

Warning: risk of electric shock! We strongly recommend that fuses or breakers be connected at the photovoltaic array side, load side and battery side so as to avoid electric shock during wiring operation or faulty operations, and make sure the fuses and breakers are in open state before wiring.

Warning: danger of high voltage! Photovoltaic arrays may produce a very high open-circuit voltage. Open the breaker or fuse before wiring, and be very careful during the wiring process.

Warning: risk of explosion! Once the battery's positive and negative terminals or leads that connect to the two terminals get short-circuited, a fire or explosion will occur. Always be careful in operation.

First connect the battery, then the load, and finally the solar panel. When wiring, follow the order of first "+" and then "-".

Power on

After connecting all power wires solidly and reliably, check again whether wiring is correct and if the positive and negative poles are reversely connected. After confirming that no faults exist, first close the fuse or breaker of the battery, then see whether the LED indicators light up and the LCD screen displays information. If the LCD screen fails to display information, open the fuse or breaker immediately and recheck if all connections are correctly done.

If the battery functions normally, connect the solar panel. If sunlight is intense enough, the controller's charging indicator will light up or flash and begin to charge the battery.

After successfully connecting the battery and photovoltaic array, finally close the fuse or breaker of the load, and then you can manually test whether the load can be normally turned on and off. For details, refer to information about load working modes and operations.

Warning: when the controller is in normal charging state, disconnecting the battery will have some negative effect on the DC loads, and in extreme cases, the loads may get damaged.

Warning: within 10 minutes after the controllers stops charging, if the battery's poles are reversely connected, internal components of the controller may get damaged.

Note:

  1. The battery's fuse or breaker shall be installed as close to the battery side as possible, and it's recommended that installation distance be not more than 150mm.
  2. If no remote temperature sensor is connected to the controller, the battery temperature value will stay at 25 °C.
  3. If an inverter is deployed in the system, directly connect the inverter to the battery, and do not connect it to the controller's load terminals.

Product Operation and Display

LED Indicators

PV array indicator: Indicating the controller's current charging mode.

BAT indicator: Indicating the battery's current state.

LOAD indicator: Indicating the loads' On/ Off and state.

ERROR indicator: Indicating whether the controller is functioning normally.

PV array indicator:

No. Graph Indicator state Charging state
BULK Steady on MPPT charging
ACCEPTANCE Slow flashing (a cycle of 2s with on and off each lasting for 1s) Boost charging
FLOAT Single flashing (a cycle of 2s with on and off lasting respectively for 0.1s and 1.9s) Floating charging
M EQUALIZE Quick flashing (a cycle of 0.2s with on and off each lasting for 0.1s) Equalizing charging
M CURRENT-LIMITED Double flashing (a cycle of 2s with on for 0.1s, off for 0.1s, on again for 0.1s, and off again for 1.7s) Current-limited charging
9 Off No charging

BAT indicator:

Indicator state Battery state
Steady on Normal battery voltage
Slow flashing (a cycle of 2s with on and off each lasting for 1s) Battery over-discharged
Quick flashing (a cycle of 0.2s with on and off each lasting for 0.1s) Battery over-voltage

LOAD indicator:

Indicator state Load state
Off Load turned off
Quick flashing (a cycle of 0.2s with on and off each lasting for 0.1s) Load overloaded/ short-circuited
Steady on Load functioning normally

ERROR indicator:

Indicator state Abnormality indication
Off System operating normally
Steady on System malfunctioning

Key Operations

LCD Startup and Main Interface

During startup, the 4 indicators will first flash successively, and after self-inspection, the LCD screen starts and displays the battery's voltage level which will be either a fixed voltage selected by the user or a voltage automatically recognized.

Main interface

Main monitoring page:

Component voltage Charging current
12.3 90.6 0.00 A

Abnormality code:

Battery voltage Battery capacity
EO 12.3 100%

Load current:

Charging capacity
0.00 21 Ah

Device temperature:

Discharging capacity
15 40 9 Ah

Load Mode Setting Interface

Load modes introduction

This controller has 5 load operating modes which will be described below:

No. Mode Descriptions
0 Sole light control (nighttime on and daytime off) When no sunlight is present, the solar panel voltage is lower than the light control on voltage, and after a time delay, the controller will switch on the load; when sunlight emerges, the solar panel voltage will become higher than the light control off voltage, and after a time delay, the controller will switch off the load.
1~14 Light control + time control 1 to 14 hours
15 Manual mode In this mode, the user can switch the load on or off by the keys, no matter whether it's day or night. This mode is designed for some specially purposed loads, and also used in the debugging process.
16 Debugging mode Used for system debugging. With light signals, the load is shut off; without light signals, the load is switched on. This mode enables fast check of the correctness of system installation during installation debugging.
17 Normal on mode The energized load keeps outputting, and this mode is suitable for loads which need 24-hour power supply.

Load mode adjustment

Users can adjust the load mode as needed on their own, and the default mode is debugging mode (see "load modes introduction"). The method for adjusting load modes is as follows:

Press and hold the Set key to enter

Tap the Up or Down key to set the mode

Press and hold the Set key to save and exit

Tap the Return key to exit without saving,

Manual load on/ off page

Manual operation is effective only when the load mode is manual mode (15), and tap the Set key to switch on/ off the load under any main interface.

System Parameter Settings

Under any interface other than load modes, press and hold the Set key to enter into the parameter setting interface.

Note: after system voltage setting, power supply has to be switch off and then on again, otherwise the system may work under an abnormal system voltage.

The controller enables users to customize the parameters according to the actual conditions, but parameter setting must be done under the guidance of a professional person, or else faulty parameter settings may render the system not able to function normally. For details about parameter settings, see table 3

No. Displayed item Description Parameter range Default setting
1 TYPE OF BAT Battery type User/flooded/Sealed/Gel/Li Sealed
2 VOLT OF SYS System voltage 12V/24V AUTO
3 EQUALIZ CHG Equalizing charging voltage 9.0~17.0V 14.6V
4 BOOST CHG Boost charging voltage 9.0~17.0V 14.4V
5 FLOAT CHG Floating charging voltage 9.0~17.0V 13.8V
6 LOW VOL RECT Over-discharge recovery voltage 9.0~17.0V 12.6V
7 LOW VOL DISC Over-discharge voltage 9.0~17.0V 11.0V

Product Protection Function and System Maintenance

Protection Functions

System Maintenance

In order to always keep the controller's performance at its optimum level, Rich Solar recommends that the following items be checked twice a year.

Warning: risk of electric shock! Before carrying out the above checkings or operations, always make sure all power supplies of the controller have been cut off!

Product Specification Parameters

Electric Parameters

Parameter RS-MPPT20 RS-MPPT30 RS-MPPT40
Model 12V/24VAuto
System voltage 12V/24VAuto
No-load loss 0.7 W to 1.2W
Battery voltage 9V to 35V
Max. solar input voltage 100V(25°C) 90V(-25°C) 100V(25°C) 90V(-25°C) 100V(25°C) 90V(-25°C)
Max. power point voltage range Battery Voltage+2V to 75V
Rated charging current 20A 30A 40A
Rated load current 20A
Max. capacitive load capacity 10000uF
Max. photovoltaic system input power 260W/12V 520W/24V 400W/12V 800W/24V 600W/12V 1100W/24V
Conversion efficiency ≤98%
MPPT tracking efficiency > 99%
Temperature compensation factor -3mv//2V default
Operating temperature -35 to +45 °C
Protection degree IP32
Weight 1.4Kg 2Kg 2Kg
Communication method RS232
Altitude ≤ 3000m
Product dimensions 210*151*59.5mm 238*173*72.5mm 238*173*72.5mm

Battery Type Default Parameters

When selecting User, the battery type is to be self-customized, and in this case, the default system voltage parameters are consistent with those of the sealed lead-acid battery. When modifying battery charging and discharging parameters, the following rule must be followed:

Over-voltage cut-off voltage > Charging limit voltage > Equalizing voltage > Boost voltage > Floating charging voltage > Boost return voltage;

Over-voltage cut-off voltage > Over-voltage cut-off return voltage;

Low-voltage cut-off return voltage > Low-voltage cut-off voltage > Discharging limit voltage;

Under-voltage warning return voltage > Under-voltage warning voltage > Discharging limit voltage;

Boost return voltage > Low-voltage cut-off return voltage

Voltage to set Battery type Sealed lead-acid battery Gel lead-acid battery Open lead-acid battery Li battery User (self-customized)
Over-voltage cut-off voltage 16.0V 16.0V 16.0V 9~17V 9~17V
Equalizing voltage 14.6V 14.8V 14.6V 9~17V 9~17V
Boost voltage 14.4V 14.2V 14.6V 14.4V 9~17V
Floating charging voltage 13.8V 13.8V 13.8V 9~17V 9~17V
Boost return voltage 13.2V 13.2V 13.2V 9~17V 9~17V
Low-voltage cut-off return voltage 12.6V 12.6V 12.6V 12.6V 9~17V
Under-voltage warning voltage 12.0V 12.0V 12.0V 12.0V 9~17V
Low-voltage cut-off voltage 11.1V 11.1V 11.1V 11.1V 9~17V
Discharging limit voltage 10.6V 10.6V 10.6V 10.6V 9~17V
Over-discharge time 5s 5s 5s 1~30s 1~30s
Equalizing charging duration 120 minutes 120 minutes 120 minutes 0~600 minutes 0~600 minutes
Equalizing charging interval 30 days 0 days 30 days (0 means the equalizing charging function is disabled) (0 means the equalizing charging function is disabled)
Boost charging duration 120 minutes 120 minutes 120 minutes 10~600 minutes 10~600 minutes

Conversion Efficiency Curve

12V System Conversion Efficiency

A graph showing the conversion efficiency (%) versus output power (W) for the MPPT 12V conversion efficiency (12V battery) at different Vmp values (20 Vmp, 40 Vmp, 60 Vmp, 75 Vmp).

24V System Conversion Efficiency

A graph showing the conversion efficiency (%) versus output power (W) for the MPPT 24V conversion efficiency (24V battery) at different Vmp values (40 Vmp, 50 Vmp, 60 Vmp, 75 Vmp).

Product Dimensions

Diagrams and specifications for the dimensions of the RS-MPPT30/RS-MPPT40 and RS-MPPT20 models, including product dimensions, hole positions, hole diameter, and applicable wire size.

Models: 30A, 40A, MPPT Solar Charge Controller, MPPT, Solar Charge Controller, Charge Controller, Controller

File Info : application/pdf, 10 Pages, 969.42KB

PDF preview unavailable. Download the PDF instead.

20A 30A 40A MPPT Solar Charge Controller Manaul adbc78d0-4928-4b06-a0bd-52f92076c261 ?v=1718730056 Adobe PDF library 15.00

Related Documents

Preview Rich Solar PWM Charge Controller User Manual
User manual for Rich Solar PWM charge controllers (RS-PWM30P, RS-PWM40P, RS-PWM50P, RS-PWM60P), detailing features, operation, safety, troubleshooting, and specifications for solar energy systems.
Preview Rich Solar Off-Grid Solar Inverter RS-H3000 Series User Manual
Comprehensive user manual for Rich Solar RS-H3000 series off-grid solar inverters (RS-H3000-24, RS-H3000-48). Covers installation, operation, safety instructions, parallel installation, fault codes, warnings, battery equalization, specifications, and troubleshooting.
Preview RICH SOLAR RS-MPPT30P User Manual: 30A MPPT Solar Charge Controller
Comprehensive user manual for the RICH SOLAR RS-MPPT30P 30A MPPT Solar Charge Controller, detailing installation, operation, safety precautions, charging stages, LED indicators, specifications, and features for efficient solar energy management.
Preview Rich Solar RS-MPPT50DC MPPT DC-DC Solar Charge Controller User Manual
User manual for the Rich Solar RS-MPPT50DC MPPT DC-DC solar charge controller. Covers product overview, features, specifications, installation, safety precautions, operation, and troubleshooting for efficient solar and alternator charging.
Preview Rich Solar RS-PWM30PF 30A PWM Solar Charge Controller User Manual
Comprehensive user manual for the Rich Solar RS-PWM30PF 30A PWM Solar Charge Controller, covering installation, operation, charging stages, specifications, and safety guidelines. Learn how to safely and efficiently manage your solar power system.
Preview Rich Solar 40A MPPT Solar Charge Controller RS-MPPT40P
Discover the Rich Solar 40A MPPT Solar Charge Controller (Model: RS-MPPT40P). Features advanced MPPT technology, intelligent system compatibility, comprehensive protection, and smart monitoring. Includes detailed specifications and proprietary technologies.
Preview Rich Solar 60A MPPT Solar Charge Controller - Features and Specifications
Detailed information on the Rich Solar 60A MPPT Solar Charge Controller, including its features, technical specifications, and connection diagram. This controller supports various battery voltages and offers advanced MPPT technology for high efficiency.
Preview Rich Solar RS-PWM40PF 40A PWM Solar Charge Controller User Manual
User manual for the Rich Solar RS-PWM40PF 40A PWM Solar Charge Controller, detailing features, installation, wiring, operation, charging stages, LED indications, and specifications.