Introduction
The Lenovo zero-U (0U) Basic and Switched and Monitored power distribution units (PDUs) are the ideal solutions when you need flexible, reliable, easy-to-deploy power distribution with branch circuit protection to minimize downtime. These rack-dense units distribute power to up to 48 outlets and 42 outlets. 0U PDUs are designed to be installed vertically in the rear channel of a Lenovo rack, thereby not consuming any horizontal rack space that otherwise be used by servers, storage and network switches (hence the term 0U).
Did you know?
With ever growing power densities in today's rack environments, it is all too easy to add load in the wrong place and trigger an overload event. The 0U Basic and Switched and Monitored PDU offerings can minimize this impact, providing the ability to quickly recover with resettable circuit breakers for each designated bank of receptacles, referred to as load groups. Breakers are color coded to the receptacles in a particular load group to aid in configuration, installation, and maintenance. Furthermore, the Basic PDUs offer a cost-effective option to users who do not require intelligence. The Switched and Monitored PDUs also offer individual outlet remote monitoring and switching (on/off), which allow for remote power sequencing and further helping to prevent unintended PDU overloading.
Introduction to PDUs
A power distribution unit (PDU) is a highly reliable, multiple outlet power strip designed to consolidate line cords within the rack and distribute conditioned power from an uninterruptible power supply (UPS) or utility power to servers and other IT equipment. The PDU efficiently distributes power within the rack and provides fault-tolerant power redundancy for high availability requirements.
Types of 0U PDUs
There are two types of 0U PDUs available from Lenovo. The PDUs covered in this document are:
- Basic PDUs: The simplest and most cost-effective power distribution. Available with various outlet configurations and line cord options to support different systems and load requirements.
- Switched & monitored PDUs: These are advanced power management solutions, providing power monitoring at the outlet level, with increased accuracy at low amperages, for more precise views of power consumption down to the individual server level instead of at the consolidated load group. These PDUs also offer management via a web-based interface which includes individual outlet switching (on/off). Outlet switching allows for remote power sequencing and helps prevent unintended PDU overloading.
Basic PDUs
The Basic PDUs offer a cost-effective option to users who do not require intelligence. Premium hydraulic-magnetic circuit breakers operate reliably in high temperature environments.
Table 1. Ordering part numbers
Part number | Feature Description | Region availability* |
---|---|---|
4PU7A93169 | 0U 36 C13 and 6 C19 Basic 32A 1 Phase PDU | International |
4PU7A93170 | 0U 24 C13/C15 and 24 C13/C15/C19 Basic 32A 3 Phase WYE PDU | International |
4XF7A93901 | 0U PDU Mounting Bracket for 9307 Rack | International |
* See region availability below
Region availability
PDUs indicated in Table 1 as available Internationally except for the following countries:
- Latin America (LAS): Argentina, Colombia, Mexico
- Europe (EMEA): Belarus, Kazakhstan, Kyrgyzstan, Moldova, Morocco, Russian Federation, South Africa, Ukraine and United Arab Emirate
- Asia Pacific (AP): Cambodia, Japan, Korea
Included with the PDUs
The PDUs include the following items:
- One Power Distribution Unit with an attached power cord
- Mounting hardware
- PDU warranty poster
- Safety guidelines
- Quick start guide
Figure 1. Lenovo 0U Basic PDUs
This figure displays two Lenovo 0U Basic PDUs. The top unit (part number 4PU7A93169) is a 36 C13 and 6 C19 outlet configuration. The bottom unit (part number 4PU7A93170) is a 24 C13/C15 and 24 C13/C15/C19 outlet configuration. Both are shown mounted vertically.
Features and specifications basic PDUs
The 0U Basic PDUs have the following common features:
- Advanced features, such as color-coded standard IEC outlets
- Enlogic's standard low-profile design
- Toolless mounting
- Operate reliably in high temperature environments.
Note: Network Management Module is not supported
Table 2. PDU specifications (Basic PDUs)
Feature | 0U 36 C13 and 6 C19 Basic 32A 1 Phase PDU | 0U 24 C13/C15 and 24 C13/C15/C19 Basic 32A 3 Phase WYE PDU |
---|---|---|
Part Number | 4PU7A93169 | 4PU7A93170 |
Region | International | International |
Input power | ||
Number of phases | Single phase input | Three phase input |
Line cord | Attached line cord, 3 m length (10 ft) | Attached line cord, 3 m length (10 ft) |
Line cord connector | IEC 60309 332P6 | IEC 60309 532P6 |
Plug design | Diagram showing plug with L, N, G pins. | Diagram showing plug with L1, L2, L3, N, G pins. |
Input voltage | 200-240V | 200-240V / 346-415v |
Input current | 30A (derated 24A) (NA) / 32A(EU) | 30A (derated 24A) (NA) / 32A(EU) |
Maximum power rating | 5 kVA / 7.40 kVA | 17.3 kVA / 22.10 kVA |
Output power | ||
Number of C13 outlets | 36x (C13) | 24x (C13/C15 combo) |
Number of C19 outlets | 6x (C19) | 24x (C13/C15/C19 combo) |
Output voltage rating at 50/60Hz | 200-240 VAC | 200-240 VAC |
Output current rating | Each C13 outlet: 10 amps; Each C19 outlet: 16 amps | Each C13 outlet: 10 amps; Each C19 outlet: 16 amps |
Circuit breakers | 2x 20A, single-pole electro mechanical switch | 6x 20A, single-pole electro mechanical switch |
Capacity per PDU (Amps) | 24A Total (NA) OR 32A Total (EU) | 24A Total (NA) OR 32A Total (EU) |
Mechanical and environmental | ||
Physical dimensions (L x W x D) | 1490 mm x 52 mm x 53 mm | 1490 mm x 56 mm x 75 mm |
Operating temperature | -5 to 60°C (23 to 140°F) | -5 to 60°C (23 to 140°F) |
Operating humidity | 5-90% RH / 5-95% RH; non-condensing | 5-90% RH / 5-95% RH; non-condensing |
Switched and Monitored PDUs
The following table provides the ordering part numbers for the 0U Switched and Monitored PDUs.
Table 3. Ordering part numbers and feature codes
Part number | Feature Description | Region availability* |
---|---|---|
4PU7A93171 | 0U 20 C13 and 4 C19 Switched and Monitored 32A 1 Phase PDU | International |
4PU7A93172 | 0U 16 C13/C15 and 16 C13/C15/C19 Switched and Monitored 24A 1 Phase PDU(30A derated) | NA* |
4PU7A93173 | 0U 18 C13/C15 and 18 C13/C15/C19 Switched and Monitored 32A 3 Phase WYE PDU | NA |
4PU7A93174† | 0U 21 C13/C15 and 21 C13/C15/C19 Switched and Monitored 48A 3 Phase Delta PDU (60A derated) | International** |
4PU7A93175† | 0U 18 C13/C15 and 18 C13/C15/C19 Switched and Monitored 63A 3 Phase WYE PDU | International |
4XF7A93184 | PDU Environmental Sensor- Temperature & Humidity | International |
4X97A93183 | PDU serial communication cable | International |
4XF7A93901 | 0U PDU Mounting Bracket for 9307 Rack | International |
* See region availability below
** Available in Canada, Taiwan, Vietnam and United States only
† Planned ship support for these PDUs is 2Q/2024
Region availability
PDUs indicated in Table above as available Internationally, or NA except for the following countries:
- Latin America (LAS): Argentina, Colombia, Mexico
- Europe (EMEA): Belarus, Kazakhstan, Kyrgyzstan, Moldova, Morocco, Russian Federation, South Africa, Ukraine and United Arab Emirates
- Asia Pacific (AP): Cambodia, Japan, Korea
Included with the PDUs
The PDU unit is delivered in a corrugated box and contains:
- One Power Distribution Unit with an attached power cord
- Network Management Controller (NMC is pre-installed)
- Plugs and wires
- Safety information sheet
- Quick start guide
- Warranty card
Figure 2. Lenovo 0U Switched and Monitored PDUs
This figure displays various Lenovo 0U Switched and Monitored PDUs. Each unit shows a different configuration of C13, C15, and C19 outlets, along with circuit breakers. Part numbers and outlet counts are indicated for each.
Features and specifications switched and monitored PDUs
The 0U Switched & Monitored PDUs have the following common and intelligent features like:
- Advanced features, such as color-coded with locking IEC outlets
- Enlogic's standard low-profile design
- Toolless mounting
- Operate reliably in high temperature environments.
- Sleek and space saving unit with low profile circuit breakers
- Color-coded receptacles and different type of power outlets which can be customized according to needs and IT requirements.
- Support Network Management Module and alerting capabilities supporting HTTP, HTTPS, SSH, SNMP, and email.
- Support encryption, passwords, and advanced authorization options including local permissions, LDAP/S, and Active Directory.
- Daisy Chain up to 64 Rack PDUs and supports a maximum of 10 environmental sensors each (sensors are optional)
- Power Sharing feature that allows the data of the PDU to be recorded even during a Power Failure.
- The Switched & Monitored PDUs also provide both current options with unique features:
- Single-Phase Models: All Single-Phase models support hydraulic magnetic breakers that are colour coded to the corresponding outlets.
- Three-Phase Models: In standard 415 V Three-Phase (Wye) configurations, the colour of each circuit breaker and outlet correspond to the appropriate input phase. The PDU is labelled to indicate the input-phase associated with each circuit breaker and outlets. In North America 208 V Three-phase (delta) configurations, the colour of the circuit breaker corresponds to the line connections and includes a label of the two connected input-phases.
Table 4. PDU specifications (Switched & Monitored PDUs)
Feature | 0U 20 C13 and 4 C19 Switched and Monitored 32A 1 Phase PDU | 0U 16 C13/C15 and 16 C13/C15/C19 Switched and Monitored 24A 1 Phase PDU(30A derated) | 0U 18 C13/C15 and 18 C13/C15/C19 Switched and Monitored 32A 3 Phase WYE PDU | 0U 21 C13/C15 and 21 C13/C15/C19 Switched and Monitored 48A 3 Phase Delta PDU (60A derated) | 0U 18 C13/C15 and 18 C13/C15/C19 Switched and Monitored 63A 3 Phase WYE PDU |
---|---|---|---|---|---|
Part Number | 4PU7A93171 | 4PU7A93172 | 4PU7A93173 | 4PU7A93174† | 4PU7A93175† |
Region | International | NA* | NA | International** | International |
Input power | |||||
Number of phases | Single phase input | Single phase input | Dual phase input | Three phase input | Three phase input |
Line cord | Attached line cord, 3 m length (10 ft) | Attached line cord, 3 m length (10 ft) | Attached line cord, 3 m length (10 ft) | Attached line cord, 3 m length (10 ft) | Attached line cord, 3 m length (10 ft) |
Line cord connector | 332P6, W+N+PE 1ph | NEMA L6-30P | 532P6, WYE, 3W+N+PE 3Ph IP67 (WATERTIGHT) | IEC460P9, Delta 3W+PE 3ph IP67 (WATERTIGHT) | IEC 60309, 4P 5W, 6H IP67 (WATERTIGHT) |
Plug design | Diagram showing plug with L, N, G pins. | Diagram showing plug with L, N, G pins. | Diagram showing plug with L1, L2, L3, N, G pins. | Diagram showing plug with L1, L2, L3, N, G pins. | Diagram showing plug with L1, L2, L3, N, G pins. |
Input voltage | 200-240V | 200-240V | 200-240V / 346-415V | 200-240V | 200-240V/ 346-415 V |
Input current | 30A (derated 24A) / 32A (EU) | 30A ( derated 24A ) / 32A (EU) | 30A (derated 24A) / 32A (EU) | 60A (derated 48A) | 60A (derated 48A) (NA) / 63A (EU) |
Maximum power rating | Dual-rated 5.0kVA (208V NOM) (NA) / 7.4kVA (230V NOM) (EU) | 5kVA (208V NOM) | Dual-rated 17.3 kVA (240V NOM )(NA) / 22.1 kVA (230V NOM ) (EU) | 17.3 kVA (208V NOM) | Dual-rated 34.6 kVA (240V NOM )(NA)/ 43.5 kVA (230V NOM )(EU) |
Output power | |||||
Number of outlets |
|
|
|
|
|
Output voltage rating at 50/60Hz | 200-240V | 200-240V | 200-240V | 200-240V | 200-240V |
Output current rating | Each C13 outlet: 10A; Each C19 outlet: 16A | Each C13/C15 Locking outlet: 10A; Each C13/C15/C19 Locking outlet: 16A | Each C13/C15 Locking outlet: 10A; Each C13/C15/C19 Locking outlet: 16A | Each C13/C15 combo outlet: 10A; Each C13/C15/C19 combo outlet: 16A | Each C13/C15 combo outlet: 10A; Each C13/C15/C19 combo outlet: 16A |
Circuit breakers | 2x 20A, single-pole electro mechanical switch | 2x 20A, double-pole electro mechanical switch | 2x 20A, single-pole electro mechanical switch | 6x 20A, single-pole electro mechanical switch | 12x 20A, single-pole electro mechanical switch |
Capacity per PDU (Amps) | 24A Total (NA) or 32A Total (EU) | 24 A | 24A Total (NA) or 32A Total (EU) | 48 A | 48A Total (NA) or 63A Total( EU) |
Mechanical and environmental | |||||
Physical dimensions (L x W x D) | 68.9 x 2.1 x 2.1 in 1750 x 52 x 53 mm | 58.7 x 2.2 x 2.9 in 1490 x 56 x 75 mm | 67.7 x 2.2 x 2.9 in 1720 x 56 x 75 mm | 67.7 x 2.3 x 2.9 in 1720 x 56 x 75 mm | 67.7 x 2.3 x 2.9 in 1720 x 56 x 75 mm |
Operating temperature | -5 TO 60 C (23 TO 140 F) | -5 TO 60 C (23 TO 140 F) | -5 TO 60 C (23 TO 140 F) | -5 TO 60 C (23 TO 140 F) | -5 TO 60 C (23 TO 140 F) |
Operating humidity | 5% to 95% without condensation | 5% to 95% without condensation | 5% to 95% without condensation | 5% to 95% without condensation | 5% to 95% without condensation |
† Planned ship support for these PDUs is 2Q/2024
* USA, Canada (single-phase)
** USA, Canada, and Japan (dual-phase).
Connectors and load groups
The 0U Basic PDU with 36x C13 and 6x C19 connectors (part number 4PU7A93169) have the components as shown in the following figure.
Figure 3. Connectors for Basic PDU (part number 4PU7A93169)
This figure illustrates the components of a Basic PDU. It shows the input power cord, outlets/receptacles, and a hydraulic magnetic circuit breaker, along with color-coded circuit breakers and outlets.
The 0U Switched and Monitored PDUs with 18x C13/C15 and 18x C13/C15/C19 connectors (part number 4PU7A93175) have the components and controls as shown in the following figure.
Figure 4. Connectors for Switched and Monitored PDU (part number 4PU7A93175)
This figure depicts the components and controls of a Switched and Monitored PDU. It shows the input power cord, outlets/receptacles, color-coded circuit breakers and outlets, and a swappable Network Management Controller (NMC) module.
Advanced Network Management
The Switched and Monitored PDUs include a hot-swappable Network Management Controller (NMC) that provides the interface and connectors to manage the PDU.
Features:
- Network Connectivity: Dual ports: 1x Gigabit Ethernet (10/100/1000 Mbps) and 1x (10/100 Mbps) connection/IP address
- Ethernet Cascading: Up to 64 units share a single "daisy-chain" Ethernet connection/IP address
- DC Power Sharing: Each PDU can provide DC power sufficient to power network management electronics and sensors in a neighboring PDU in the event of AC power source loss
- Dual Ethernet Support: Dual Ethernet ports for redundant communication
- Remote Connectivity: HTTP(s), iPV4 and iPV6, SSH, Virtual Serial, SNMP (v1, v2c, v3), JSON-RPC, LDAP(S), FTP/SFTP, RADIUS, Redfish DMTF RESTful API
- WebUI Interface: Data efficient REACT framework with native mobile device support
Figure 5. Interface of the Network Management Controller
This figure shows the LED screen and the ports of the NMC. The LED interface provides information about the load status, events, measurements, identification, and settings. It features an LED screen displaying AMPS, CB BANK, and load levels (L1, L2, L3), an OLED screen for Setup, Alarms, Power, and Sensors, USB-C and Ethernet interface ports, and a reset button. Navigation buttons (Menu, Select, Scroll) are also visible.
The components of the NMC are as follows:
- LED screen:
- Graphical alarm icon PDU Alarm
- Daisy Chain Indicator
- Environmental Sensor Alarm
- Security Sensor Alarm
- Circuit Breaker & outlet Alarm
- Source color coding - user selected option
Figure 6. LED screen source color coding samples
This figure displays examples of the LED screen with different "Source Color Coding" applied to the outlets and circuit breakers, showing various numerical values and load indicators.
- OLED Screen:
- Setup
- Alarms
- Power
- Sensors
- Reset button: Use this button to reset the PDU for communication purposes only. Resetting the PDU does not affect the outlets/loads.
Interface Ports
The NMC provides various interface ports:
- USB-C port: Use the USB connection to upgrade firmware and configuration file download/upload.
- Ethernet ports: Use for redundancy and cascading (daisy chain)
- 1x Gigabit Ethernet (10/100/1000 Mbps)
- 1x (10/100 Mbps)
- Serial ports:
- Digital Sensor port 1: dual function - sensor or serial connectivity. Use this port to open a serial connection to the PDU from your laptop.
- Digital Sensor port 2: sensor connectivity
- Supports up to 10 physical sensors (optional sensors such as: door open/close, fluid spot leak detector, humidity, temperature available thru Enlogic vendor)
Daisy chain port
Use ports to daisy chain two PDUs together. This setup enables multiple PDUs to connect over one Ethernet port. In daisy chain mode, up to 64 PDUs can be connected via one (1) IP address. This allows users to gather information and data of all daisy chained PDUs from the master PDU.
Figure 7. Daisy-chain PDU setup
This figure illustrates a daisy-chain PDU setup. It shows multiple PDUs connected via Ethernet ports, with a master PDU managing the chain.
RNA (Redundant Network Access) Functionality
Enlogic RNA allows to secure the access of PDU data and statistics on two separate private networks. RNA is used with a redundant power delivery design including two rack PDUs for each IT rack. PDUs are used in RNA applications that must be of the same SKU.
Figure 8. RNA setup with LAN
This figure shows a sample RNA setup with a Master PDU and a Slave PDU connected to Server A, demonstrating redundant network connectivity.
Browser interface
The PDU provides a graphical user interface that you can view from a web browser. Using a web browser, you can access and monitor the PDU power outlets and output devices remotely from a computer.
The following tasks can be performed though browser interface:
- Controls individual outlets (On/Off)
- Displays PDU current, watts, output power in VA, power factor, and frequency
- Displays outlet level voltage, power factor and cumulative KW hour output
- Sets outlet alarm thresholds
- Views temperature and humidity status where the PDU is located and set thresholds to trigger alarm notifications
- Views dry, humidity and temperature status
- Accesses a graphical historical view of PDU data for statistical trend analysis
- Views PDU Alarms
- Views Event/System Logs
Selecting the right PDU
To avoid over sizing or under sizing power, it is important to understand the power requirements of the hardware that will be powered by the PDU(s). A useful tool to leverage to help calculate overall power usage is the Lenovo Capacity Planner (LCP) https://datacentersupport.lenovo.com/us/en/solutions/lnvo-lcp.
Likewise, to avoid over sizing it is also important to understand the PDU capabilities and capacities.
Consider the following for capabilities:
- Do you require monitoring and/or outlet switching? If so, then consider the switched and monitored PDUs described here. If not, consider the Basic PDUs described above as well.
- Do you require environmental monitoring capabilities? If so, then consider the switched and monitored PDUs described here. If not, consider the Basic PDUs described above as well.
- Does the PDU have the right type of power for your scenario? For example, 16A, 30A, 32A, 63A and single or three phase power?
- Does the PDU have enough of the correct type of outlets for your scenario?
Consider the following for capacities:
- Will each outlet be able to support the load being connected to it? For example, C13 outlets have a 10A limit.
- Will each load group be able to support the hardware being connected to it?
- Will each phase, where applicable, be able to support the hardware being connected to it?
- Is the overall power capacity of the PDU able to support the hardware being connected to it?
- Do you have enough PDUs to be N+N or N+1 redundancy if this is required?
For additional information on selecting the right PDU, load groups, phases, outlets, line cords, plugs and specifications, reference tables above and/or vendor's nVent (CIS) site.
Supported rack cabinets
The 0U Switched and Monitored PDUs can be installed in the following racks:
- S2 42U Standard Rack cabinet (Types 9307)
- 42U 1200mm Deep Dynamic Rack (Type 9360)
- 42U 1200mm Deep Static Rack (Type 9361)
- 42U 1100mm Enterprise V2 Dynamic Rack (Type 9363)
- The 42U or 48U Heavy Duty Rack Cabinet (machine types 7D6D or 7D6E) are supported.
Enlogic PDUs are built with tool-less mounting in most rack enclosure designs.
These PDUs are designed to be mounted without the use of tools. Mounting buttons are pre-installed on the rear of the PDU at the factory. The mounting buttons allow for three mounting methods for installing the 0U Switched and Monitored PDUs vertically in a rack.
- Using factory-installed buttons on the PDU to mount the PDU in keyhole openings in the rack frame
For additional information on racking the 0U basic or Switched and Monitored PDUs, refer to User's Guide for the PDUs.
Warranty
The Lenovo zero-U (0U) Basic and Switched and Monitored power distribution units (PDUs) are offered with a three-year limited warranty. At Lenovo discretion this warranty will be either CRU service (customer replaceable unit) or a Lenovo employee, subcontractor or reseller will be assigned to repair the failing item. Proof and date of purchase is required for warranty claims.
Agency approvals
The PDUs conform to the following standards:
- CE, Demko Certified to IEC/EN60950-1
- ROHS, REACH
Related publications and links
For more information, see the following documents:
- Enlogic user manual basic PDUs: https://enlogic.com/product/EB0337
- Enlogic user manual switched and monitored PDUs: https://enlogic.com/product/EN6381
- Lenovo Capacity Planner (LCP): https://datacentersupport.lenovo.com/us/en/solutions/lnvo-lcp
Related product families
Product families related to this document are the following:
- Power Distribution Units
Notices
Lenovo may not offer the products, services, or features discussed in this document in all countries. Consult your local Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead. However, it is the user's responsibility to evaluate and verify the operation of any other product, program, or service. Lenovo may have patents or pending patent applications covering subject matter described in this document. The furnishing of this document does not give you any license to these patents. You can send license inquiries, in writing, to:
Lenovo (United States), Inc.
8001 Development Drive
Morrisville, NC 27560
U.S.A.
Attention: Lenovo Director of Licensing
LENOVO PROVIDES THIS PUBLICATION "AS IS" WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some jurisdictions do not allow disclaimer of express or implied warranties in certain transactions, therefore, this statement may not apply to you.
This information could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new editions of the publication. Lenovo may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time without notice.
The products described in this document are not intended for use in implantation or other life support applications where malfunction may result in injury or death to persons. The information contained in this document does not affect or change Lenovo product specifications or warranties. Nothing in this document shall operate as an express or implied license or indemnity under the intellectual property rights of Lenovo or third parties. All information contained in this document was obtained in specific environments and is presented as an illustration. The result obtained in other operating environments may vary. Lenovo may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you.
Any references in this publication to non-Lenovo Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this Lenovo product, and use of those Web sites is at your own risk. Any performance data contained herein was determined in a controlled environment. Therefore, the result obtained in other operating environments may vary significantly. Some measurements may have been made on development-level systems and there is no guarantee that these measurements will be the same on generally available systems. Furthermore, some measurements may have been estimated through extrapolation. Actual results may vary. Users of this document should verify the applicable data for their specific environment.
© Copyright Lenovo 2024. All rights reserved.
This document, LP1884, was created or updated on April 24, 2024.
Send us your comments in one of the following ways:
- Use the online Contact us review form found at: https://lenovopress.lenovo.com/LP1884
- Send your comments in an e-mail to: comments@lenovopress.com
This document is available online at https://lenovopress.lenovo.com/LP1884.
Trademarks
Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo in the United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at https://www.lenovo.com/us/en/legal/copytrade/.
The following terms are trademarks of Lenovo in the United States, other countries, or both: Lenovo®
The following terms are trademarks of other companies:
Active Directory® is a trademark of Microsoft Corporation in the United States, other countries, or both.
Other company, product, or service names may be trademarks or service marks of others.